[0001] The present patent application relates to a canned motor pump used to extract water
from wells, capable of switching off automatically and immediately when the water
tap is turned off and switching on automatically when the water tap is turned on.
[0002] The canned motor pump according to the present invention has been designed to overcome
the serious drawback of the currently available canned motor pumps represented by
their manual operation.
[0003] The advantages of the pump according to the present invention will become evident
from a brief description of the state of the art.
[0004] Traditional canned motor pumps used to extract water from wells feature a rather
elongated cylindrical structure provided with a top cap used to hook the cable that
holds the pump inside the well and insert the power electric cable and the water delivery
pipe.
[0005] At present, the controls used to switch on the pump and supply water are located
on the surface and consist of a switch connected to the electric power supply cable
and of a tap connected to the water delivery pipe, respectively.
[0006] In this way, in order to start the water supply, the user needs to activate the pump
motor with the switch and then open the tap located at the end of the water delivery
pipe. On the other hand, in order to stop the water supply, it is necessary to switch
off the pump motor with the switch and then close the tap.
[0007] The big drawback of traditional pumps is represented by the fact that, in order to
stop the water supply, the user only turns off the tap. As a matter of fact, since
the water supply stops when the tap is turned off, most of the times the user forgets
to switch off the pump motor.
[0008] In this unfortunate event, the pump continues to operate without supplying water
and this will soon cause permanent damage to the motor.
[0009] It must be said that expedients were designed long time ago in order to avoid the
above-mentioned damage of the motor in canned motor pumps. All these expedients are
based on the automatic stall of the motor when the pressure of the water supply exceeds
the set value. In particular, this value is reached when the pump continues to operate
even if the tap is turned off.
[0010] To this purpose a tank with a pressure switch is sometimes installed on the surface,
along the delivery pipe just before the tap and outside the well. In particular, apart
from stopping the pump, the tank is also capable of accumulating a certain volume
of water at the top of the tap.
[0011] At this regard, it is important to note that all the automatic stop devices of canned
motor pumps are characterized by the fact that they are located on the surface and
physically separated from the pump.
[0012] Generally, the automatic stop devices are mounted after the installation of the pumps
and they often require the intervention of skilled installers, as in the case of tanks.
[0013] The purpose of the present invention is to create a canned motor pump capable of
switching on and off automatically and immediately when the tap is opened and closed,
respectively. It is important to note that the pump according to the present invention
is capable of switching on and off automatically without using additional separate
devices.
[0014] As a matter of fact, the main peculiarity of the pump according to the present invention
is represented by the fact that all the components that are necessary to automatically
switch on and off the pump are contained in the pump structure and available for the
user from the moment he purchases the pump.
[0015] This means that the pump according to the present invention is not only capable to
gLiarantee the integrity of the electric motor, but also to avoid all the difficulties
and costs necessary today to install tanks or similar devices on the surface in order
to automatically stop the operation of the pump motor, according to the description
above.
[0016] In practice, the pump according to the present invention is capable of stopping automatically
and immediately when the water pressure in the delivery water pipe exceeds the set
value (as it happens when the tap is closed and the pump motor is still operating),
and starting up again automatically when the water pressure drops below the second
threshold (as it happens when the tap is re-opened).
[0017] For major clarity the description of the invention continues with reference to the
enclosed drawings, which are intended for purposes of illustration and not in a limiting
sense, whereby:
- Figure 1 is a schematic drawing that shows the canned motor pump according to the
present invention in operating condition;
- Figure 2 is an enlarged view of the pump with the top cap partially removed in order
to show the internal parts in a schematic view;
- Figure 3 is the diagram of the electric circuit connected to the pump motor according
to the present invention.
[0018] With reference to the above mentioned figures, the pump (1) according to the present
invention usually features an elongated cylindrical structure which houses the electric
motor (2) in its lower end. A cap (1a) is located at the top of the pump, on which
the connections for the riser pipe (3) and the electrical cable (4) are located, as
well as an eyebolt (5) for the supporting rope.
[0019] Inside the cap (1a) a non-return valve (7) is installed in intermediate position
between the connection point of the external vertical riser pipe (3) and the internal
delivery water conduit (6). Thanks to the valve action, the water remains inside the
riser pipe (3) between the body of the pump (1) and the water tap (3a) even when the
pump motor is not working.
[0020] In the same cap (1a) a pressure sensor (8) that communicates through a small pipe
(8a) with the mouth of the external riser pipe (3) is mounted immediately below the
non-return valve (7). In this way the pressure sensor (8) is capable of detecting
the water pressure in the mouth of the external riser pipe (3).
[0021] As a matter of fact, the sensor (8) is responsible for the activation and deactivation
of the motor of the pump (1), since it determines the deactivation of the electric
motor when a set (high) water pressure value is detected inside the riser pipe (3).
At the same time, it is responsible for the reactivation of the pump motor when a
set (low) pressure threshold is detected inside the riser pipe (3).
[0022] The first condition - that is a high pressure value in the riser pipe (3) - is determined
when the tap (3a) is closed by the user, but the motor of the pump (1) is still operating.
The second condition - that is a low pressure value in the riser pipe (3) - is determined
when the tap (3a) is re-opened and the motor of the pump (1) is in stall.
[0023] In other words, when the user opens the tap (3a) on the surface, the motor (2) of
the pump (1) is switched on automatically and immediately, while when the tap (3a)
is closed, the motor (2) of the pump is switched off automatically and immediately.
[0024] Moreover, it must be said that the pressure sensor (7) features two logical states
(on-off) that alternate when the water in the riser pipe (3) reaches the set minimum
or maximum pressure value.
[0025] The two logical states are part of an electric circuit (shown in figure 3) capable
of switching on the pump when the tap is opened (with the low pressure threshold detected
by the sensor) or switching off the pump when the tap is closed (with the high pressure
threshold detected by the sensor).
[0026] In practice, the sensor is capable of switching on and off a relay (9) that is an
integral part of the electric circuit and is responsible for directly controlling
the switching on and off of the motor (2) of the pump (1). The electric circuit is
also equipped with a float switch (10) used to permanently cut out the motor (2),
regardless of the fact that the tap (3a) is opened or closed.
[0027] The float switch can be very useful when the pump remains unattended for a long time
to avoid its accidental switching on, due to the accidental opening of the tap by
unauthorized personnel.
[0028] The components of the electric circuit of the motor (2) are housed inside the pump
(1) next to the pressure sensor (8).
[0029] The same location can also be used to install electronic boards (possibly with microprocessor)
to switch on and off the pump in a more articulated way, according to the specific
requirements or needs.