[0001] Boilers using demineralized makeup water are known to be prone to caustic attack.
High pressure boilers are particularly susceptible to this type of metal corrosion.
[0002] The inside surfaces of the boiler are typically protected with magnetite. Hydroxide
ion, being the predominant anion in high purity boiler water, can dissolve the magnetite
when highly concentrated. Even though high purity water is being used, caustic can
nonetheless become highly concentrated, primarily due to the presence of iron oxide
deposits on radiant wall tubes. While the bulk water may contain only 5-10 ppm of
caustic, it is quite possible to have localized caustic concentrations of up to 100,000
ppm. The iron oxide deposits are extremely porous so that water is drawn thereinto.
Due to heat being applied from beneath, steam is generated and passes out of the porous
deposit, while fresh water is again drawn thereinto. The result is the noted high
concentrations of caustic which must be dealt with if the boiler is to properly be
protected..
[0003] A widely used method for controlling caustic corrosion in boilers using demineralized
(high purity) makeup water, particularly in high pressure boilers, is the coordinated
phosphate/pH control treatment. This method of treatment is detailed in an article
by George Gibson entitled "The Basics of Phosphate-pH Boiler Water Treatment", Power
Engineering, February, 1978, p. 66, which article is incorporated herein by reference
to the extent necessary to complete this disclosure. In any event, portions are excerpted
below for purposes of explanation.
[0004] The coordinated phosphate/pH corrosion control treatment is based on two principles:
first, that sodium phosphates are a pH buffer; and second, that disodium hydrogen
phosphate converts potentially corrosive caustic into relatively harmless trisodium
phosphate according to the following equation:

Accordingly, general corrosion is prevented through the control of boiler water pH,
and adherent deposits with concomitant caustic corrosion are prevented by maintaining
a disodium hydrogen phosphate residual in the boiler water to react with caustic according
to equation (1).
[0005] The program is implemented with a control chart such as in Figure 1. Disodium hydrogen
phosphate is present if the coordinate of pH and phosphate lies within the control
boundary.
[0006] Many sodium phosphates are used in boiler water-treatment. Of these, orthophosphates
are preferred. Complex phosphates, in the form of polymer chains, break down into
orthophosphates at boiler water temperatures by a process known as reversion. The
orthophosphates are monosodium dihydrogen phosphate (MSP), disodium hydrogen phosphate
(DSP) and trisodium phosphate (TSP).
[0007] Orthophosphates can be identified by name, formula or sodium-to-phosphate ratio which
can be expressed with the notation "Na:P0
4", read as sodium-to-phosphate ratio.
[0008] Monosodium dihydrogen phosphate has one mole of sodium per mole of phosphate. Therefore,
the sodium-to-phosphate ratio is one- to-one (Na:P0
4 = 1:1). Disodium hydrogen phosphate, with two moles of sodium per mole of phosphate,
has a Na:P0
4 = 2:1, and trisodium phosphate has a Na:P0
4 = 3:1.
[0009] Sodium-to-phosphate ratios are useful to describe mixtures of phosphates in solution.
For example, solutions of DSP and TSP have a Na:P0
4 between 2:1 and 3:1. The Na:P0
4 is fairly proportional to the mix ratio. For instance, a solution of half DSP and
half TSP has a ratio of about 2.5:1 (it is actually 2.46:1 because DSP and TSP have
different molecular weights).
[0010] Figure 2 shows the relation between solution pH and phosphate concentration for various
sodium-to-phosphate molar ratios. Examination of the figure reveals pH increases with
increasing Na:P04,:(at equal phosphate concentrations). Accordingly, solution pH and
phosphate concentration identify phosphate form, it being kept in mind that disodium
hydrogen phosphate is the species which neutralizes caustic according to equation
(1).
[0011] A trisodium phosphate solution exists if the phosphate/pH coordinate falls on the
Na:P0
4 = 3:1 line; disodium hydrogen phosphate solution if the coordinate falls on the 2:1
line; and a mixture of DSP and TSP if the coordinate falls between the 2:1 and 3:1
lines. As the coordinate approaches the 3:1 line, there is more and more TSP and less
and less DSP in the solution.
[0012] The solution is a mixture of TSP and caustic if the coordinate falls above the 3:1
line. In this "free caustic" region there is no DSP to tie up the caustic.
[0013] It is seen that the phosphate/pH coordinate must be below the Na:P0
4 = 3:1 line to ensure that there is DSP in solution to tie up the caustic. The further
the phosphate/pH coordinate is kept below the line the greater the caustic-absorbing
capacity of the water and the less chance of drifting into the region above the 3:1
line.
[0014] Figure 2 is based on pure sodium phosphate solution. The pure solution theory can
be used with impure boiler water because the concentration of other species is low
and their solubility high. Complex chemistry is avoided-by using pH as a variable.
It is desirable to keep the Na:P0
4 between 2.8:1 and 2.2:1. The phosphate- pH control chart, Figure 1, is a refinement
of Figure 2 with a control boundary in the appropriate range to prevent caustic corrosion.
The control chart is the heart of phosphate-pH control.
[0015] There has been some confusion in applying sodium-to-phosphate ratios. The Na:P0
4 used in phosphate-pH control is determined only from boiler water pH and phosphate
concentration, not by measuring sodium and phosphate concentrations of the boiler
water.
[0016] This information can be used to make a phosphate-pH control chart by first setting
phosphate limits. Maximum allowable phosphate decreases with increasing boiler pressure
because of carryover and phosphate "hideout." The latter term, incidentally, refers
to the phenomenon of diminishing boiler water phosphate levels with increased firing
rate (everything else held constant) and the reappearance of boiler water phosphate
level when the firing rate is reduced. Hideout phosphate is believed to be caused
by precipitating the phosphates under high heat flux conditions.
[0017] Individual plants have set their own phosphate limits, based on what works for them
and on results at similar installations. The limits chosen for the control chart shown
in Figure 1 are consistent with industry practice and have proved to be satisfactory
in practical applications.
[0018] Note that the residual phosphate limits contained in the control chart (Figure 1)
are the maximum levels recommended for satisfactory boiler operation. Whatever the
allowable residual phosphate concentration, it is prudent to operate with as little
phosphate as practicable.
[0019] There should be an upper Na:P0
4 limit of 2.85:1 to prevent caustic corrosion and a lower Na:P0
4 limit of 2.13:1 to prevent acid attack. But, it would be prudent to include a safety
factor into these numbers,which safety factor depends on individual boiler characteristics
and system water tightness. Lower pressure boilers have less trouble with caustic
corrosion than higher pressure boilers and generally can be run with Na:P0
4 close to the 2.85:1 line. Of course, if caustic corrosion is occurring, a lower maximum
limit should be set for the boilers involved. High pressure boilers tend to be more
susceptible to caustic corrosion, and a maximum Na:P0
4 line of 2.6:1 usually is chosen. This has proved to be an effective limit.
[0020] It should be understood from the foregoing that the coordinated phosphate/pH control
treatment consists primarily of two basic steps as follows:
(1) maintenance of an appropriate level of residual orthophosphate in the boiler water;
and
(2) maintenance of the proper Na:P04 ratio in the water.
[0021] The residual orthophosphate level will depend on such known factors as the nature
and severity of the problem and boiler pressure. Since it is considered best to operate
with as little phosphate as possible, amounts as low as about 1 ppm could be used,
with about 2 ppm being the preferred minimum. While amounts as high as about 50 ppm
residual orthophosphate could be used, about 30 ppm is the preferred maximum.
[0022] While the coordinated phosphate/pH corrosion control treatment is widely used, it
is not without its drawbacks and limitations. Often, it is desirable to supplement
the treatment with additional corrosion inhibitor; however, this is not always practicable.
It has been customary for many years to use the sodium salt of a polymeric dispersant,
such as sodium polymethacrylate, as the supplement. When the sodium salt form is used,
the Na:P0
4 in the boiler water is often significantly altered and the solids level of the boiler
water rises. If the Na:P0
4 is allowed to rise over the 3:1 line of Figure 2, caustic attack again becomes a
problem, and, particularly in high pressure boiler systems, increased solids levels
can lead to undesirable foaming in the water. Thus, the use of supplemental treatment
has been severely limited. In fact, when the Na:P0
4 is near the control limit, the supplemental treatment has been completely omitted.
[0023] The present invention relates to an improvement in the coordinated phosphate/pH corrosion
control treatment for boiler water. According to the present invention, a supplemental
corrosion inhibitor is provided which neither significantly alters the sodium burden
of the boiler nor significantly increases the solids level therein.
[0024] The present invention is drawn to the use, in conjunction with a coordinated phosphate/pH
corrosion control treatment, of an aqueous solution of an organic acid dispersant
which has been neutralized with any one of a class of specific amines, hereinafter
referred to as "alpha" amines. More specifically, according to the present invention,
the organic acid dispersant is neutralized with a suitable amine (or NH
3) which is volatile under the conditions of the boiler water to be treated and has
a basicity constant of 8.0 or less. A detailed description of how to determine suitable
amines is presented below.
[0025] The invention offers certain advantages as follows:
(1) the sodium burden in the boiler is limited, thus limiting caustic gouging and
other forms of boiler metal corrosion;
(2) advantage (1) is accomplished with volatile materials that do not concentrate
in the boiler and, thereby, do not contribute to either corrosion or deposition processes;
and
(3) the supplemental material will aid in corrosion control in both the boiler and
in the steam distribution system (due to volatile neutralizing agents).
[0026] The utility of the present invention is considered to be greatest for those high
pressure (above about 900-1200 psig) boiler systems experiencing difficulty in maintaining
a Na:P0
4 less than 2.8:1. The use of a low sodium supplement under these conditions does not
contribute to the sodium burden of the boiler, thereby simplifying the maintenance
of a coordinated phosphate/pH control treatment, i.e., supplemental feed to the boiler
feedwater can be made without disrupting the sodium to phosphate ratio.
[0027] According to the present invention, a supplemental corrosion inhibitor is provided
in which a volatile organic base has replaced caustic as a neutralizing agent. This
resulting alkaline product is considered to be preferable to an acidic product. Furthermore,
the volatile organic base finds utility as a condensate corrosion inhibitor, neutralizing
carbonic acid at steam condensation sites.
The Organic Acid
[0028] Any reference hereinafter to the polymers used in accordance with the present invention
is intended to include the polymers individually as well as any combination of homopolymer,
copolymer and mixtures thereof. The term "polymeric acid" is intended to include any
polymer containing acid functional group(s), as well as acid precursor compounds (e.g.,
anhydrides).
[0029] As already noted, the compounds which are considered to be useful in practicing the
present invention are any of the well known organic acid dispersants, such as polymeric
sulfonic acids, polymeric phosphonic acids, polymeric carboxylic acids and poly phosphonic
acids.
[0030] Illustrative examples of polymeric carboxylic acids would be as follows:
polyacrylic acid
polymethacrylic acid
polymaleic anhydride
acrylic acid/hydroxypropylacrylate copolymer
sulfonated styrene/maleic anhydride copolymer
methylvinyl ether/maleic anhydride copolymer
acrylic acid/methacrylic acid copolymer
[0031] Illustrative examples of polymeric sulfonic acids would be as follows:
sulfonated polystyrene
polyvinylsulfuric acid
sulfonated styrene/maleic anhydride copolymer polyvinylsulfonic acid
poly[2-acrylamido-2-methylpropanesulfonic acid]
[0032] Illustrative examples of poly phosphonic acids would be:
ethylenediamine tetra(methylene phosphonic acid) 1-hydroxyethylidene-1,1-diphosphomc
acid nitrilotri(methylene phosphonic acid)
[0033] These compounds are believed to be useful in boilers of up to about 1500 psig.
[0034] The polymeric phosphonic acids are believed to be suitable for use at pressures up
to well above 1500 psig; however, few are presently commercially available. Illustrative
examples of these compounds are polyvinyl phosphonic acid and its substituted analogs.
[0035] As is well known in the art, the amount of supplemental corrosion inhibitor would
depend on such factors as the nature and severity of the problem to be treated and
could vary over a wide range. The amount of organic acid could, accordingly, be as
low as about 1 part polymer per million parts of boiler water (ppm). The preferred
minimum is considered to be about 5 ppm. Based on economic considerations, the upper
limit for the organic acid dosage is considered to be about 150 ppm; while 50 ppm
represents the preferred maximum.
[0036] With respect to the polymeric organic acids, it is well known that molecular weight
is not critical. In any event, a molecular weight of from about 1000 to about-200,000
is believed to be operable.
The Neutralizing Agent
[0037] Suitable amines for use as neutralizing agents in accordance with the present invention
have already been described as alpha amines. The important properties of these amines
are, first, that they are volatile under the operating conditions of the boiler and,
second, that they have sufficient basicity to neutralize the organic acid dispersant.
Defining the first property in terms of distribution ratio and the second in terms
of basicity constant, pK
b, alpha amines are those having a distribution ratio of 0.01 or greater under the
operating conditions of the boiler and a pK
b of 8.0 or less.
[0038] The distribution ratio, DR, is defined as the quantity of voltile amine found in
the steam phase over the quantity found in the bulk fluid and is represented by:

[0039] The values for this ratio, of course, are easily obtained by drawing a condensed
steam sample and a blowdown sample from the boiler and analyzing for respective amine
contents.
[0040] The basicity constant is a well known comparison for basicities of amines in terms
of their respective abilities to accept hydronium ion from water. Using the reaction:

the basicity constant, pK
b, is defined by:

Each amine has its own pK
b, and, the lower the value, the stronger the base. As is well known to the artisan,
tabulated values for pK
b's are readily obtainable from numerous chemical reference books. For example, a table
of such values can be found in the "Handbook of Chemistry and Physics", The Chemical
Rubber Co., 45th Edition (1964-1965), p. D-76.
[0041] Following is an exemplary list of alpha amines believed to be suitable for use in
accordance with the present invention:
morpholine
aminomethylpropanol (AMP)
dimethylaminomethylpropanol (DMAMP)
cyclohexylamine
dimethylpropanolamine (DMPA)
diethylaminoethanol
N-hexylamine
methoxypropylamine (MPA)
benzylamine
ammonia
monoisopropanolamine
1,6 hexanediamine
1,3 diaminopropane
tributylamine
triethylamine
n-amylamine
n-methylmorpholine
N,N-dimethyl-1,3 propanediamine.
EXAMPLES
Determining Distribution Ratios
Example 1
[0042] A first series of tests were conducted to determine the DR's of various amines using
a research boiler similar to the one schematically illustrated in Figure 3. Two fiberglass
feed tanks were filled with a total of 600 liters of deionized water which was deaerated
by nitrogen sparging for two hours. At the end of the deaeration period one tank was
charged with 50 ppm amine, while the other was charged with various chemicals to provide
boiler test water as follows:
"P" alkalinity = 200 ppm
residual silica = 20 ppm, added as sodium metasilicate
residual phosphate = 20 ppm, added as sodium dihydrogen phosphate
residual sulfite = 20 ppm, added as sodium sulfite calcium hardness = 10 ppm, added
as calcium chloride magnesium hardness = 5 ppm, added as magnesium sulfate cycles
of concentration = 15 ppm
02 level after N2 sparging = 0.25-0.5 ppm
[0043] The boiler was energized and allowed to come to equilibrium overnight at 100 psig.
On the second through fifth days two sets of samples (each set consisted of a steam
sample and a blowdown sample) were taken per pressure step at a minimum of one hour
and a maximum of one and a half hours between sets (at a given pressure). The samples,
refrigerated during the accumulation stage in glass containers, were then analyzed
using standard gas chromatographic procedures under the following conditions:
G.C. unit: Perkin Elmer Model 990
Detector(s): Thermal conductivity or flame ionization Column Size: 6' x 2 mm id Pyrex
Packing: 14% Carbowax 20 M/2% KOH on 80/100 mesh Supelcoport Oven Temperature: 110°C
.Carrier Gas: N2 at 20 ml/min at 40 psig
Sample Size: 1 µl
Injection Temperature: 105°C.
[0044] The resulting distribution ratios, calculated according to equation (I), are reported
below in Table 1. Also reported are the dissociation constants, pK
b, for the materials tested.

Example 2
[0045] An investigation was undertaken to determine the possible effects, if any, of boiler
chemicals or water quality on DR. The testing method used was similar to that reported
in Example 1. In the present test, however, water "P" alkalinity was increased by
a factor of two; and in the comparative "without chemical" tests, the hardness, phosphates
and silicates were removed completely. Some results of these tests are reported below
in Table 2 in terms of comparative average DR values with chemicals and without chemicals.
All DR's reported are averages of at least two to nine separate data points.

[0046] The results of Table 2 are seen to indicate that over the pressure range of interest,
with respect to practicing the present invention, no significant effect on DR was
noted due to either the absence of boiler chemicals or an increase in alkalinity.
Example 3
[0047] Also investigated was the effect, if any, of increased neutralizing amine concentration
on the various DR's. This was accomplished by simply doubling the amine concentration
from 50 ppm to 100 ppm and comparing the results. A testing method similar to that
reported in Example 1 was used. The amines tested were morpholine and cyclohexylamine.
The results of these tests are reported below in Table 3 in terms of comparative average
DR at 50 ppm and 100 ppm.

[0048] Based on the results from Table 3, there is seen to be no significant effect of amine
concentration on the DR. Of course, the individual values for quantity of amine present
in the steam and blowdown samples increased significantly, but the magnitude of the
DR still remained about the same.
MAKING AMINE-NEUTRALIZED ORGANIC ACID
Example 4
[0049] This example is seen to illustrate the preparation of an aqueous solution of alpha
amine-neutralized organic acid to be used in accordance with the present invention.
The starting material was polymethacrylic acid (PMA) having the formula:

which polymer had a molecular weight average of 6,000 to 12,000 as determined by gel
permeation chromatography, using as reference a commercial sodium polymethacrylate
of advertised molecular weight of 8,000-10,000.
[0050] A stock solution is made by the following procedure:
1. weigh out 250 g of tap water (pH = 8.2)
2. add 65 g of PMA (30.8% actives)
3. mix well
4. record pH and neutralize to desired pH with amine
[0051] At this point, the 4% PMA solution is reweighed and the amount of amine used is recorded.
The solution is brought to a final weight of 500 g and a final pH reading is taken.
The tap water added increased the pH by about .2 units.
[0052] The weights of the amine used to reach various pH's for numerous solutions actually
made were as follows:
Solution 1: 4% PMA stock solution, 500 g total weight, pH about 2.5
Solution 2: Solution 1 neutralized to pH = 7 with 17.5 g of morpholine; final pH =
7.2
Solution 3: Solution 1 neutralized to pH = 7 with 18.0 g of AMP; final pH = 7.1
Solution 4: Solution 1 neutralized to pH = 7 with 17.2 g of cyclohexylamine; final
pH = 7.0
Solution 5: Solution 1 neutralized to pH = 9.5 with 211.3 g of morpholine; final pH
= 9.7 (this solution less than 4% PMA)
Solution 6: Solution 1 neutralized to pH = 10 with 25.5 g of AMP; final pH = 10.0
Solution 7: Solution 1 neutralized to pH = 7 with 15.5 g of morpholine, then to pH
= 10.8 with 59.7 g of AMP; final pH = 10.9
Solution 8: Solution 1 neutralized to pH = 7 with 18.2 g of morpholine, then to pH
= 10.9 with 53.7 g of cyclohexylamine; final pH = 11.1
Solution 9: Solution 1 neutralized to pH = 7 with 18.4 g of morpholine, then to pH
= 9.8 with 46.8 g of AMP; final pH = 10.1
Solution 10: Solution 1 neutralized to pH = 7 with 19.0 g of morpholine to pH = 9
with 11.1 g of AMP, then to pH = 11 with 37.9 g of cyclohexylamine; final pH = 11.0
Solution 11: Solution 1 neutralized to pH = 7 with 24.1 g of morpholine, to pH = 9
with 15.3 g of AMP, then to pH = 11 with 8.9 g of sodium hydroxide anhydrous; final
pH = 11.5
Solution 12: Solution 1 neutralized to pH = 8 with 21.2 g of morpholine; final pH
= 8.0
Solution 13: Solution 1 neutralized to pH = 7.5 with 22 g of AMP; final pH = 8.0
Solution 14: Solution 1 neutralized to pH = 8 with 20.9 g of cyclohexylamine; final
pH = 8.1
Example 5
[0053] This example is seen to further illustrate the preparation of an aqueous solution
of alpha amine-neutralized organic acid to be used in accordance with the present
invention. The starting material was Acrysol A - 41, commercially available from Rohm
and Haas. It is a copolymer of methacrylic and acrylic acid, having a molecular weight
average of about 10,000-12,000 and a mole ratio of methacrylic acid to acrylic acid
of about 9:1.
[0054] A stock solution is made according to the same procedural steps set forth in the
preceding example, however, (71.5 g of) Acrysol A-41 (28% actives) was used instead
of the PMA.
[0055] The weights of the amine used to reach various pH's for numerous solutions actually
made were as follows:
Solution 1: 4% copolymer stock solution, 500 g total weight, pH about 2.65
Solution 2: Solution 1 neutralized to pH = 7 with 19.3 g of morpholine; final pH =
7.2
Solution 3: Solution 1 neutralized to pH = 7 with 20.2 g of AMP; final pH = 7.2
Solution 4: Solution 1 neutralized to pH = 7 with 23 g of cyclohexylamine; final pH
= 7.6
Solution 5: Solution 1 neutralized to pH = 9.2 with 129.6 g of morpholine; final pH
= 9.4 (not stable at this pH)
Solution 6: Solution 1 neutralized to pH = 10 with 43.6 g of AMP; final pH = 10.2
Solution 7: Solution 1 neutralized to pH = 10 with 35.5 g of cyclohexylamine; final
pH = 10.1
Solution 8: Solution 1 neutralized to pH = 7 with 21.7 g of morpholine, then to pH
= 9 with 13.6 g of AMP, then to pH = 10.8 with 114 g of cyclohexylamine; final pH
= 11.1
EFFICACY OF TREATMENT IN BOILER
Example 6
[0056] A series of tests were conducted to determine the efficacy of alpha amine-neutralized
organic acids as boiler water treatments. The tests were conducted in the research
boiler described in Example 1 and schematically illustrated in Figure 3. As already
noted, certain boilers are highly susceptible to caustic corrosion as a result of
iron oxide deposits formed on interior surfaces. Thus, any treatment which will prevent
the formation of iron oxide deposits is considered to be a highly desirable supplement
for a coordinated phosphate/pH control program.
[0057] Since the research boiler was electrically powered using immersion heating probes,
deposits formed directly on probe surfaces. On completion of the tests, the deposits
formed on the heating probes were analyzed to determine the quantity of iron oxide
present and the total amount of deposit.
[0058] During the tests performed, boiler conditions included a . coordinated phosphate/pH
control program, 15 cycles of concentration, operating pressure of 1450 psig, 3.4
ppm Fe
+2 contaminated feedwater, and boiler probes of differing heat flux values. One probe
had a heat flux value of 240,000 BTU/ft
2/hr; while the other had a heat flux of 185,000 BTU/ft
2/hr. Test durations were 2 days.
[0059] The feedwater had the following composition:

[0060] The tests included comparative studies of alpha amine-neutralized polymeric acid
dispersants with commonly used polymeric acid dispersants as sodium salts. The materials
tested were as follows:
Comparative Product X: Commercial sodium polymethacrylate, reported molecular weight
= 6,000-8,000
Comparative Product Y: Commercial sodium polymethacrylate, reported molecular weight
= 8,000-10,000
Product A: Polymeric acid starting material of Example 5, neutralized with AMP, pH
= 10.0, stored at 120°F for three months before testing
Product B: Polymeric acid starting material of Example 5, neutralized with morpholine,
pH = 8.0, stored at 120°F for three months before testing
Product C: Polymeric acid starting material of Example 4, neutralized with morpholine
and AMP, pH = 10.3, stored at 120°F for three months before testing
Product D: Polymeric acid starting material of Example 4, neutralized with morpholine,
pH = 8.1, stored at 120°F for three months before testing
[0061] The results of these tests are reported below in Table 4 in terms of amount of iron
deposition (in g/ft
2) on the probes.

[0062] Based on the results reported in Table 4, not only are treatments according to the
present invention considered to be efficacious for boiler water, but they are seen
to compare favorably with treatments containing the sodium salts of the organic acids.
Accordingly, the coordinated phosphate/pH corrosion control treatment can be supplemented
with an organic acid treatment in a form which will neither adversely affect the critical
Na:P0
4 nor increase the solids level in the boiler water.
[0063] It should be kept in mind that the stronger the basicity of the alpha amine neutralizing
agent, the less amine required to neutralize the polymeric acid dispersant. To avoid
problems related to fungi growth, higher pH formulations, e.g., above 8.5, are preferred.
[0064] A preferred supplemental treatment composition for use with the coordinated phosphate/pH
corrosion control treatment is Solution 1 of Example 5 neutralized to pH = 8.5 with
27.3 grams of morpholine.
[0065] Having thus described the invention, what is claimed is: