[0001] The invention concerns a control and monitoring equipment for a gas burner applied
to a heat generator. The best known burner control and monitoring equipments are suited
to monitor different operation phases, such as the pre-ventilation of the combustion
chamber where the burner operates, the ignition of the flame preceded by the opening
of the solenoid valves for the inlet of the gas, the holding of said flame and a resting
period whenever the reference figure of the physical value pre-set in the heat generator
has been reached.
[0002] European and international safety rules foresee that when the pre-ventilation phase
has been completed, the control and monitoring equipment of the gas burner must monitor
the appearance of the flame within a period of time set by the rule, which is usually
3-5 seconds from the end of the pre-ventilation phase. If the flame does not appear
within such period of time, the burner equipment must shut down with the consequent
cut-off of the power supply to the solenoid valves monitoring the gas distribution.
In order to meet such safety requirement the usual known technique foresees for the
low-rate oil or gas burners to be supplied with a resistance wound on a bi-metallic
element, which, properly fed, causes a contact controlled by the bi-metallic element
to commutate within the time set by the rules, should the flame not ignite. On the
contrary, if the flame appears, the power supply to the resistance is cut off before
the time necessary for the bi-metallic element to intervene on the contact controlled
by it. With regard to high rate equipment, the bi-metallic element is replaced by
a timer which intervenes with the same above mentioned procedures.
[0003] If one of the two safety devices now described breakdown at the moment they should
intervene, the known technique does not foresee any reserve safety and, therefore,
the chance for the equipment to keep the gas valves fed without a flame burning exists.
This fact represents a highly dangerous situation, which the invention has the purpose
of overcoming.
[0004] The main purpose of the invention is to obtain a control and monitoring equipment
for gas burners which, in the transient period between the end of the pre-ventilation
phase and the ignition of the flame, foresees a double safety device such that the
second device can intervene if the first one breaks down. All of this has the purpose
of increasing the operating safety of the equipment and the prevention of accidents
caused by the failure of the shut-down to occur because of a breakdown not foreseen
by the rules.
[0005] These and other purposes which will be better illustrated hereinafter are reached
by a control and monitoring equipment for gas burners suited to control and monitor
the following phases: the pre-ventilation of the burner chamber, the ignition of the
flame, the holding of said flame, the resting period after the temperature of the
water in the boiler has been reached, comprising:
- at least one electric fan supplying the air necessary for the combustion;
- at least one safety solenoid valve placed before at least one solenoid valve for the
distribution of the gas;
- a device for the gas ignition;
- sensors of the physical value to be monitored and of the air pressure in the burner
having electrical contacts connected to said equipment;
- a logic circuit for the monitoring of the flame;
- a logic circuit for the count down of the pre-ventilation time and of the waiting
interval before the flame ignites (safety time), said logic circuit sending out first
impulses at the end of the pre-ventilation phase such that they cause the solenoid
valves of the gas distribution to open, and second impulses, just before the end of
the time interval before the flame ignition, of such intensity as to set the shutdown
relay of the equipment into conduction, wherein said equipment is characterized in
that said first impulses feed a first relay, the contacts of which close the circuit
feeding a second shutdown relay through a first resistance wound on a bi-metallic
element interacting with a commutable contact, said connection causing the equipment
to stop either through the intervention of the shutdown relay which opens the contact
connected to it and feeding the equipment or, in case of operating failure of said
shutdown relay, through the commutation of the contact interacting with the bi-metallic
element coupled with said resistance.
[0006] Advantageously, said first resistance wound on a bi-metallic element according to
the invention, acts as an alternative of the shutdown relay should the flame disappear
while the burner is in operation and should the shutdown relay break down.
[0007] A preferred embodiment of the invention also foresees another resistance wound on
the same bi-metallic element which allows the equipment to insure the performance
of the electric fan even after the water temperature of the boiler has been reached
when the equipment sensor has opened its contacts, should the flame sensor continue
to detect the flame.
[0008] This fact is particularly important since, should the solenoid valves for the gas
distribution break down, so that the gas continues to flow even after the closing
command has been given to the solenoid valves, the amount of air sufficient for keeping
the burner in operation until the flame goes off will be assured.
[0009] A preferred embodiment of the invention also foresee another resistance interacting
with another bi-metallic element which, with a proper circuit, will insure the shutdown
of the equipment if there already is a flame when starting or if, during the pre-ventilation
phase, the air necessary for the burner to work is insufficient.
[0010] The control and monitoring equipment for gas burners according to the invention will
now be described with reference to a particular wiring diagram given by way of illustration
only with the help of the enclosed tables referring to the various temporal phases
of the equipment performance, beginning from the moment in which the sensor for the
control of the physical value to be monitored gives the start signal to the equipment
until the latter performs its operation and then stops. Some intervention procedures
of the equipment intervening during operations of the burner which differ from the
rules will be also described. The drawings attached to the patent refer to the electronic
diagram of the equipment circuit according to the invention, wherein:
- Fig. 1 represents the equipment according to the invention soon after the thermostat
has disconnected;
- Fig. 2 shows the diagram of the equipment during the pre-ventilation phase;
- Fig. 3 shows the diagram of the equipment at the end of the pre-ventilation phase
with the solenoid valves for the gas distribution being energized and with the ignition
transformer being fed, but before the flame ignites;
- Fig. 4 shows the diagram of the equipment in case of normal operation before the second
regulating solenoid valve begins to be energized;
- Fig. 5 shows the diagram of the equipment during the normal operation of the burner;
- Fig. 6 shows the diagram of the equipment in case of shutdown at the end of the safety
period of time;
- Fig. 7 is the diagram showing the condition of the equipment if the flame ignites
during the pre-ventilation phase;
- Fig. 8 shows the diagram of the equipment when the pressure sensor senses the lack
of air at the start;
- Fig. 9 shows the diagram of the equipment, should the flame disappear while the burner
is working;
- Fig. 10 shows the diagram of the equipment should the combustion continue after the
thermostat has come on again.
THE DEVICE AT THE INSTANT 0+1.
[0011] As soon as the thermostat marked with TL in the diagram of Fig. 1 disconnects, for
instance because the lower limit temperature of the room or the lower limit temperature
of the water has been reached, the T relay is excited and, as a consequence, all the
contacts T1, T2, T3 and T4 are closed. Through the 1E contact, which is normally closed
the B relay, also called third relay, is also excited, then the B1 and B2 contacts
also close. The motor is energized through the PA contact which is connected with
the air pressure sensor, which at this time does not sense the presence of air yet.
Thus the M motor of the fan is fed and the pre-ventilation phase begins.
PRE-VENTILATION PHASE
[0012] With reference to Fig. 2 and to the power part of the equipment, as soon as the M
motor starts operating, the air pressure sensor senses the presence of a sufficient
pressure and the PA contact commutes, so as to excite the RPA2 relay.
[0013] The M motor of the fan presents a secondary winding at the ends of which the VBT
low tension is collected, said low tension feeding the entire logical part L for the
monitoring of the equipment which, as can be observed in Fig.2 is to be found after
the terminals 1, 2. The feeding of the monitoring circuit entails the feeding of the
A RF logic circuit and, through the latter the RPA1 relay is also fed.
[0014] The feeding of said relay causes the 1RPA1 contact to close. The closing of the 1RPA1
contact makes it possible for the M motor to continue to be fed, even if in the meantime
the PA contact has gone to its resting position from the feeding of the motor to the
feeding of the RPA2 relay. The feeding of the monitoring circuit of the equipment
also entails the energizing of the t1 timer, which starts counting down a period of
time, for instance of about 20÷70 seconds, this occurring as a function of the RC
time constant of the t1 circuit due to the R, R1 resistances placed in series and
to the inner capacity of the logic circuit of t1.
[0015] As can be observed, the feeding of the t1 circuit closes through the 2RF contacts.
END OF THE PRE-VENTILATION PHASE - OPERATION WITHOUT FLAME
[0016] At the end of the pre-ventilation phase, the circuit of the equipment sends out a
signal which opens the gas valves and also feeds a transformer connected with the
spark.
[0017] According to the safety rules the ignition of the flame must occur within a maximum
time span of 3 seconds from the end of the pre-ventilation.
[0018] For this reason, with reference to Fig. 3, when the electronic timer t1 has finished
the pre-ventilation phase and has therefore finished the count down of the time pre
set for the pre-ventilation, a first signal t1₁ is sent out by the logic circuit which
excites the RT relay and, as a consequence, its RT1 and RT2 contacts close. These
contacts permit a retention current through the BL2 resistance, also called second
resistance, through the 2RPA2, RT1, RT2, RTA contacts
Said retention current suffices to excite the first RTA relay. As a consequence the
contacts of said relay, namely the 1RTA and 2RTA contacts, close. The closing of the
1RTA contact causes the short circuit of the R resistance and, as a consequence, the
variation of the RC time constant of the logic circuit of t1. Thus the RC constant
of the circuit changes from 20 ÷ 70 seconds to a max. of 3 seconds.
[0019] The closing of the 2RTA contact with the 3RF contact in its resting position causes
the REV relay to be fed through the BLS1 resistance, also called first resistance.
The feeding of the REV relay entails the closing of the 1REV contact and, therefore,
the consequent feeding of the REV1 relay placed in series with the RL relay. During
this phase the RL relay is not excited.
[0020] During the time interval corresponding with the 3-second count down it occurs that,
since the REV and REV1 relays are excited, the corresponding EVS and EV1 solenoid
valves for the gas distribution are opened, the EVS valve being the safety valve placed
before the two EV1 and EV2 valves.
[0021] When the REV1 relay is excited, the 1REV1 contact also closes and, through the T3
contact and the 2RL contact, which is normally closed, it feeds the transformer feeding
the TR spark. Therefore, all the conditions for the ignition of the flame are present,
since the TR transformer feeding the spark and the EVS and EV1 solenoid valves for
the gas distribution are being fed.
THE FLAME IGNITES DURING THE SAFETY PERIOD OF TIME
[0022] As has previously been said, the safety rules foresee a period of time not exceeding
3 seconds after the end of the pre-ventilation phase within which the flame must ignite.
[0023] If the flame ignites, as can be observed in the diagram of Fig. 4, the A RF flame
sensor senses the ignition and all the contacts 1RF, 2RF, 3RF and 4RF, the last one
being also called first contact, are commuted. By commuting the 2RF contact, the t1
timer stops being fed, so that the count down and any signal output are stopped. By
subsequently commuting the 3RF contact so that, as a consequence the first BLS1 resistance
is no longer fed, the RL relay is fed at full voltage, so that the normally closed
2RL contact opens and the igniting spark stops because of the interruption of the
feeding of the TR transformer. The commutation of the 3RF contact causes the t2 timer
to start counting, so that for the purpose of counting a signal is sent out such that
it will excite the REV2 relay, as can be observed in Fig. 5.
NORMAL OPERATION
[0024] During the normal operation of the burner with the regular presence of the flame
it occurs that the EV2 solenoid valve also opens, since at the end of the count down
by t2 the REV2 relay is excited and the 1REV2 contact feeds the EV2 solenoid valve.
Therefore, during its normal operation, the burner is fed through the EVS safety valve
and the EV1 and EV2 valves.
SAFETY PERIOD OF TIME AT THE END OF THE PRE-VENTILATION PHASE
[0025] Within a maximum of three seconds from the end of the pre-ventilation it has been
said that the rules require for the flame to ignite. With reference to Fig. 6, if
the flame sensor does not sense the flame within this period of time, a few fractions
of a second before the three seconds have elapsed, the logic of t1 is such, that a
t1₂ second impulse, much stronger than the t11, which would send the RT relay into
conduction, is sent out by the logic circuit of t1. In this situation the second BL
relay also enters into conduction. The conduction of the second BL relay entails the
closing of the 1BL1 contact and, therefore, the opening of the circuit feeding the
part of power relating to the burner, thus sending the burner into a shutdown.
[0026] The operation can be reset by the user by manually commuting the 1BL1 contact.
CASE OF WORKING FAILURE OF THE ELECTRONIC CIRCUIT LOGIC DURING THE 3 SECONDS FOLLOWING THE PRE-VENTILATION PHASE
[0027] Always with reference to Fig. 6, should the logic circuit t1 interrupt the countdown,
or should a breakdown occur, thus causing the second impulse t1₂ to be sent out by
the logic circuit t1 so that the shutdown relay BL is activated, or should said second
shutdown relay BL, because of working failure, not start working, so that the feed
circuit does not stop, it happens that the gas continues to flow through the EVS and
EV1 solenoid valves, without the flame igniting, even though the TR ignition transformer
is activated.
[0028] In this case, since the first RTA relay is excited, the 1RTA and 2RTA contacts are
also closed and, through the REV relay, feed said first BLS1 resistance, which is
a resistance wound around a bi-metallic rod, which begins to heat up because of the
movement of the bi-metal. After a period varying from 3.1 to 5 seconds this bi-metallic
rod on which BLS1 is wound will commute the BLG1 contact. This commutation interrupts
the feeding of the entire logic of the monitoring circuit and, as a consequence, also
of the REV1 relay. This causes the opening of the REV1 contact which by opening stops
the feeding of the EVS and EV1 solenoid valves. Thus one more safety feature is obtained,
besides the traditional shutdown which occurs within the 3 seconds.
[0029] This safety feature intervenes regardless of the operation of the electronic logic,
since said safety feature depends on the electro-mechanic operation of a bi-metallic
rod commuting the contacts after a very brief heating-up period.
[0030] The BLG1 contact, the commutation of which has caused the shutdown of the equipment,
is protected so that it can not be accessible to the user, but only to specialized
personnel, whose intervention becomes necessary, since the commutation of the BLG1
contact has only occurred because of a failure of the BL shutdown relay, so that it
becomes important to replace it.
IN CASE THE FLAME IS IGNITED AT THE START OF THE OPERATION
[0031] When the contacts of the thermostat, i.e. the T1, T2, T3 and T4 contacts, close,
according to the diagram represented in Fig. 7, the M motor for the pre-ventilation
begins to be fed. At the same time the countdown of the logic circuit t1 should also
start. The presence of a flame which is sensed by the A RF circuit for the monitoring
of the flame, the 1RF, 2RF, 3RF 4RF contacts are commuted. As can be observed in Fig.
7, because of the position of the 2RF contact, the RC charge circuit of the time constant
of the timer t1 is not closed at this point, so that it is not possible for the first
impulse t1₁ to be sent out, since the countdown is interrupted. Since the A RF flame
monitoring contact is excited, the RPA1 relay is also excited and, as a consequence,
the 2RPA2 contact, also called second contact, is commuted and it permits, also through
the closing of said first 4RF contact, the feeding of said second BL shutdown relay
through the second BL2 resistance, which is also wound around a bi-metallic element,
deferring from the one previously described. Thus it occurs that if a flame is ignited
at the start up, the equipment foresees the immediate shutdown.
NO AIR IS PRESENT DURING THE PRE-VENTILATION PHASE
[0032] With reference to Fig. 9, during the normal operation of the burner the EVS, EV1,
EV2 solenoid valves for the gas distribution are open. When the flame goes out the
A RF system resumes its resting state, during which all the 1RF, 2RF, 3RF and 4RF
contacts re-open. By commuting the 1RF contact, said second BL relay is fed through
the second BL2 resistance, so that an immediate shutdown occurs, because the 1BL1
contact connected with said second BL relay opens.
[0033] If, however, for any reason, said second BL relay is not excited, the interruption
of the 3RF contact due to the disappearance of the flame entails the feeding of the
first BLS1 resistance which, as has been said, is wound around a bi-metallic element
and, therefore, after a period of time slightly exceeding 3 seconds, the bi-metal
closes the BLG1 contact and the system shuts down irreversibly.
POST-COMBUSTION SHUTDOWNS
[0034] With reference to Fig. 10, when the TL limit thermostat opens, the T relay is de-energized
and, as a consequence, all the T1, T2, T3 and T4 contacts open. When the T3 contact
opens the EVS safety solenoid valve is no longer energized. In the same way, the opening
of the T2 contact causes the solenoid valve of the REV2 relay to stop being energized.
As a consequence, the corresponding EV2 solenoid valve is no longer energized. If
no gas leaks out of the EVS safety solenoid valve, EV1 receives no gas, so that the
flame goes out. If the flame goes out, the A RF relay commutes again and consequently
the fourth E relay, which was kept in short circuit by the 2RF contact, is also excited.
Consequently the corresponding 1E contact also opens and it causes the third B relay
to open. The de-energizing of the third B relay causes also the opening of the contacts
connected with said relay, i.e. the B1 and B2 contacts, which cause the M motor to
stop: it then occurs that after the signal has been sent out by the limit thermostat,
the motor keeps on working as long as the logic circuit which senses the presence
of the flame insures that the flame is out.
[0035] On the other hand, should the flame continue to burn, because, for instance, some
gas still leaks out of the EVS safety solenoid valve, although it has been de-energized,
since the RF flame circuit is excited, the 2RF contact feeds, as can be observed in
Fig. 10, a third BLG resistance wound around the same bi-metallic element, around
which the first BLS1 resistance is wound. Said bi-metallic element permits, after
a certain pre-determined period of time, to close the irreversible BLG1 contact. When
BLG1 goes into commutation, the feeding of the REV1 relay stops, because the circuit
does not give enough voltage to feed said relay. As a consequence the EV1 solenoid
valve is no longer fed. If the closing of the EV1 solenoid valve suffices to put out
the flame, the 2RF contact goes into commutation, since it depends on the A RF circuit
and said circuit no longer senses the flame. Consequently said fourth E relay is fed
and the corresponding 1E contact opens. With the opening of the 1E contact the third
B relay is de-energized. As a consequence the B1 and B2 contacts open and the M motor
is no longer fed. In this situation the pre-combustion ventilation stops.
[0036] If, on the other hand, the flame keeps on burning after the EVS and EV1 solenoid
valves have closed, it occurs that, because the 2RF contact remains in the position
described and represented in Fig. 10, it continues to keep said fourth E relay de-energized.
Consequently the 1E contact remains closed, so as to insure the exciting of the third
B relay which, as a consequence keeps the B1 and B2 contacts closed, so that the feeding
of the M motor continues.
[0037] Therefore, should the flame continue to burn in spite of all the controls of the
gas solenoid valve being closed, the system foresees that the motor, which supplies
the combustion air, keeps supplying an amount of ventilation sufficient for the inlet
gas to burn, thereby creating the ideal condition preventing dangerous situations
due to the buid-up of unburnt gas.
1. A control and monitoring equipment for gas burners suited to control and monitor the
following phases: the pre-ventilation of the burner chamber, the ignition of the flame,
the holding of said flame, the resting period after the temperature of the water in
the boiler has been reached, comprising:
A) A power part (P) consisting of:
- at least one electric fan supplying the air necessary for the combustion;
- at least one safety solenoid valve (EVS) placed above at least one solenoid valve
(EV1) for the distribution of the gas;
- a device (TR) for the gas ignition;
- sensors (TL) of the physical value to be monitored and of the air pressure (PA)
in the burner having electrical contacts connected to said equipment;
B) a logic part (L) consisting of:
- a logic circuit (A RF) for the monitoring of the flame;
- a logic circuit (t1) for the count down of the pre-ventilation time and of the waiting
interval before the flame ignites, said logic circuit sending out a first impulse
(t1₁) at the end of the pre-ventilation phase such that it causes the solenoid valves
(EVS, EV1) of the gas distribution to open, and a second impulse (t1₂), just before
the end of the time interval before the flame ignition, of such intensity as to set
the shutdown relay (BL) of the equipment into conduction, should the flame not ignite,
characterized in that said first impulse (t1₁) feeds a first relay (RTA), the contacts
(1RTA, 2RTA) of which close the circuit feeding a second shutdown relay (BL) through
a first resistance (BLS1) wound on a bi-metallic element interacting with a commutable
contact (BLG1), said connection causing the equipment to stop either through the intervention
of the shutdown relay (BL) which opens the contact (1BL1) connected to it and feeding
the equipment or, in case of operating failure of said shutdown relay (BL), through
the commutation of the contact (BLG1) inter-acting with the bi-metallic element coupled
with said resistance (BLS1) (Fig. 6).
2. An equipment according to claim 1, characterized in that said first resistance (BLS1)
wound around said bi-metallic element is dimensioned in such a way, that the commutation
of the contact (BLG1) interacting with said bi-metallic element occurs after the output
of the second impulse (t1₂) of said count down logic circuit (t1) if the flame is
absent and if said second shutdown relay (BL) of the equipment fails to intervene
(Fig. 6).
3. An equipment according to claim 1, characterized in that the absence of the flame
while the burner is in operation without the opening of the contact (TL) connected
with the sensor measuring the figure of the reference physical value, causes the feeding
of said second shutdown relay (BL) and of said first resistance (BLS1) wound around
a bi-metallic element, suited to commutate a contact (BLG1) through the opening of
the contacts (1RF, 3RF) controlled by the flame monitoring logic circuit (A RF), said
contacts causing the shutdown of the equipment through the stop of said second shutdown
relay (BL) which opens the contact (1BL1) feeding the equipment or, should said second
shutdown relay (BL) fail to operate, through the commutation of the contact (BLG1)
connected with the bi-metallic element interacting with said first resistance (BLS1)
and having a commutation period of time which is longer than the time of intervention
of the shutdown relay (Fig. 9).
4. An equipment according to claim 1, characterized in that, at the beginning of the
operation and if the flame is present, the flame monitoring logic circuit (A RF) commutates
a first contact (4RF) which, together with a second contact (2RPA2) commuted by a
relay (RPA2), feeds said second shutdown relay (BL) through a second resistance (BL2)
wound around another bi-metallic element, said connection causing the shutdown of
the equipment through the intervention of said second shutdown relay (BL) which opens
the contact (1BL1) feeding the equipment.
5. An equipment according to claim 1, characterized in that, when the sensor (PA) of
the air pressure during the pre-ventilation phase senses the lack of air, the contacts
(1RPA2, 2RPA2) of the relay (RPA2) connected with said sensor (PA) feed said second
shutdown relay (BL) through said second resistance (BL2) wound around another bi-metallic
element, said connection causing the shutdown of the equipment through the intervention
of said second shutdown relay (BL) which opens the contact (1BL1) feeding the equipment
(Fig. 8).
6. An equipment according to claim 1, characterized in that when the figure of the reference
physical value to be monitored has been reached and the flame keeps on burning in
the burner after the solenoid valve for the gas distribution has been closed, the
electric feeding of the motor (M) of the electric fan supplying the combustion air
continues, said feeding action being insured by the closing of the contacts (B1, B2)
of a third relay (B) which is excited by the closed position of a normally closed
contact (1E) belonging to a de-energized fourth relay (E), said fourth relay (E) being
placed in series to a third resistance (BLG) wound around a bi-metallic element and
in parallel with a closed contact (2RF) belonging to the flame monitoring logic circuit
(A RF), said commutation excluding the short circuit of said fourth relay (E) placed
in series to said third resistance (BLG) and opening the normally closed contact (1E)
of said fourth relay (E) so as to interrupt the feeding of said third relay (B), the
open contacts (B1, B2) of which de-energize the motor (M) of the electric fan (Fig.
10).
7. An equipment according to the claims 1 or 3 or 6, characterized in that the resistances
(BLS1, BLG) which intervene respectively in case of breakdown of the timer logic at
the end of the pre-ventilation phase and if the flame continues to burn after the
end of the combustion, are wound around the same bi-metallic element activating the
same contact (BLG1).