[0001] The invention concerns a control and monitoring equipment for a gas burner applied
to a heat generator. The best known burner control and monitoring equipments are suited
to monitor different operation phases, such as the pre-ventilation of the combustion
chamber where the burner operates, the ignition of the flame preceded by the opening
of the solenoid valves for the inlet of the gas, the holding of said flame and a resting
period whenever the reference figure of the physical value pre-set in the heat generator
has been reached.
[0002] European and international safety rules foresee that when the pre-ventilation phase
has been completed, the control and monitoring equipment of the gas burner must monitor
the appearance of the flame within a period of time set by the rule, which is usually
3-5 seconds from the end of the pre-ventilation phase. If the flame does not appear
within such period of time, the burner equipment must shut down with the consequent
cut-off of the power supply to the solenoid valves monitoring the gas distribution.
[0003] European safety rules foresee an other safety device which provides a check of sealing
of the gas valves. Said check can be provided before the cycle of the burner starts
or when the reference figure of the physical pre-set value has been reached. When
in the equipment there are two valves of gas in series, the purpose of checking said
valves is to verify that at least one valve is sealed. If one of the valves does not
seal, the gas equipmet shuts off.
[0004] This kind of check system presents at least two drawbacks.
[0005] The first one drawback is that this check system uses expensive devices, expecially
for burners of low capacity.
[0006] Another drawback consists in the fact that, when the reference figure of the physical
value (i.e. temperature of the water) is reached and the flame of the burner does
not stop, said check monitoring devices shut down preventing the burner to work.
[0007] In this circumstance due to the lack of the right quantity of the combustion air,
the flame can stop, but the gas continues to flow; this is a high dangerous situation
because the gas unburnt can accumulate in the combustion chamber and can explode.
[0008] The purpose of the invention is to overcome the afore said drawbacks.
[0009] The main purpose of the invention is to carry out a control and monitoring equipment
for a gas burner which permits the working prefixed of the fan of the burner, if the
flame remains after the shut down of the electrovalve which controls the flow of the
gas when the prefixed temperature of the water of the heater is reached.
[0010] In such a way it is ensured the connect amount of the air to support the flame.
[0011] Another purpose to be reached is that the control and monitoring equipment stops
the motor of the fan of the burner after the disappearance of the flame.
[0012] These and other purposes which will be better illustrated hereinafter are reached
by a control and monitoring equipment for gas burners the main features of which are
according to claim 1.
[0013] According to the invention when the temperature of the medium to be monitored has
been reached, if the flame keeps on burning in the burner after the interruption of
the power to the solenoid valve for the gas safety, the electric feeding of the motor
of the electric fan supplying the combustion air keeps on, said feeding action being
insured by the closing of the contacts placed above the motor of the electric fan
of a first relay belonging to the power circuit and excited by the closed position
of a normally closed contact. Said normally closed contact belongs to a de-energized
second relay inserted in the logic part of the equipment and placed in series to a
first resistance wound around a bi-metallic element and in parallel with a closed
contact belonging to the flame monitoring logic circuit. The feeding of the motor
of the electric fan stops when the flame for the commutation of the contact belonging
to the flame monitoring logic circuit disappears. Said commutation excluds the short
circuit of the aforesaid second relay placed in series to said first resistance and
opens the normally closed contact of said second relay so as to interrupt the feeding
of said first relay and the open contacts of which de-energize the motor of the electric
fan.
[0014] Advantageously, the afore-said first resistance wound on a bi-metallic element according
to the invention, acts as an alternative of the shutdown relay should the flame disappear
while the burner is in operation and should the shutdown relay break down.
[0015] A preferred embodiment of the invention also foresees another resistance wound on
the same bi-metallic element which allows the equipment to insure the performance
of the electric fan even after the water temperature of the boiler has been reached
when the equipment sensor has opened its contacts, should the flame sensor continue
to detect the flame.
[0016] This fact is particularly important since, should the solenoid valves for the gas
distribution break down, so that the gas continues to flow even after the closing
command has been given to the solenoid valves, the amount of air sufficient for keeping
the burner in operation until the flame goes off will be assured.
[0017] A preferred embodiment of the invention also foresee another resistance interacting
with another bi-metallic element which, with a proper circuit, will insure the shutdown
of the equipment if there already is a flame when starting or if, during the pre-ventilation
phase, the air necessary for the burner to work is insufficient.
[0018] The control and monitoring equipment for gas burners according to the invention will
now be described with reference to a particular wiring diagram given by way of illustration
only with the help of the enclosed tables referring to the various temporal phases
of the equipment performance, beginning from the moment in which the sensor for the
control of the physical value to be monitored gives the start signal to the equipment
until the latter performs its operation and then stops. Some intervention procedures
of the equipment intervening during operations of the burner which differ from the
rules will be also described. The drawings attached to the patent refer to the electronic
diagram of the equipment circuit according to the invention, wherein:
- Fig. 1 represents the equipment according to the invention soon after the thermostat
has disconnected;
- Fig. 2 shows the diagram of the equipment during the pre-ventilation phase;
- Fig. 3 shows the diagram of the equipment at the end of the pre-ventilation phase
with the solenoid valves for the gas distribution being energized and with the ignition
transformer being fed, but before the flame ignites;
- Fig. 4 shows the diagram of the equipment in case of normal operation before the second
regulating solenoid valve begins to be energized;
- Fig. 5 shows the diagram of the equipment during the normal operation of the burner;
- Fig. 6 shows the diagram of the equipment in case of shutdown at the end of the safety
period of time;
- Fig. 7 is the diagram showing the condition of the equipment if the flame ignites
during the pre-ventilation phase;
- Fig. 8 shows the diagram of the equipment when the pressure sensor senses the lack
of air at the start;
- Fig. 9 shows the diagram of the equipment, should the flame disappear while the burner
is working;
- Fig. 10 shows the diagram of the equipment should the combustion continue after the
thermostat has come on again.
THE DEVICE AT THE INSTANT 0+1.
[0019] As soon as the thermostat marked with TL in the diagram of Fig. 1 closes, for instance
because the lower limit temperature of the room or the lower limit temperature of
the water has been reached, the T relay is excited and, as a consequence, all the
contacts T1, T2, T3 and T4 are closed. Through the 1E contact, which is normally closed
the B relay, also called third relay, is also excited, then the B1 and B2 contacts
also close. The motor is energized through the PA contact which is connected with
the air pressure sensor, which at this time does not sense the presence of air yet.
Thus the M motor of the fan is fed and the pre-ventilation phase begins.
PRE-VENTILATION PHASE
[0020] With reference to Fig. 2 and to the power part of the equipment, as soon as the M
motor starts operating, the air pressure sensor senses the presence of a sufficient
pressure and the PA contact commutes, so as to excite the RPA2 relay.
[0021] The M motor of the fan presents a secondary winding at the ends of which the VBT
low tension is collected, said low tension feeding the entire logical part L for the
monitoring of the equipment which, as can be observed in Fig.2 is to be found after
the terminals 1, 2. The feeding of the monitoring circuit entails the feeding of the
A RF logic circuit and, through the latter the RPA1 relay is also fed.
[0022] The feeding of said relay causes the 1RPA1 contact to close. The closing of the 1RPA1
contact makes it possible for the M motor to continue to be fed, even if in the meantime
the PA contact has gone to its resting position from the feeding of the motor to the
feeding of the RPA2 relay. The feeding of the monitoring circuit of the equipment
also entails the energizing of the t1 timer, which starts counting down a period of
time, for instance of about 20÷70 seconds, this occurring as a function of the RC
time constant of the t1 circuit due to the R, R1 resistances placed in series and
to the inner capacity of the logic circuit of t1.
[0023] As can be observed, the feeding of the t1 circuit closes through the 2RF contacts.
END OF THE PRE-VENTILATION PHASE - OPERATION WITHOUT FLAME
[0024] At the end of the pre-ventilation phase, the circuit of the equipment sends out a
signal which opens the gas valves and also feeds a transformer connected with the
spark.
[0025] According to the safety rules the ignition of the flame must occur within a maximum
time span of 3 seconds from the end of the pre-ventilation.
[0026] For this reason, with reference to Fig. 3, when the electronic timer t1 has finished
the pre-ventilation phase and has therefore finished the count down of the time pre
set for the pre-ventilation, a first signal t1
1 is sent out by the logic circuit which excites the RT relay and, as a consequence,
its RT1 and RT2 contacts close. These contacts permit a retention current through
the BL2 resistance, also called second resistance, through the 2RPA2, RT1, RT2, RTA
contacts
[0027] Said retention current suffices to excite the first RTA relay. As a consequence the
contacts of said relay, namely the 1RTA and 2RTA contacts, close. The closing of the
1RTA contact causes the short circuit of the R resistance and, as a consequence, the
variation of the RC time constant of the logic circuit of t1. Thus the RC constant
of the circuit changes from 20 ÷ 70 seconds to a max. of 3 seconds. The closing of
the 2RTA contact with the 3RF contact in its resting position causes the REV relay
to be fed through the BLS1 resistance, also called first resistance. The feeding of
the REV relay entails the closing of the 1REV contact and, therefore, the consequent
feeding of the REV1 relay placed in series with the RL relay. During this phase the
RL relay is not excited.
[0028] During the time interval corresponding to the 3-second count down it occurs that,
since the REV and REV1 relays are excited, the corresponding EVS and EV1 solenoid
valves for the gas distribution are open, the EVS valve being the safety valve placed
before the two EV1 and EV2 valves. When the REV1 relay is excited, the 1REV1 contact
also closes and, through the T3 contact and the 2RL contact, which is normally closed,
it feeds the transformer feeding the TR spark. Therefore, all the conditions for the
ignition of the flame are present, since the TR transformer feeding the spark and
the EVS and EV1 solenoid valves for the gas distribution are being fed.
THE FLAME IGNITES DURING THE SAFETY PERIOD OF TIME
[0029] As has previously been said, the safety rules foresee a period of time not exceeding
3 seconds after the end of the pre-ventilation phase within which the flame must ignite.
If the flame ignites, as can be observed in the diagram of Fig. 4, the A RF flame
sensor senses the ignition and all the contacts 1RF, 2RF, 3RF and 4RF, the last one
being also called first contact, are commuted.
[0030] By commuting the 2RF contact, the t1 timer stops being fed, so that the count down
and any signal output are stopped. By subsequently commuting the 3RF contact so that,
as a consequence the first BLS1 resistance is no longer fed, the RL relay is fed at
full voltage, so that the normally closed 2RL contact opens and the igniting spark
stops because of the interruption of the feeding of the TR transformer. The commutation
of the 3RF contact causes the t2 timer to start counting, so that for the purpose
of counting a signal is sent out such that it will excite the REV2 relay, as can be
observed in Fig. 5.
NORMAL OPERATION
[0031] During the normal operation of the burner with the regular presence of the flame
it occurs that the EV2 solenoid valve also opens, since at the end of the count down
by t2 the REV2 relay is excited and the 1REV2 contact feeds the EV2 solenoid valve.
Therefore, during its normal operation, the burner is fed through the EVS safety valve
and the EV1 and EV2 valves.
SAFETY PERIOD OF TIME AT THE END OF THE PRE-VENTILATION PHASE
[0032] Within a maximum of three seconds from the end of the pre-ventilation it has been
said that the rules require for the flame to ignite. With reference to Fig. 6, if
the flame sensor does not sense the flame within this period of time, a few fractions
of a second before the three seconds have elapsed, the logic of t1 is such, that a
t1
2 second impulse, much stronger than the t1
1, which would send the RT relay into conduction, is sent out by the logic circuit
of t1. In this situation the second BL relay also enters into conduction. The conduction
of the second BL relay entails the closing of the 1BL1 contact and, therefore, the
opening of the circuit feeding the part of power relating to the burner, thus sending
the burner into a shutdown.
[0033] The operation can be reset by the user by manually commuting the 1BL1 contact.
CASE OF WORKING FAILURE OF THE ELECTRONIC CIRCUIT LOGIC DURING THE 3 SECONDS FOLLOWING THE PRE-VENTILATION PHASE
[0034] Always with reference to Fig. 6, should the logic circuit t1 interrupt the countdown,
or should a breakdown occur, thus causing the second impulse t1
2 to be sent out by the logic circuit t1 so that the shutdown relay BL is activated,
or should said second shutdown relay BL, because of working failure, not start working,
so that the feed circuit does not stop, it happens that the gas continues to flow
through the EVS and EV1 solenoid valves, without the flame igniting, even though the
TR ignition transformer is activated.
[0035] In this case, since the first RTA relay is excited, the 1RTA and 2RTA contacts are
also closed and, through the REV relay, feed said first BLS1 resistance, which is
a resistance wound around a bi-metallic rod, which begins to heat up because of the
movement of the bi-metal. After a period varying from 3.1 to 5 seconds this bi-metallic
rod on which BLS1 is wound will commute the BLG1 contact. This commutation interrupts
the feeding of the entire logic of the monitoring circuit and, as a consequence, also
of the REV1 relay. This causes the opening of the 1REV1 contact which by opening stops
the feeding of the EVS and EV1 solenoid valves. Thus one more safety feature is obtained,
besides the traditional shutdown which occurs within the 3 seconds.
[0036] This safety feature intervenes regardless of the operation of the electronic logic,
since said safety feature depends on the electro-mechanic operation of a bi-metallic
rod commuting the contacts after a very brief heating-up period.
[0037] The BLG1 contact, the commutation of which has caused the shutdown of the equipment,
is protected so that it can not be accessible to the user, but only to specialized
personnel, whose intervention becomes necessary, since the commutation of the BLG1
contact has only occurred because of a failure of the BL shutdown relay, so that it
becomes important to replace it.
IN CASE THE FLAME IS IGNITED AT THE START OF THE OPERATION
[0038] When the contacts of the thermostat, i.e. the T1, T2, T3 and T4 contacts, close,
according to the diagram represented in Fig. 7, the M motor for the pre-ventilation
begins to be fed. At the same time the countdown of the logic circuit t1 should also
start. The presence of a flame which is sensed by the A RF circuit for the monitoring
of the flame, the 1RF, 2RF, 3RF 4RF contacts are commuted. As can be observed in Fig.
7, because of the position of the 2RF contact, the RC charge circuit of the time constant
of the timer t1 is not closed at this point, so that it is not possible for the first
impulse t1
1 to be sent out, since the countdown is interrupted. Since the A RF flame monitoring
contact is excited, the RPA1 relay is also excited and, as a consequence, the 2RPA2
contact, also called second contact, is commuted and it permits, also through the
closing of said first 4RF contact, the feeding of said second BL shutdown relay through
the second BL2 resistance, which is also wound around a bi-metallic element, deferring
from the one previously described. Thus it occurs that if a flame is ignited at the
start up, the equipment foresees the immediate shutdown.
NO AIR IS PRESENT DURING THE PRE-VENTILATION PHASE
[0039] With reference to Fig. 9, during the normal operation of the burner the EVS, EV1,
EV2 solenoid valves for the gas distribution are open. When the flame goes out the
A RF system resumes its resting state, during which all the 1RF, 2RF, 3RF and 4RF
contacts re-open. By commuting the 1RF contact, said second BL relay is fed through
the second BL2 resistance, so that an immediate shutdown occurs, because the 1BL1
contact connected with said second BL relay opens.
[0040] If, however, for any reason, said second BL relay is not excited, the interruption
of the 3RF contact due to the disappearance of the flame entails the feeding of the
first BLS1 resistance which, as has been said, is wound around a bi-metallic element
and, therefore, after a period of time slightly exceeding 3 seconds, the bi-metal
closes the BLG1 contact and the system shuts down irreversibly.
POST-COMBUSTION SHUTDOWNS
[0041] With reference to Fig. 10, when the TL limit thermostat opens, the T relay is de-energized
and, as a consequence, all the T1, T2, T3 and T4 contacts open.
[0042] When the T3 contact opens the EVS safety solenoid valve is no longer energized. In
the same way, the opening of the T2 contact causes the solenoid valve of the REV2
relay to stop being energized. As a consequence, the corresponding EV2 solenoid valve
is no longer energized. If no gas leaks out of the EVS safety solenoid valve, EV1
receives no gas, so that the flame goes out. If the flame goes out, the A RF relay
commutes again and consequently the fourth E relay, which was kept in short circuit
by the 2RF contact, is also excited. Consequently the corresponding 1E contact also
opens and it causes the third B relay to open. The de-energizing of the third B relay
causes also the opening of the contacts connected with said relay, i.e. the B1 and
B2 contacts, which cause the M motor to stop: it then occurs that after the signal
has been sent out by the limit thermostat, the motor keeps on working as long as the
logic circuit which senses the presence of the flame insures that the flame is out.
[0043] On the other hand, should the flame continue to burn, because, for instance, some
gas still leaks out of the EVS safety solenoid valve, although it has been de-energized,
since the RF flame circuit is excited, the 2RF contact feeds, as can be observed in
Fig. 10, a third BLG resistance wound around the same bi-metallic element, around
which the first BLS1 resistance is wound. Said bi-metallic element permits, after
a certain pre-determined period of time, to close the irreversible BLG1 contact. When
BLG1 goes into commutation, the feeding of the REV1 relay stops, because the circuit
does not give enough voltage to feed said relay. As a consequence the EV1 solenoid
valve is no longer fed. If the closing of the EV1 solenoid valve suffices to put out
the flame, the 2RF contact goes into commutation, since it depends on the A RF circuit
and said circuit no longer senses the flame. Consequently said fourth E relay is fed
and the corresponding 1E contact opens. With the opening of the 1E contact the third
B relay is de-energized. As a consequence the B1 and B2 contacts open and the M motor
is no longer fed. In this situation the pre-combustion ventilation stops.
[0044] If, on the other hand, the flame keeps on burning after the EVS and EV1 solenoid
valves have closed, it occurs that, because the 2RF contact remains in the position
described and represented in Fig. 10, it continues to keep said fourth E relay de-energized.
Consequently the 1E contact remains closed, so as to insure the exciting of the third
B relay which, as a consequence keeps the B1 and B2 contacts closed, so that the feeding
of the M motor continues.
[0045] Therefore, should the flame continue to burn in spite of all the controls of the
gas solenoid valve being closed, the system foresees that the motor, which supplies
the combustion air, keeps supplying an amount of ventilation sufficient for the inlet
gas to burn, thereby creating the ideal condition preventing dangerous situations
due to the buid-up of unburnt gas.
1. A control and monitoring equipment for gas burners suited to control and monitor the
following steps: pre-ventilation of the burner chamber, ignition of the flame, holding
of said flame, extinguishing said flame when a reference temperature of a medium to
be heated has been reached, comprising:
A) A power part (P) including and powering over a supply line:
- the electric motor (M) of at least one electric fan supplying the air necessary
for the combustion;
- at least one safety solenoid valve (EVS) placed upstream of at least one solenoid
valve (EV1) for the distribution of the gas;
- a device (TR) for the gas ignition; and further including:
- a sensor (TL) of the temperature of said medium to be monitored and a sensor of
the air pressure (PA) in the burner having respective electrical contacts (TL, PA)
connected to said equipment;
B) a logic part (L) consisting of:
- a logic circuit (A RF) for the monitoring of the flame;
- a logic circuit (t1) for the count down of the pre-ventilation time and of a ignition
interval within which a flame shall be detected, said logic circuit sending out a
first impulse (t11) at the end of the pre-ventilation step such that it causes the solenoid valves (EVS,
EV1) of the gas distribution to open, and a second impulse (t12) terminating the ignition interval and having such an intensity as to set a first
shutdown relay (BL) of the equipment into conduction, should the flame not be detected,
characterized in that when the temperature of said medium to be monitored has been
reached, if the flame keeps on burning in the burner after the interruption of the
power to the solenoid valve for the gas safety, the electric feeding of the motor
(M) of the electric fan supplying the combustion air keeps on, said feeding action
being insured by the closing of the contacts (B1, B2) placed above the motor (M) of
the electric fan of a first relay (B) belonging to the power circuit and excited by
the closed position of a normally closed contact (1E), said normally closed contact
belonging to a de-energized second relay (E) inserted in the logic part of the equipment,
said second relay (E) being placed in series to a first resistance (BLG) wound around
a bi-metallic element and in parallel with a closed contact (2RF) belonging to the
flame monitoring logic circuit (A RF), the feeding of the motor (M) of the electric
fan stopping when the flame for the commutation of the contact (2RF) belonging to
the flame monitoring logic circuit (A RF) disappears, said commutation excluding the
short circuit of said second relay (E) placed in series to said first resistance (BLG)
and opening the normally closed contact (1E) of said second relay (E) so as to interrupt
the feeding of said first relay (B), the open contacts (B1, B2) of which de-energize
the motor (M) of the electric fan (Fig. 10).
2. An equipment according to claim 1, characterized in that, when the monitoring temperature
has been reached and in case of flame ignition, the commutation of the contact (BLG1)
interacting with the bi-metallic element around which said first resistance (BLG)
is wound, causes the de-energizing of a relay (REV1), the contact (1REV1) of which
will open by closing the solenoid valve (EV1) for the distribution of the gas still
opened.
3. An equipment according to claim 1, characterized in that said first impulses (t11) sent out by the logic circuit (t1) at the end of the pre-ventilation step, feed
a first relay (RTA) belonging to the logic part of the equipment, the contacts (1RTA,
2RTA) of which close a circuit feeding a second shutdown relay (REV) through a second
resistance (BLS1) wound around a bi-metallic element interacting with a commutable
contact (BLG1), said connection causing the equipment to stop either through the intervention
of the first shutdown relay (BL) which opens a contact (1BL1) in the power part supply
line feeding the equipment or, in case of operating failure of said first shutdown
relay (BL), through the commutation of said commutable contact (BLG1) interacting
with the bi-metallic element (BLG) coupled with said second resistance (BLS1) (Fig.
6).
4. An equipment according to claim 3, characterized in that said second resistance (BLS1)
wound around said bi-metallic element is dimensioned in such a way, that the commutation
of the contact (BLG1) interacting with said bi-metallic element occurs after the output
of the second impulses (t12) of said count down logic circuit (t1) if the flame is absent and if said shutdown
relay (BL) of the equipment fails to intervene (Fig. 6).
5. An equipment according to claim 1, characterized in that the absence of the flame
while the burner is in operation without the opening of the contact (TL) connected
with the sensor measuring the valve of said medium temperature, causes the feeding
of said shutdown relay (BL) and a second resistance (BLS1) wound around a bi-metallic
element, suited to commutate a contact (BLG1) through the opening of the contacts
(1RF, 3RF) controlled by the flame monitoring logic circuit (A RF), said contacts
causing the shutdown of the equipment through the stop of said first shutdown relay
(BL) which opens the contact (1BL1) feeding the equipment or, should said shutdown
relay (BL) fail to operate, through the commutation of the contact (BLG1) connected
with the bi-metallic element interacting with said second resistance (BLS1) and having
a commutation period of time which is longer than the time of intervention of said
shutdown relay (Fig. 9).
6. An equipment according to claim 1, characterized in that, at the beginning of the
operation and if the flame is present, the flame monitoring logic circuit (A RF) commutates
a first contact (4RF) which, together with a second contact (2RPA2) commuted by a
relay (RPA1) excited by said flame monitoring logic circuit, feeds said first shutdown
relay (BL) through a third resistance (BL2) wound around another bi-metallic element,
said connection causing the shutdown of the equipment through the intervention of
said second shutdown relay (REV) which opens the contact (1BL1) feeding the equipment
(Fig. 7).
7. An equipment according to claim 1, characterized in that, when the sensor (PA) of
the air pressure during the pre-ventilation step senses the lack of air, the contacts
(1RPA2, 2RPA2) of the relay (RPA2) connected with said sensor (PA) feed said first
shutdown relay (BL) through said third resistance (BL2) wound around a bi-metallic
element, said connection causing the shutdown of the equipment through the intervention
of said first shutdown relay (BL) which opens the contact (1BL1) feeding the equipment
(Fig. 8).
8. An equipment according to the claims 1 or 3, or 6, characterized in that the resistances
(BLS1, BLG) which intervene respectively after the end of the combustion if the flame
is present and in case of breakdown of the timer logic at the end of the pre-ventilation
step, are wound around the same bi-metallic element activating the same contact (BLG1).