TECHNICAL FIELD
[0001] The present invention relates to a multiple level building and, more particularly,
to an elevator system utilizing an emergency elevator evacuation control system that
allows the use of the elevators as a means of reliable egress and evacuation during
an emergency.
BACKGROUND OF THE INVENTION
[0002] A building and a method according to the preamble of claims 1 and 27 is already known
from US-A-4 592 270.
[0003] The Americans with Disabilities Act passed into law assuring all people an equal
opportunity to gain access to all buildings used by the general public. Even with
the adoption of this law, non-ambulatory people are generally afforded ingress to
all buildings but not necessarily given a protected means of egress from the building
during emergency circumstances. During a building emergency, such as a fire, ambulatory
and non-ambulatory building occupants, even those who are clear thinking people under
normal circumstances, can panic or make irrational decisions, which can result in
injury to themselves and others.
[0004] Faced with a difficult emergency situation, people many times revert to their most
comfortable behavior. In terms of leaving a multi-story building during non-emergency
conditions, this means using the elevator. People normally arrive at and depart from
the upper floors of the building via the elevator, and most never have used the emergency
stair system. Given a typical response to an emergency situation, people will retrace
their most familiar path of travel, which usually includes passing in front of the
elevators as they attempt to find an escape route from the building.
[0005] During an emergency situation, elevators are usually taken out of service except
for controlled use by the fire department. Accordingly, the building occupants cannot
currently use the elevator as a safe and reliable means of egress during the emergency
situation, such as a fire. They must therefore attempt either to use an unfamiliar
stairway or wait within the building to be rescued. Non-ambulatory and disabled people
unable to use stairs have no choice but to await help.
[0006] In multiple level buildings it is difficult to evacuate building occupants via the
stairs. Generally, there are two classifications of buildings relative to fire and
life safety: high-rise buildings and mid-rise buildings. The major distinction is
that a standard hook and ladder type fire apparatus can only reach the point of a
building about 75 feet or 6 floors above the ground, so "high-rise" buildings, those
above about 6 floors, must be evacuated from within the building.
[0007] In mid-rise buildings, fire departments use the stairs to transport personnel and
equipment to the fire floor, which drastically interferes with the designed egress
capacity of the exit stair system. In high-rise buildings, the difficulties with occupant
evacuation are compounded. Although the elevator cars can be used by the fire department
to transport personnel to a selected staging floor below the fire floor, many times
smoke is present in the hoistway shaft by the time of their arrival to the staging
floor. Stack effect pressures within the building move large volumes of air through
the vertical hoistway shafts. The shafts quickly become smoke filled chimneys and
are often capable of transporting smoke throughout the building in a matter of minutes.
[0008] Since the fire department cannot reach the building's upper floors from outside the
building, the building's occupants are forced to either use an exit stairway to evacuate
or remain in the burning building until rescued by the fire department. As the fire
department personnel uses one stairway to advance on the fire, the stairway doors
are typically propped open with fire hoses, thereby allowing smoke from the fire floor
to enter the stairway. Accordingly, that stairway is not suitable for evacuation of
the building occupants during an emergency.
[0009] The evacuation of people is the primary responsibility of the fire department. The
fire department personnel do not begin a fire attack until the building occupants
are safe. Conventional evacuation of building occupants, however, is a very time consuming
process. During a fire, the chaotic environment increases the complexity and danger
of an evacuation procedure, which also usually increases the time required to evacuate
the building. It is even more difficult and time consuming to evacuate the non-ambulatory,
injured, and disabled occupants.
[0010] Even if available for use, conventional elevator systems are an unreliable method
of escaping a building fire, and under current regulations, can only be used by the
fire department under a narrow range of conditions. For example, the elevator system
is not used when there is a high risk of a power outage, because such a power outage
will shut the elevator system down and potentially trap passengers between floors.
The conventional elevator control system is also easily short circuited by water that
enters either the machine room or the hoistway shaft. Smoke is easily drawn into the
hoistway shaft by naturally occurring stack effect pressures, and the smoke can quickly
fill the hoistway, thereby creating an unsafe environment for people without self-contained
breathing devices.
[0011] Therefore, the elevators are not usable for building occupants as a reliable means
of egress during a building fire. Placards stating "Do not use Elevators during a
Fire" are commonly placed next to the hall call stations to notify the occupants of
the proper emergency exiting strategy. Ambulatory occupants are therefore forced to
use exit stairways to escape a building fire, even from the top floors of mega high-rise
buildings.
Conventional Emergency Evacuation Procedures
[0012] When an emergency condition is identified in a building an alarm signal is manually
or automatically provided to the fire department. Upon receiving the alarm signal,
the fire department only knows that an alarm has been activated, but it does not know
the status of the building systems until the response team arrives at the building
and access the building's fire alarm panel or other data information bank. As a result,
the response team loses valuable time with respect to controlling the building conditions
and establishing a desired building evacuation sequence and emergency response strategy
for the particular building.
[0013] Even though the fire department response time to arrive at the building is typically
less than six or seven minutes, fifteen minutes can easily pass before an evacuation
sequence is initiated. The total evacuation time for upper floors of a high-rise building
may take up to an hour. During a building fire, time is critical and unnecessary delays
can increase the danger of the situation.
[0014] In accordance with a typical standard incident command procedure, an incident command
post is established in the main floor lobby upon arrival by the fire department. The
fire department personnel can then override the elevator system and use the elevators
to send an investigation team to a safe point several floors below the fire floor.
The investigation team then takes the stairs to the fire floor to assess the extent
of the fire involvement and determine the necessary evacuation procedures. Fire Department
personnel and equipment are then typically staged two floors below the fire floor
and a rescue assistance area is established four floors below the fire floor. Building
occupants are then initially evacuated through the stairway to the rescue assistance
area.
Conventional Elevator and Fire/Smoke Detection Systems
[0015] The basic configuration and operation of an elevator system is well known. A multiple
floor building contains a vertical elevator shaft defined by a top, bottom and vertical
structural walls through which an elevator car travels between floors. An opening
in one of the structural walls at each floor forms a hoistway entrance through which
building occupants can safely pass into and out of the elevator car when the elevator
car is adjacent to the hoistway entrance during non-emergency conditions. An interlock
mechanism connects the elevator car door to the hoistway door when the elevator car
is adjacent to the hoistway entrance and the elevator car door opened or closed.
[0016] The elevator car's vertical travel in the hoistway is controlled by a conventional
elevator control system. The elevator control system typically includes a motion controller
and a car controller that receives signals from hall call stations located on each
floor. The elevator control system is adapted to position the car adjacent the signaling
floor to allow passengers to enter or exit the car. When a "send" or "floor destination"
button within the car is activated, a signal is sent to the elevator control system,
which in turn moves the car to the designated floor and opens the door to allow passengers
to exit the car. Accordingly, the elevator control system permits the building occupants
to quickly and efficiently travel between floors of the multi level building during
normal conditions.
[0017] The typical high-rise building has a fire alarm/smoke detection system, such as a
system manufactured by the Simplex Corporation. The fire alarm/smoke detection system
is comprised of a plurality of smoke and heat sensing devices which are remotely located
throughout the building and capable of detecting the early signs of a building fire.
These remote detectors are electrically connected to a central fire alarm panel and
are functional to either open or close a series of relay contacts, thereby capable
of sending a signal to a building security station, to the fire department, and to
an alarm system that alerts the building occupants with audible and strobe alarms.
The central fire alarm panel also initiates the operation of fire doors, air conditioning
systems, and the like within the building. Many times the fire alarm/smoke detection
system also has an auxiliary relay contact as a backup system that is functionally
connected to the elevator control system. The elevator control system is programmed,
such that when it receives a distinctive signal from the central fire alarm panel,
the elevator control system recalls all elevator cars to a predesignated floor, e.g.,
the lobby floor, and prevents elevator cars from stopping at a floor where smoke has
been detected.
[0018] Prior to 1973, elevators remained fully operational during a building fire without
any safeguards that took into account the location of the building fire. Building
occupants on the fire floor trying to quickly escape a fire could push the elevator
hall call station buttons and inadvertently call an elevator full of people to the
fire floor. Building security personnel investigating a signaling smoke detector could
likewise find themselves faced with the fire as the elevator doors opened on the fire
floor. Fire temperatures or water flowing from the activation of a fire sprinkler
could also short circuit the elevator hall call station buttons and call the elevators
to the fire floor, thereby jeopardizing fire department personnel trying to utilize
the elevators to stage personnel and equipment.
[0019] In an effort to minimize this dangerous situation, all modem elevator systems are
equipped with a recall function that is initiated either automatically by the detection
of smoke or manually by building security or fire department personnel. The 1996 Edition
of the ASME A17.1 code for elevators requires recall on all elevators. Once sent into
alarm condition, all hall call stations are de-energized and all elevator cars are
automatically recalled to a predesignated floor of the building. If the predesignated
floor is the floor where smoke has been detected, the elevator cars are recalled to
an alternate floor. The elevators are parked with the doors open and the elevators
are temporarily taken out of service. Upon arrival, the fire department can override
the recall function by activating a fire department key switch to utilize each elevator
car individually. The conventional elevators, however, in an emergency such as a building
fire, cannot be used as a safe means of egress of occupants from the building even
under the control of the fire department.
[0020] Many state of the art buildings are also equipped with a smoke detection system that
is designed and installed in accordance with industry standards. At least one smoke
detector is located in each elevator lobby and is functionally connected to the elevator
control system. Additional remote smoke detectors may be located throughout the building
and are functionally connected to the elevator control system. When smoke from a building
fire is detected by the elevator lobby detector or by a remote smoke detector, an
alarm signal activates building emergency systems, which results in the closing of
certain predetermined doors, sounding audible alarms, and the like. The elevator recall
function is activated either automatically or manually, and the elevator control system
deactivates the hall call stations and the car destination buttons.
[0021] If an elevator car is moving upwardly, the elevator control system de-energizes the
motion controller, stops the car's ascent, and activates the motion controller to
position the car at a predesignated egress floor. If the car is moving downwardly,
the elevator control system activates the motion controller to continue the decent
to the predesignated egress floor.
[0022] Four basic elements are important for an elevator car to be used as an emergency
means of egress, which are not all provided by conventional elevator systems: reliable
power, a smoke free hoistway shaft, no unshielded electronics in the hoistway or machine
room that can be damaged by water, and the ability of the elevator system to respond
to changing building conditions due to migrating smoke. Power outages can stall the
elevator car, trapping passengers within the hoistway shaft and further consuming
fire department resources to locate the stalled car and evacuate the trapped passengers.
An emergency power source is only a mandatory building code requirement in buildings
above 75 feet to the highest occupied level. Accordingly, there is a need for an elevator
system that is usable for emergency evacuation of building occupants during a building
fire or other emergency.
[0023] One significant reason that conventional elevator systems are not used for emergency
egress during a building fire is the danger presented by smoke. Smoke that is present
at the hoistway door can also be interpreted by the electronic eye as an obstacle
in the elevator doorway, thereby preventing the door from closing properly. Smoke
also contains toxic gases and products of combustion that create an untenable environment
for people, even at room temperature. Smoke in the elevator hoistway would subject
any passengers riding in the elevator car to such an untenable environment and expose
them to increased risk.
[0024] At least one model building code in the United States prescribes an enclosed elevator
lobby in all buildings to separate the hoistway shaft from the remainder of the building
in an effort to control smoke. Some building code jurisdictions allow an air pressurization
system utilizing the elevator hoistway shaft to create positive air flow from the
shaft into the fire floor to blow smoke out of and away from the hoistway shaft. An
automatically deployable hoistway door gasketing system is described in U.S. Patent
Nos. 5,195,594 and 5,383,510 to keep smoke from entering the hoistway. Additional
methods of providing a smoke barrier at the hoistway door are described in my co-pending
U.S. applications, namely, U.S. Patent Application No. 08/732,129, filed October 18,
1996, and U.S. Patent Application No. 08/423,958, filed April 18, 1995.
[0025] Another reason for not using the elevator system for egress during an emergency is
the risks presented when water gets into the elevator system. Water used for fire
suppression, such as from automatic fire sprinklers or from the fire department hoses,
is usually present during a building fire. Water can enter the hoistway and short
circuit the car controls located on the top of the elevator car. A raised sill at
the hoistway door or a slight slope of the lobby floor away from the hoistway door
can help prevent water from draining into the hoistway shaft. Water entering the hoistway
shaft can also be controlled by the water shield/drainage system for the hoistway
door, described in my co-pending U.S. Patent Application No. 08/751,306, filed November
18, 1996.
[0026] The evacuation time as calculated in the "Routine Analysis of the People Movement
Time for Elevator Evacuation" is about forty minutes for an eleven story building
using a single elevator. A twenty-one story building was estimated to take three hours
to evacuate. Interviews of building occupants after actual fire incidents indicate
the initiation time from first hearing an alarm to beginning any evacuation sequence
may exceed thirty minutes. Therefore, the use of the conventional elevator systems
for evacuation is neither efficient nor realistic in its present configuration.
SUMMARY OF THE INVENTION
[0027] The present invention is directed toward a transportation system with an emergency
evacuation control system that overcomes problems experienced in the prior art and
provides additional benefits. One embodiment of the invention provides a multi-story
building having a plurality of floors, a plurality of detectors, such as smoke detectors,
and a vertical transportation system that is usable for moving building occupants
between selected floors during an emergency condition in the building. The building
includes an air handling system, an emergency suppression system, and a signal control
system. The signal control system is coupled to the detectors to receive a detection
signal, and is coupled to the vertical transports system, the air handling system,
or the emergency suppression, each of which provides a status signal to the signal
control system. The signal control system has a communication mechanism connectable
to a remote communication system at a location remote from the building, such as a
fire department. The communication mechanism sends the detection signal and at least
one of the status signals to the remote communication system to provide building status
information to the location remote from the building. The vertical transportation
system includes a transport unit that is positionable in the building at locations
adjacent to selected floors. A transport controller is coupled to the transport unit
to move the transport unit to the locations adjacent to the selected floors. A control
unit is coupled to the transport controller to send a selected control signal to the
transport controller to move the transport unit to one of the floors. The control
unit is coupled to the detectors to receive a detector signal from a signaling detector
that has detected an emergency condition in the building.
[0028] The control unit is programmed to identify the floor where the signaling detector
is located and defines that floor as a signaling floor. The control unit is also programmed
to define an evacuation zone in a portion of the building relative to the signaling
floor. The evacuation zone includes the signaling floor, a priority evacuation floor
located one floor away from the signaling floor, and an evacuation assistance floor
that is spaced apart from the signaling floor and the priority evacuation floor. The
control unit is also programmed to send the control signal to the transport controller
to move the transport unit within the evacuation zone and to evacuate the building
occupants from the signaling floor and the priority evacuation floor to the evacuation
assistance floor during the emergency condition. The information defining the emergency
evacuation assistance floor and the signaling floor is included in the vertical transportation
system's status signal sent to the remote communication system.
[0029] Another embodiment of the invention is an evacuation control system having an elevator
controller that controls the activities of an elevator car during a building fire
or other emergency situation for reliable and continuous elevator operation during
the emergency situation. The elevator controller for each elevator car is operationally
connected to the signal control system. In an exemplary embodiment, the signal control
system is a central fire alarm panel. The elevator controller is programmed to position
the elevator car in selected locations in the emergency evacuation zone during an
emergency situation, so as to aid in the emergency evacuation of the building occupants.
[0030] According to an exemplary embodiment of the present invention, a smoke detector or
preestablished compilation of sensing devices, such as water flow detectors or pull
stations, sends the building into an alarm state, thereby initiating the closing of
fire doors and dampers, and starting the air handling equipment to provide positive
pressure in the vertical shafts and enclosed elevator lobby areas. In an exemplary
embodiment, other building systems, such as emergency suppression systems (
i.e., sprinkler system). As distinctive, source-identifying alarm signals from the sensing
devices are received by the signal control system, the signals are sent to a central
processing unit, translated, and sent to the elevator controller, which is programmed
to respond to these distinctive signals. Status signals from the building systems,
such as the fire doors and dampers and air handling equipment, are also provided to
the signal control system and sent to the remote communication system.
[0031] The elevator controller is programmed to identify a first signaling floor,
e.g., the floor from which the alarm signal is generated, as the probable fire floor.
The elevator controller is also programmed to define and designate an emergency evacuation
zone within the building relative to the first signaling floor (
i.e., the fire floor). The emergency evacuation zone is defined by the probable fire floor,
the two floors above the fire floor, and one floor below the fire floor. The elevator
controller is also programmed to provide evacuation priorities, wherein the first
priority is evacuation of the fire floor, and the second priority is evacuation of
the floor directly above the fire floor. The third priority is evacuation of the floor
directly below the fire floor, and the fourth priority is evacuation of the floor
two floors above the fire floor. The elevator controller is also programmed to establish
a rescue assistance floor at a selected location away from the fire floor, such as
four floors below the fire floor. Information defining the priority evacuation floors
and the rescue assistance floor is provided to the signal control system and sent
to the remote communication system. Accordingly, the elevators are used to evacuate
the building occupants to the rescue assistance floor during the emergency situation,
wherein the occupants can be attended to by emergency personnel and evacuated from
the building if required. Status information regarding such evacuation is provided
to the emergency personnel even before they arrive at the building.
[0032] During an evacuation procedure, the elevator controller positions the elevator car
or cars at the first signaling floor in a ready state with the car and hoistway doors
in an open position. Only the hall call stations in the emergency evacuation zone
are operable, and the other hall call stations are deactivated. The hall call stations
within the emergency evacuation zone provide a visual notification of the emergency
evacuation status by continuously blinking the down button. Audible notification is
given by the continuous intermittent sounding of the elevator car arrival bell. A
fan located in the elevator car is energized to blow tenable air from the hoistway
shaft through the open doors thereby preventing smoke from entering the elevator car.
[0033] When any control button on an operating panel in the car is pushed or otherwise activated,
the elevator controller closes the elevator doors, moves the elevator car to the predetermined
rescue assistance floor, and opens the doors to allow egress out of the car. In one
embodiment, the elevator cars are equipped with a recorded-voice enunciator that provides
audible instructions to reinforce the egress activity. After the occupants exit the
elevator car, the elevator controller closes the doors and repositions the elevator
car at the first signaling floor as described above, and awaits a call signal from
a floor within the emergency evacuation zone.
[0034] When a building occupant pushes the hall call station from a floor within the emergency
evacuation zone other than the fire floor, the elevator controller moves the car from
the first signaling floor to the calling floor and opens the car and hoistway doors,
thereby allowing the occupant to enter the elevator car. The elevator controller then
closes the doors, moves the elevator car to the rescue assistance floor, and opens
the doors to allow the occupants to exit the car. The elevator car is then returned
to the first signaling floor and awaits another call signal.
[0035] In accordance with the exemplary embodiment of the present invention, the smoke detectors
throughout the building are polled by the signal control system. If a smoke detector
located within an elevator lobby senses smoke, a signal is provided to the signal
control system,
e.g., the central alarm panel, and the central alarm panel notifies the elevator controller.
The signal is also provided to the signal control system and can be provided to the
signal control system and can be provided to the remote communication system to inform
emergency personnel about the status of the emergency. The elevator controller also
de-energizes the hall call station on the floor where smoke was detected in the elevator
lobby and prevents the elevator car from opening its door when on that floor.
[0036] The smoke detectors continue to be polled and if smoke is detected within the hoistway
shaft or at the elevator car, the elevator controller automatically recalls all elevators
traveling within the hoistway to the main lobby floor. At this time all hall call
stations and car buttons are de-energized.
[0037] The fire department can override the emergency evacuation sequence from the main
lobby or the central fire alarm panel and recall the desired number of elevators to
the main lobby. By accessing the signal control system, the fire department can designate
additional evacuation floors thereby increasing the size of the emergency evacuation
zone, and if desired, to eventually include all floors within the building.
BRIEF DESCRIPTION OF THE DRAWINGS
[0038] This invention, along with its many attendant advantages and benefits, will become
better understood by reading the detailed description of the invention with reference
to the following drawings, wherein:
Figure 1 is a sectional view of a multiple level building with a building egress system
in accordance with an embodiment of the present invention, with an emergency evacuation
zone and an evacuation assistance floor shown outlined by hash marks for clarification.
Figure 2 is a schematic representation showing an exemplary building egress system
of the building egress system of Figure 1.
Figure 3 is an enlarged schematic perspective view of an elevator car in the building
of Figure 1.
Figure 4 is an enlarged elevational view of an elevator lobby of the building ofFigure
1 looking toward the hoistway door area and showing the elevator car with broken lines.
Figure 5 is a partial schematic flow chart illustrating an exemplary emergency evacuation
sequence upon activation of a remote smoke detector in accordance with one embodiment
of the present invention.
Figure 6 is a partial schematic flow chart illustrating the exemplary emergency evacuation
mode of the emergency evacuation sequence of Figure 5.
Figure 7 is a schematic flow chart illustrating an exemplary emergency evacuation
sequence during further developed stages of a building fire in accordance with one
embodiment of the present invention.
Figure 8 is a sign placard located within the elevator car and at each elevator lobby
for use with the present invention.
DETAILED DESCRIPTION OF THE INVENTION
[0039] Referring now to the drawings wherein like reference characters designate identical
or corresponding parts, and more particularly to Figure 1 thereof, there is shown
a multiple level building 2 with a building egress system 4 in accordance with an
exemplary embodiment of the present invention. The building egress system 4 includes
a vertical transportation system, such as an elevator system 6, that is connected
to a smoke and fire detection/alarm system 8 by a communication or interconnection
system 10. The elevator system 6, the detection/alarm system 8, and the interconnection
system 10 are interconnected to be used during normal, non-emergency conditions and
also to allow the elevator system to be used by the building occupants for egress
from the building 2 during a fire or other emergency situation.
[0040] The elevator system 6 includes at least one elevator car 20 controlled by an elevator
controller 16 that moves the elevator car to selected floors 21 of the building 2.
The elevator controller 16, such as a controller manufactured by the Dover Elevator
Corporation of Memphis, Tennessee, includes an interconnected relay network or a central
processing unit (CPU) that is programmed with a communication language utilizing an
analog or digital protocol for operation and movement of the elevator car 20. The
CPU's protocol provides an information feedback loop that maintains a desirable status
of operation within the elevator system 6.
[0041] The smoke and fire detection/alarm system 8 includes a plurality of smoke/fire detectors
22 that are connected to a signal control system 25, such as a fire alarm panel 26,
by a detection/alarm communication system 28. The fire alarm panel 26, such as one
manufactured by the Simplex Time Recorder Corporation of Gardner, Massachusetts, includes
an interconnected relay network or a central processing unit (CPU) that is programmed
with a communication language utilizing an analog or digital protocol. The CPU is
programmed to locate and identify distinctive, location-identifying signals from individual
smoke/fire detectors 22. The CPU is also programmed to send further distinctive signals
to conventional control devices 24 in the building 2 to operate specific building
functions, such as automatically closing fire doors and a hoistway pressurization
system. The CPU's protocol provides an information feedback loop that maintains a
desirable status of operation within the smoke and fire detection/alarm system 8.
[0042] The interconnection system 10 has an interconnection system operator 34 that is operatively
connected to the fire alarm panel 26 and the elevator controller 16. The interconnection
system operator 34 includes an interconnected relay network or a central processing
unit (CPU) 38 that is programmed with a communication language utilizing an analog
or digital protocol, such as one that complies with the ANSI/ASHRAE 135-1995 BACnet
Standard. The CPU 38 is programmed to locate and identify distinctive signals from
the signal control system 25, such as the fire alarm panel 26 or other individual
interconnection system signal initiating devices. The CPU 38 is also programmed to
send distinctive signals to the elevator controller 16, or other interconnection system
signal responsive devices, to operate specific interconnection functions, such as
selectively moving the elevator car 20 in response to the location of smoke and fire
during a building fire. The CPU's protocol provides an information feedback loop that
maintains a desirable status of operation within the interconnection system 10.
[0043] An emergency power supply system 40 complying with industry standards, is connected
to the building egress system 4. The emergency power supply system 40 provides continuous
secondary power to the building egress system 4 during an outage of primary building
power, thereby allowing the elevators to continue to operate during an emergency situation.
Accordingly, the elevator system 6, which is responsive to the location of fire and
smoke within the multiple level building 2, is usable during building fire or other
building emergencies for occupant egress away from the emergency situation in a safe
and efficient manner.
The Elevator System
[0044] The building egress system 4 of the exemplary embodiment described herein can be
used with a single elevator car 20 traveling within a single hoistway shaft 42, or
with multiple cars traveling within a common hoistway shaft, or with multiple cars
in multiple shafts. The building egress system 4 can also use various types of elevator
systems 6 in accordance with embodiments of the present invention.
[0045] The elevator system 6 of the exemplary embodiment, as best seen in Figure 1, includes
the elevator hoistway shaft 42 having an upper limit 44, a lower limit 46, and a midpoint
48 with a hoistway wall structure 50 extending therebetween. A hoistway opening 52
in the wall structure 50 is provided at each floor 21 of the building 2, defining
a hoistway entrance 54 that is closable by a movable hoistway door assembly 56. The
hoistway shaft 42 contains at least one elevator car 20 that is movably positionable
between floors 21. Each elevator car 20 includes a car floor platform 58, a front
panel 60, a rear panel 62, side panels 64, a ceiling/roof panel 66, and a movable
car door assembly 68. The car door assembly 68 is movable with the hoistway door assembly
56 between closed and open positions to allow people to enter and exit the elevator
car 20.
[0046] Each elevator car 20 is connected by a car support cable 70 to a motion controller
72 that is located in a machine room 74 positioned above the hoistway shaft 42. In
an alternate embodiment, the elevator car 20 is a part of a hydraulic elevator system
(not shown), and the elevator car is attached to a hydraulic piston that is operatively
connected to the motion controller 72. The motion controller 72, such as a conventional
motor driven drum, a hydraulic pump, or the like, is coupled to an elevator communication
system 18. The motion controller 72 receives and sends distinctive signals from the
elevator controller 16, which receives distinctive signals from elevator call devices
12, or other signal initiating devices, located at each floor 21. The motion controller
72 and elevator controller 16 control the vertical motion and positioning of the elevator
car 20 between the building's floors 21 in response to the signals from elevator call
devices 12 on each floor 21.
[0047] The elevator controller 16 is connected to one end of a traveling cable 76 of the
elevator communication system 18, and the traveling cable's other end is connected
to a car control communication system 78 that is mounted on the elevator car 20, as
best seen in Figure 3. Accordingly, the traveling cable 76 operatively connects the
elevator car control communication system 78 to the elevator controller 16. The car
control communication system 78 includes remote car control devices 80 mounted within
the elevator car 20, signal responsive devices 82 operatively connected to the car
control devices, and an elevator car controller 84 that is also operatively connected
to the car control devices.
[0048] The car control devices 80 in the exemplary embodiment include a plurality of destination
buttons 86, a door open button 88, a door close button 90, an emergency stop button
92, an emergency fire service override switch 94, and an audible car notification
device 96. The car control devices 80 are located on a car operating panel 98 and
are functional to send and receive distinctive signals to and from the car controller
84 and the elevator controller 16 (Figure 1). An emergency elevator telephone 100
located within a front panel 60 of the elevator car 20 is likewise connected to the
traveling cable 76 and terminates at a building maintenance office, not shown, or
an automatic dialer connected to an outside telephone line.
[0049] Each destination button 86 is operatively connected in a conventional manner to the
elevator controller 16 (Figure 1) via the traveling cable 76. When a destination button
86 is activated, the destination button generates a distinctive signal that is received
by the elevator controller 16. The elevator controller 16 energizes the motion controller
72 to move the elevator car 20 to the desired floor. When the elevator car 20 is in
registration with the hoistway opening 52 of the selected floor 21, the car goes through
a conventional ingress/egress cycle, wherein the car door assembly 68 and hoistway
door assembly 56 (Figure 4) are opened to allow passengers to enter or exit the car.
After a selected period of time the door assemblies 68 and 56 are closed. The elevator
car 20 is then ready to move to the next selected floor 21.
[0050] As best seen in Figure 4, the elevator call devices 12 of the exemplary embodiment
includes a plurality of hall call stations 104 located in close proximity to the hoistway
door assembly 56 in each elevator lobby 106 of the building 2. The hall call station
104 has an up direction call button 108 and a down direction call button 110, each
functionally connected to an input/output terminal 112, that is operatively connected
to the elevator communication system 18. When an up or down direction call button
108 or 110 is activated, such as when a building occupant desires to leave a particular
floor 21, the input/output terminal 112 sends a distinctive signal to the elevator
communication system 18 and to the elevator controller 16 to energize the motion controller
72 and move the elevator car 20 to the elevator lobby 106 of the hall call station
104 with the button that has been activated.
[0051] A car arrival indicator 114 is located in close proximity to the hoistway door assembly
56 or in close proximity to the elevator car door assembly 68 as best seen in Figure
4. The car arrival indicator 114 has an up direction light 116 and a down direction
light 118, each operatively connected to an input/output terminal 120 which is connected
to the elevator communication system 18. When a hall call station 104 is activated
and the elevator car 20 arrives at the elevator lobby 106 during normal or non-emergency
operations, the elevator controller 16 activates the car arrival indicator 114 showing
the car's travel direction by energizing the respective up or down direction light
116 or 118. The elevator controller 16 also energizes an audible car arrival notification
device 122 to make distinctive tones for an elevator car traveling upwardly or downwardly.
[0052] As best seen in Figure 4, the location of the elevator car 20 in the hoistway 42
is determined by a position sensor 124 and a position indicator 127 in the hoistway.
The position sensor 124 is attached to the elevator car 20 and is connected to an
input/output terminal 126, which is operatively connected to the traveling cable 76.
The position indicator 127 is attached to the hoistway wall structure 50 within the
hoistway shaft 42 near each elevator lobby 106. The position indicator 127 is positioned
so that when the position sensor 124 is in direct registry with the position indicator
127, a distinctive signal is sent from the position sensor 124 to the elevator controller
16. The elevator controller 16 then de-energizes the motion controller 72 (Figure
1) to stop the elevator car's vertical motion and to align the car floor platform
58 in direct registry with a lobby floor 128. The position indicator 127 is operatively
connected to the signal control system 25 and provides position status signals indicating
the elevator car's location in the hoistway 42.
[0053] When the car floor platform 58 is stationarily positioned adjacent to the lobby floor
128, the ingress/egress cycle is initiated. The car controller 84 energizes a conventional
door motion controller 130 that is operationally connected to the movable car door
assembly 68 to move the car door assembly and the hoistway door assembly 56 via an
interlock system 132 to an open position, thereby allowing passengers to pass into
and out of the elevator car. After a predetermined period of time, such as ten seconds,
the elevator controller 16 energizes the door motion controller 130 which moves the
hoistway and car door assemblies 56 and 68 to the closed position.
[0054] As best seen in Figure 3, a car door leading edge 134 of the elevator car door assembly
68 is connected to a conventional obstacle sensor, which is connected to the car control
communication system 78. The obstacle sensor sends a distinctive signal to the car
controller 84, which energizes the door motion controller and automatically reopens
the hoistway and car door assemblies 56 and 68 (Figure 4) if an obstacle, such as
a passenger, is in the hoistway entrance as the door assemblies are closing. Accordingly,
the obstacle sensor is adapted to prevent the doors from closing and injuring a passenger
or the like that is blocking the hoistway and car door assemblies 56 and 68 (Figure
4) during the door closing cycle.
[0055] The car controller 84 is preprogrammed to re-close the hoistway and car door assemblies
56 and 68 (Figure 4) after a predetermined amount of time, such as two seconds. The
car controller 84 is further programmed to stop the reopening operation of the hoistway
and car door assemblies 56 and 68 (Figure 4) after a predetermined number of closing
attempts, such as three attempts, at which time the car controller 84 is programmed
to activate the audible car notification device 96 and the doors are moved toward
the closed position engaging the obstacle. Once the obstacle is removed and the hoistway
and car door assemblies 56 and 68 (Figure 4) are moved to the fully closed position,
the car controller 84 de-activates the audible car notification device 96.
[0056] A conventional door-closed-sensor is attached to the car door assembly 68 and is
operatively connected to the elevator communication system 18 to determine when the
car door assembly 68 is in the closed position. Once the car door assembly 68 is in
the closed position, the door-closed-sensor provides a distinctive signal to the elevator
communication system 18 and the elevator controller 16. The elevator controller 16
then energizes the motion controller 72 which moves the car 20 vertically to other
selected floors. As seen in Figure 4, the hoistway door assembly 56 remains in a closed
position until again engaged through the interlock system 132 by the car door assembly
68, thereby preventing accidental access to the hoistway shaft 42.
[0057] A conventional load sensor is attached to the motion controller 72 and is operatively
connected to the elevator communication system 18 and to the elevator controller 16.
The elevator controller 16 is programmed to evaluate the available load capacity of
the elevator car 20 by determining a live load weight within the car as established
by the load sensor and comparing this weight to the predetermined total live load
capacity of the car. As the elevator car 20 responds to the activation of hall call
stations 104 within a run, the car will stop at signaling floors until the safe operating
capacity of the car has been reached, at which time the elevator car will not respond
to additional signaling hall call stations.
[0058] When a live load weight exceeds the capacity, the elevator controller 16 activates
the audible car notification device 96 and does not permit the motion controller 72
to energize the door motion controller 130. After the load sensor indicates a live
load below the safe operating capacity, the elevator controller 16 de-activates the
audible car notification device 96 and allows the motion controller 72 to energize
the door motion controller 130.
[0059] During normal non-emergency operations, the elevator controller 16 is preprogrammed
to respond to additional hall call stations 104 that are activated in the traveling
direction while the elevator car 20 is traveling to one of the desired floor 21. Once
the elevator car 20 has reached the furthest activated hall call station 104, the
elevator controller 16 deactivates all activated floor destination buttons and reverses
the car's travel direction.
[0060] The position and status of each elevator car 20 is monitored by a conventional car
position indicator 150, illustrated in Figure 1, in the signal control system 25,
and located in close proximity to the fire alarm panel 26. The car position indicator
150 is connected in a conventional manner to the elevator controller 16 via the elevator
communication system 18. The car position indicator 150 provides a visual indication
showing the position, direction of travel and operational status of each elevator
car 20.
Fire and Smoke Detection System
[0061] As described above and best seen in Figure 1, the smoke and fire detection/alarm
system 8 includes a plurality of remote smoke/fire detectors 22. The smoke/fire detectors
22 are strategically located throughout each floor 21 of the building 2 in accordance
with local building and fire codes. The detectors 22 are functional to detect the
presence of combustion byproducts, such as smoke or toxic fumes. Each detector 22
is operatively connected to the smoke and fire detection/alarm communication system
28. Each individual detector 22 is programmed or otherwise configured to initiate
and send a distinctive, location-identifying alarm signal to the fire alarm panel
26 when smoke or another combustion byproduct is detected.
[0062] The fire alarm panel 26 is programmed to identify the distinctive signal received
from each detector 22. The fire alarm panel 26 is further programmed with the location,
type and operating parameters of each detector 22, so as to determine where and which
detector in the building was activated upon detecting smoke or the like.
[0063] The fire alarm panel 26 is also operatively connected to the detection/alarm communication
system 28 and is adapted to control or activate conventional audible/visual building
alarms. The detection/alarm communication system 28 also operates a conventional public
address-type annunciation system, and a fire department notifier, such as an automatic
dialer connected to an outside telephone line, and other conventional smoke and fire
detection/alarm system signal responsive devices.
[0064] The fire alarm panel 26 is also operatively connected to a plurality of the building's
systems and is adapted to receive status signals from those systems. Accordingly,
the fire alarm panel is used to determine the building's status, such as when a fire
or other emergency condition is detected. As an example, the fire alarm panel 26 is
operatively connected to self-closing fire doors on each floor 21 that close to separate
the respective elevator lobby 106 from the remainder of the building. The fire alarm
panel 26 is also operatively connected to air handling equipment (
i.e., HVAC system) in the building to provide positive air pressure within the elevator
lobby 106 and the elevator hoistway shaft 42 to keep the lobby and hoistway shaft
clear of smoke. The fire alarm panel is also connected to one or more emergency suppression
systems, such as sprinkler systems or the like, that are activated upon detecting
an emergency.
[0065] The detectors 22, best seen in Figure 1, are strategically placed throughout the
building 2 with a minimum of one per floor. Lobby smoke detectors 174 are also strategically
located throughout the building 2, with a minimum of one in each elevator lobby 106.
An elevator car smoke detector 176, best seen in Figure 3, is mounted on the elevator
car 20 and is operatively connected to the smoke and fire detection/alarm communication
system 28 by the traveling cable 76. detectors 178 are
[0066] As best seen in Figure 1, a plurality of hoistway smoke detectors 178 are located
within the hoistway shaft 42. An upper hoistway smoke detector 180 is connected to
the wall structure 50 near the hoistway shaft's upper limit 44. A lower hoistway smoke
detector 182 is connected to the wall structure 50 near the hoistway shaft's lower
limit 46. An intermediate hoistway smoke detector 184 is connected to the wall structure
50 near the hoistway shaft's midpoint 48. When a detector 22 is activated upon detecting
smoke or the like, the detector sends a distinctive signal to the fire alarm panel
26 that allows the fire alarm panel to determine where the signaling detector is located..
[0067] The fire alarm panel 26 also has an elevator recall switch 186 that is connected
to the elevator controller 16 via the elevator communication system 18, as described
above. The elevator recall switch 186 may be automatically activated, such as when
a detector 22 is activated. The elevator recall switch 186 may also be manually activated,
such as during a non-fire emergency. The elevator recall switch 186 provides a signal
to the elevator controller 16, which de-activates all hall call stations 104 and destination
buttons 86 in all elevator cars 20 and energizes the motion controller 72 to move
all elevator cars to a predesignated recall floor 188, typically established as the
ground floor with a ready exit from the building 2.
[0068] A recall floor smoke detector 190 is strategically located at the predesignated recall
floor 188 and connected to the elevator communication system 18, which is operatively
connected to the elevator controller 16, as described above. When the recall floor
smoke detector 190 detects smoke, a distinctive signal is sent to the elevator controller
16 which energizes the motion controller 72 to move the elevator cars 20 to a predesignated
alternate recall floor 192, typically established as a floor located two floors above
the ground floor.
The Control Protocol Interface
[0069] During non-emergency normal operation, the smoke and fire detection/alarm system
8 and the interconnection system 10 remains in the normal mode, wherein the elevator
system 6 operates in a conventional non-emergency manner. During this normal operation,
the fire alarm panel 26 polls and monitors the smoke/fire detectors 22 and selected
other building systems. As best seen in Figure 5, in the event of a building fire,
smoke or heat from the fire is detected by one or more detectors 22, the detector
sends a distinctive first alarm signal 200 to the fire alarm panel 26. The first alarm
signal 200 is transmitted by the fire alarm panel 26 through the interconnection communication
system 10 to the CPU 38 and translated by the BACnet protocol language, thereby initiating
an emergency elevator evacuation sequence 194.
[0070] During the fire or other building emergency, the components of the building egress
system 4 of the exemplary embodiment, as described herein and schematically illustrated
in Figure 2, work together in an emergency elevator evacuation sequence that utilizes
the one or more elevator cars 20 to evacuate selected portions of the building 2.
The interconnection system's CPU 38 is engineered and programmed to initiate a preprogrammed
emergency elevator evacuation sequence. During the evacuation sequence, the CPU 38
sends distinctive output signals to the elevator controller 16 in response to distinctive
input signals received from the fire alarm panel 26. Upon receiving the output signals,
the elevator controller 16 strategically positions one or more elevator cars 20 at
selected floors to evacuate portions of the building 2. The CPU 38 also sends distinctive
output signals to the fire alarm panel 26 in response to distinctive input signals
initiated by the elevator controller 16, thereby notifying the fire alarm panel 26
of the status of all elevator cars 20. As discussed in greater detail below, the fire
alarm panel 26 also contacts the fire department or other remote emergency response
team and provides information as to the current status of the building 2. The emergency
evacuation sequence is then initiated.
The Emergency Evacuation Sequence
[0071] The emergency elevator evacuation sequence establishes an emergency evacuation zone
202, as best seen in Figure 1, encompassing a four floor area around a first signaling
floor (FSF) 206 on which a first signaling remote smoke/fire detector 204 of the detectors
22 is located. The first signaling floor 206 is assigned by the CPU 38 a first priority
during the evacuation of the emergency evacuation zone 202. The emergency evacuation
zone 202 also includes a second evacuation priority floor 208 located one floor above
the first signaling floor 206, a third evacuation priority floor 210 located one floor
below the first signaling floor, and a fourth priority evacuation floor 212 located
two floors above the first signaling floor. The emergency evacuation zone 202 also
includes an evacuation assistance floor 214 located four floors below the first signaling
floor 206. The floors 21 outside the emergency evacuation zone 202 are defined as
non-emergency floors 215. If the first signaling floor 206 is within the first seven
floors 21 above the ground floor, the evacuation assistance floor (EAF) 214 is established
as the predesignated recall floor 188 (usually the ground floor).
[0072] The configuration of the emergency zone 202 may be changed depending upon air flow
direction in the hoistway shaft 42. In the exemplary embodiment, an air flow sensing
device 216, shown in Figure 1, is mounted in the hoistway shaft 42, and is operatively
connected to the CPU 38 of the interconnection system operator 34. The air flow sensing
device 216 identifies the direction of air flow in the hoistway shaft 42. The air
flow sensing device 216 has an upper sensor 218 connected to the wall structure 50
of the hoistway shaft 42 near the upper limit 44 thereof and a lower sensor 220 connected
to the wall structure 50 of the hoistway shaft 42 near the lower limit 46 thereof,
each operationally connected to the interconnection communication system 36.
[0073] If the airflow is upward, so smoke within the hoistway shaft will likewise move upwardly
toward the upper floors, the emergency evacuation zone 202 is as described above.
If, however, the airflow is downward, so smoke would travel downwardly toward lower
floors, the CPU 38 is programmed to reverse the order of floors in the emergency evacuation
zone 202 described above. Accordingly, the evacuation assistance floor 214 is located
four floors above the first signaling floor 206. The second evacuation priority floor
208 is one floor below the first signaling floor 206, the third evacuation priority
floor 210 is two floors below the first signaling floor, and the fourth evacuation
priority floor is one floor above the first signaling floor.
[0074] The emergency elevator evacuation sequence 194, therefore, is functional to conduct
emergency evacuation via the elevator cars 20 in a compact six floor zone. The evacuation
time is therefore relative to elevator travel within this six floor zone and not relative
to elevator car travel within the entire height of the building 2.
When Smoke is Detected
[0075] When one of the detectors 22 detects smoke or the like, as best schematically illustrated
in Figure 5, the detector sends a first alarm signal 200 to the interconnection system
operator's CPU 38, and the CPU initiates the emergency elevator evacuation sequence
194. The CPU 38 sends a distinctive signal to the fire alarm panel 26 identifying
the emergency zone 202, including the location of the signaling floor 206, the evacuation
assistance floor 214 and the second through fourth evacuation priority floors 208,
210, and 212, respectively. The CPU 38 further sends a distinctive signal to the elevator
controller 16 which energizes a car fan 222 (see Figure 3) that moves air from the
elevator hoistway shaft 42 into the elevator car 20. In step 224, the elevator controller
polls the hall call stations 104 of the floors in the emergency evacuation zone 202,
and in step 226, deactivates all hall call stations of floors outside of the emergency
evacuation zone. In step 228, the elevator controller further energizes the down direction
light 114 in the hall call stations 104 located within the emergency evacuated zone
202 to blink in a continuous intermittent manner. In step 230, the elevator controller
16 further deactivates all destination floor buttons 86 in the elevator car 20.
[0076] The elevator controller 16 also polls in step 232 the car status and determines in
step 234 if the elevator car 20 is moving. If the elevator car is not moving, in step
236 the elevator controller 16 sends a distinctive signal to the motion controller
72 which in step 238 moves the elevator car to the first signaling floor 206. The
elevator controller 16 initiates an evacuation-ready mode in step 240 in which the
hoistway and car door assemblies 56 and 68 are moved to the open position, the down
direction light is intermittently blinked, and the car arrival notification device
122 is energized to ring in a continuous intermittent manner.
[0077] If the elevator car 20 is moving, in step 242 the elevator controller 16 polls in
step 244 the car's direction of travel. If the car travel direction is upwardly, in
step 246 the elevator controller 16 polls in step 248 the elevator car's location
relative to the evacuation assistance floor 214. If in step 250 the elevator car is
above the evacuation assistance floor 214, the elevator controller stops the car's
ascent in step 252, in step 254 energizes the car destination button 86 for the evacuation
assistance floor 214, and in step 256 moves the car to the evacuation assistance floor.
The elevator controller 16 then in step 258 initiates the ingress/egress cycle, as
described above. If the elevator car 20 is traveling upwardly in step 246 and is below
the evacuation assistance floor in step 260, the elevator controller 16 in step 254
energizes the car destination button 86 for the evacuation assistance floor 214, in
step 256 moves the car to the evacuation assistance floor, and in step 258 initiates
the ingress/egress cycle.
[0078] If in step 262 the elevator car 20 is traveling downwardly, in step 264 the elevator
controller 16 polls the location of the downwardly traveling car. If in step 266 the
elevator car is above the evacuation assistance floor, in step 254 the elevator controller
16 energizes the car destination button 86 for the evacuation assistance floor 214,
in step 256 moves the car to the evacuation assistance floor, and in step 258 initiates
the ingress/egress cycle.
[0079] If in step 262 the elevator car 20 is traveling downwardly and in step 268 is below
the evacuation assistance floor 214, in step 270 the elevator controller 16 energizes
the car destination button 86 for the evacuation assistance floor 214, in step 272
moves the car to the evacuation assistance floor or a designated alternate floor,
and in step 258 initiates the ingress/egress cycle. Once the ingress/egress cycle
is completed, and the occupants move out of the car to the evacuation assistance floor
214, in step 274 the elevator controller moves the car to the first signaling floor
206 and in step 240 the car controller initiates the evacuation-ready mode.
The Evacuation-Ready Mode at the First Signaling Floor
[0080] During the evacuation-ready mode, step 240 of the emergency elevator evacuation sequence,
as best illustrated schematically in Figure 6, the elevator car is positioned at the
first signaling floor with the doors open awaiting the arrival of passengers. When
in step 276 a passenger enters the car and activates any car button 86, 88, or 90,
the elevator controller 16 in step 278 energizes the car destination button for the
evacuation assistance floor 214. The elevator controller will also automatically energize
the car destination button for the evacuation assistance floor when the car's load
sensor detects additional weight in the elevator car, such as when a passenger enters
the car. In step 280 the elevator controller 16 closes the hoistway and car door assemblies
56 and 68, in step 282 moves the elevator car from the first signaling floor 206 to
the evacuation assistance floor 214, and in step 284 initiates the ingress/egress
cycle to allow the passengers to exit from the car. The elevator controller in step
286 then moves the elevator car back to the first signaling floor 206 and in step
240 restarts the evacuation-ready mode of step 240.
[0081] The elevator car 20 remains at the first signaling floor 206 for a predetermined
amount of time, such as thirty seconds, in the evacuation-ready mode. If in step 288
a car button 86, 88, or 90 is not manually or automatically activated within the predetermined
amount of time, the elevator car is then available to respond to the activation of
hall call stations 104 on other floors within the emergency evacuation zone 202. When
in step 290 a hall call station 104 is activated on another floor within the emergency
evacuation zone 202, in step 292 the elevator controller 16 closes the hoistway and
car door assemblies 56 and 68 and moves the car to the floor on which the hall call
station was activated. The elevator controller then initiates the evacuation-ready
mode of step 240, as described above. If hall call stations 104 are activated on more
than one floor in the emergency evacuation zone 202, the elevator controller 16 moves
the elevator car to the floor having the highest priority of the second evacuation
priority floor 208, the third evacuation priority floor 210 or the fourth priority
evacuation floor 212.
[0082] If in step 294 a passenger activates a car destination button 86 or if the load sensor
detects additional weight in the elevator car within the predetermined amount of time,
in step 278 the elevator controller 16 energizes the car destination button 86 for
the evacuation assistance floor 214. The elevator controller in step 280 closes the
hoistway and car door assemblies 56 and 68, in step 282 moves the elevator car to
the evacuation assistance floor 214, and in step 284 initiates the ingress/egress
cycle. The elevator controller in step 240 then moves the elevator car 20 back to
the first signaling floor 206 and initiates the evacuation-ready mode.
[0083] If in step 296 the elevator car is in the evacuation-ready mode of step 240 on a
floor other than the first signaling floor 206 and a destination car button 86 is
not manually or automatically activated within the predetermined amount of time, the
elevator controller 16 in step 298 closes the hoistway and car doors 56 and 68, in
step 300 moves the car back to the first signaling floor 206, opens the door assemblies,
and initiates the evacuation-ready mode of step 240.
[0084] The elevator car remains in step 288 in the evacuation-ready mode of step 240 on
the first signaling floor 206 until a car button 86, 88, or 90 is activated, or in
step 290 the load sensor detects additional weight within the car, or a hall call
station 104 within the emergency evacuation zone 202 is activated.
[0085] In the exemplary embodiment, the elevator controller 16 is programmed to respond
to only one hall call station 104 activation within each trip cycle to allow passengers
safe egress onto the evacuation assistance floor 214. The elevator controller is further
programmed to respond to the first signaling floor 206 as the highest priority and
then follow the prioritization of evacuation floors as described above. The evacuation
of building occupants from the emergency evacuation zone 202 to the evacuation assistance
floor 214 is thereby quickly, efficiently and safely accomplished.
As the Smoke Migrates
[0086] As schematically illustrated in Figure 7, in step 304 upon the detection of smoke
by one of the remote smoke/fire detectors 22 that is not located in that floor's elevator
lobby, the remote detector in step 306 sends a first distinctive detection signal
to the fire alarm panel 26. The interconnection system operator's CPU 38 receives
a signal from the fire alarm panel 26, translates the signal and sends a signal to
the elevator controller 16. The elevator controller 16 then initiates the emergency
elevator evacuation sequence of step 194, as described above with reference to Figure
5. When in step 30 the smoke/fire detector 22 located in the elevator lobby of any
floor in the emergency evacuation zone 202 is activated, in step 310 the lobby smoke/fire
detector sends a second distinctive detection signal to the fire alarm panel 26. A
signal is sent to the CPU 38 where it is translated and sent to the elevator controller
16. The elevator controller 16 in step 312 then deactivates the hall call station
104 on the floor where the lobby smoke/fire detector was activated, thereby preventing
the car door assemblies 68 from opening at that floor. As a result, the occupants
on that floor must use the stairway for evacuation to the evacuation assistance floor
214. In one embodiment, audible recorded instructions are played over the recorded-voice
enunciator system so as to provide instructions to occupants to proceed to the stairwell
for evacuation, because the elevators are out of service.
[0087] When in step 309, the car smoke detector 176 detects smoke or in step 178 the hoistway
smoke detector 178 detects smoke, in step 314 that smoke detector sends a third distinctive
detection signal to the fire alarm panel 26, which sends the signal to the interconnection
system operator's CPU 38. The CPU 38 translates the signal and sends it to the elevator
controller 16. The elevator controller 16 in step 316 then initiates an emergency
recall sequence in which all hall call stations 104 and car destination buttons 86
are deactivated and all cars are moved and parked at the predesignated recall floor
188. The elevator controller then powers down, thereby taking the car out of service.
Audible instructions are played over the recorded-voice enunciator on the floors of
the emergency evacuation zone 202 to proceed to the stairwells for evacuation, because
the elevators are out of service. All remaining building occupants must await the
arrival of the fire department for rescue or use the building exit stairways for evacuation.
[0088] In the exemplary embodiment, the car controller 84 (see Figure 3) is equipped with
an emergency battery, having the capacity to open and close the hoistway and car door
assemblies 56 and 68 if the emergency power supply 40 is interrupted. When building
or emergency power is not available, the emergency battery energizes the door motion
controller 130 to move the hoistway and car door assemblies 56 and 68 to the closed
position. The car controller 84 then sends an alarm signal to the fire alarm panel
26, signaling a stranded elevator car.
[0089] In the exemplary embodiment, a sign placard such as the placard 320 illustrated in
Figure 8, is located in each elevator car and in each elevator lobby, as shown in
Figure 3. The placard provides instructions to building occupants regarding emergency
evacuation via the elevators. The placard 320 also provides information to the occupants
about using the stairway for evacuation.
[0090] The exemplary embodiment of the building egress system 4 of the present invention
provides an increased level of protection for elevator passengers traveling within
the hoistway shaft 42 and provides an evacuating sequence to evacuate the building
occupants in a safe manner during an emergency, such as a building fire. Further modifications
and improvements within the scope of the present invention can be made to the building
egress system for particular building configurations, including programming the interconnection
system 10 to measure the time between the detection of smoke or the like at individual
smoke/fire detectors 22, so as to monitor and anticipate the speed at which the smoke
and fire is spreading within the building.
Additional Fire Floors
[0091] If the building's elevator system 6 has more than one elevator car 20 and if smoke
is detected on a floor in the emergency evacuation zone 202, a second emergency evacuation
zone is established by the interconnection system operator's CPU 38 in the manner
described above. The evacuation assistance floor 214 remains as designated and described
above. Half of the available elevator cars are dedicated to the emergency evacuation
of the second emergency evacuation zone. If smoke is detected on another floor outside
the emergency evacuation zone 202, another emergency evacuation zone is established
in the manner described above and a second evacuation assistance floor is designated.
In the event a third emergency evacuation zone is established, one half of the available
cars are dedicated to the first emergency evacuation zone, one quarter of the available
elevator cars are dedicated to the second emergency evacuation zone, and one quarter
of the available elevator cars are dedicated to the third emergency evacuation zone.
The emergency evacuation sequence is then completed in each evacuation zone with the
available elevator cars for that evacuation zone.
Communication to Fire Department
[0092] In the exemplary embodiment, the fire alarm panel 26 is adapted to automatically
contact and provide an alarm signal and building status information directly to the
fire department. Accordingly, the fire department can determine the status of the
building 2 during an emergency condition while fire department personnel prepare to
leave the fire house or while in route to the building. When the fire department personnel
then arrive at the building, they can immediately address the emergency condition
without losing valuable time determining the building's status.
[0093] As best seen in Figure 5, the signal control system 25, such as the fire alarm panel
26, is operatively connected to a plurality of the building's systems 350, such as
elevator system 6, the smoke detectors 22, a fire suppression system 353, air handling
systems 355, fire door systems, and an elevator control system. The fire alarm panel
26 receives, collects, and stores the status information from the selected building
systems 350. Accordingly, the fire alarm panel 26 includes the data that defines the
current status of the building 2.
[0094] The fire alarm panel 26 also includes a modem 351 or other communication mechanism
connected to the panel's CPU and also connected to one or more telephone lines. The
fire alarm panel's CPU, via its communication protocol discussed above, transmits
the status information through the modem and the phone lines to a remote communication
system 352 at the fire department, which is remote from the building 2. The fire alarm
panel's CPU and the remote communication system, in one embodiment, are programmed
to allow the fire department to control some or all of the selected building systems
350 from the fire station or even from fire department vehicles equipped with a suitable
communication system. As a result, fire department personnel can monitor and control
the building's status upon receiving the initial alarm signal and prior to arriving
at the building 2 experiencing the emergency condition. The fire alarm panel's CPU
also provides the fire department with a summary of the building's floor plan and
systems, along with the condition of the building systems to as to enable the fire
department to establish an emergency response sequence for that particular building.
[0095] In operation, when the fire alarm panel 26 receives the fire alarm signal 200 or
the like, the fire alarm panel 26 polls the selected building systems 350 and collects
the status information. The status information includes, as an example, the location.
of the signaling floor, the evacuation assistance floor, the emergency evacuation
zone, and evacuation priority floors in the emergency evacuation zone. The status
information also includes data from the hoistway and elevator car detectors indicating
whether smoke has been detected in the hoistway or elevator car. The status information
also includes data defining the status of the elevator cars and the air handling systems
355 during the emergency condition.
[0096] The fire alarm panel 26 automatically contacts the remote fire department and sends
the alarm signal and the status information to the fire department communication system
352. The fire department personnel can then evaluate the status of the building systems,
and the information that identifies the particular location and condition of the emergency.
If the building conditions warrant considering the established emergency evacuation
sequence automatically created, as discussed above to the designated floor, the fire
department personnel would then selectively control the building systems, such as
controlling hoistway pressurization elevator car recall. Accordingly, the fire department
can remotely control the building systems as soon as the emergency signal is received
until the fire department personnel arrive at the building, at which time the fire
department personnel can control the building systems directly from within the building.
Reprogramming by the Fire Department
[0097] In the exemplary embodiment, the interconnection system operator's CPU 38 is reprogrammable
by fire department personnel to control the function of the elevator cars 20 during
a building emergency. Visual indication of the status, mode and location of all cars
is provided at the car position indicator 150 adjacent to the fire alarm panel 26
so the fire department has a full understanding of the status of each elevator car
20 prior to overriding the standard programming. Any number of elevators may be recalled
to the predesignated egress floor 188. The fire department can then manually control
and use the elevator cars to evacuate people from the emergency evacuation zone 202,
from the evacuation assistance floor 214, or from the remainder of the building 2.
The fire department can also manually control the elevator cars to stage men and equipment
at selected floors 21 relative to the fire floor. The fire department can 5 also establish
additional emergency evacuation zones as well as altering the priority of evacuation
floors in accordance with a modified evacuation procedure.
[0098] The size, spacing and priority of floors in the emergency evacuation zone can be
modified to provide a larger emergency evacuation zone, such as when a larger number
of elevator cars are available for the emergency evacuation procedure.
1. A multi-floor building (2), comprising:
a plurality of floors (21);
a plurality of detectors (22), at least one of the detectors being located on a respective
one of the floors, each detector being positioned to detect a selected emergency condition,
the detector that detects the emergency condition being a signaling detector that
generates a detector signal upon detecting the emergency condition;
a vertical transportation system (6) usable for moving building occupants between
selected floors during an emergency condition, the vertical transportation system
provides a first status signal;
an air handling system coupled to the vertical transportation system, the air handling
system provides a second status signal;
characterized by:
an emergency suppression system having suppression members on selected floors, the
emergency suppression system provides a third status signal; and
a signal control system (26), coupled to the detectors to receive the detector signal
from the signaling detector, the signal control system being coupled to one of the
vertical transportation system, the air handling system, and the emergency suppression
system and receives one of the first, second, and third status signals, the signal-control
system having a communication mechanism connected to a remote communication system
at a location remote from the building, the communication mechanism sends the detector
signal and one of the first, second, and third status signals to the remote communication
system to provide building status information to the location remote from the building,
and the communication mechanism configured to receive a signal &om the remote communication
system to control at least one of the vertical transportation system, the air handling
system, and the emergency suppression system.
2. The multi-floor building of claim 1 wherein the signal control system receives the
first, second, and third status signals and provides the first, second, and third
status signals to the remote communication system.
3. The multi-floor building of claim 1 wherein the communication mechanism is a modem.
4. The multi-floor building of claim 1 wherein the emergency suppression system is a
fire suppression system.
5. The multi-floor building of claim 1 wherein the air handling system includes a hoistway
pressurization system.
6. The multi-floor building of claim 1 wherein the vertical transportation system in
an elevator system having an elevator car and an elevator controller.
7. The multi-floor building of claim I wherein the plurality of floors includes a building
exit floor, and the vertical transport system includes:
a transport unit sized to hold at least one building occupant and vertically movable
in the building, the transport unit being positionable to locations adjacent to selected
floors in the building;
a transport controller coupled to the transport unit to move the transport unit to
the locations adjacent to the selected floors; and
a control unit coupled to the transport controller to send a selected control signal
to the transport controller to move the transport unit to a selected one of the locations
adjacent to the selected floors, the control unit being coupled to the detectors to
receive the detector signal from the signaling detector, the control unit defining
a floor where the signaling detector is located as a signaling floor, defining an
evacuation assistance floor that is different than the building exit floor and that
is spaced apart from the signaling floor, and defining floors considered to be non-emergency
floors where the transport unit will be restricted from receiving building occupants
during the emergency condition while the building occupants are being evacuated from
the signaling floor, the control unit being configured to send the control signal
to the transport controller to cause movement of the transport unit between the signaling
floor and the evacuation assistance floor and not the nonemergency floors during the
emergency condition to evacuate building occupants from the signaling floor to the
evacuation assistance floor during the emergency condition.
8. The building of claim 7 wherein the first status signal includes data defining a location
of the emergency evacuation assistance floor defined by the control unit.
9. The building of claim 7 wherein the first status signal includes data defining a location
of the first signaling floor.
10. The building of claim 7 wherein the control unit is configured to establish an evacuation
zone that includes the signaling floor as a first priority evacuation floor and a
second priority evacuation floor one floor away from the signaling floor, the control
unit determining which of the first and second priority evacuation floors has a highest
priority and controlling the transport controller to move the transport unit to evacuate
the highest priority evacuation floor first.
11. The building of claim 10 wherein the first status signal includes data defining a
location of the evacuation zone.
12. The building of claim 10 wherein the first priority evacuation floor is a higher priority
evacuation floor than the second priority evacuation floor.
13. The building of claim 10 wherein the second priority evacuation floor is one floor
away from the signaling floor in a first direction, and the evacuation zone has a
third priority evacuation floor located one floor away from the signaling floor in
a second direction, and the control unit being configured to send the control signal
to the transport controller to move the transport unit between the first, second and
third priority evacuation floors, and the evacuation assistance floor to evacuate
building occupants from first, second, and third priority evacuation floors to the
evacuation assistance floor.
14. The building of claim 7 wherein the signaling floor is a first priority evacuation
floor, and the building further includes a second priority evacuation floor located
one floor above the signaling floor, a third priority evacuation floor located one
floor below the signaling floor, and a fourth priority evacuation floor located two
floors above the signaling floor, the control unit being configured to send the control
signal to the transport controller to move the transport unit between the first, second,
third, and fourth priority evacuation floors, and the evacuation assistance floor
to evacuate building occupants from the first, second, third, and fourth priority
evacuation floors to the evacuation assistance floor.
15. The building of claim 14 wherein the control unit is configured to send the control
signal to the transport controller to evacuate building occupants from the floors
with the higher priority before floors with a lower priority, and wherein the first
priority evacuation floor is the highest priority evacuation floor, the second priority
evacuation floor is the second highest priority evacuation floor, the third priority
evacuation floor is the third highest priority evacuation floor, and the fourth priority
evacuation floor is the fourth highest priority evacuation floor.
16. The building of claim 14 wherein the first status signal includes data defining a
location and priority of the first, second, third, and fourth priority evacuation
floors.
17. The building of claim 7 wherein the transport unit is an elevator car, and the transport
controller is an elevator controller.
18. The building of claim 1 wherein the detectors are smoke detectors.
19. The building of claim 7 wherein the signal control system is a fire alarm panel to
which the detectors are operatively connected, and the control unit is an interconnection
device that communicates with the detectors and the transport controller, the interconnection
device having a central processing unit that establishes an evacuation zone upon detection
of the emergency condition that includes the signaling floor and at least one additional
floor from which the transport unit will receive building occupants during the emergency
condition for evacuation to the evacuation assistance floor.
20. The building of claim 7, further including a hoistway detector that detects the emergency
condition if located in a hoistway within which the transportation unit is vertically
movable, the hoistway detector being coupled to the control unit and adapted to send
a hoistway detection signal to the control unit when the hoistway detector detects
the emergency condition in the hoistway, the control unit sending a deactivation signal
to the transport controller to take the transport unit out of service in response
to the control unit receiving the hoistway detection signal.
21. The building of claim 20 wherein the hoistway detector sends the hoistway detection
signal to the signal control system, and the communication mechanism sends the hoistway
detection signal to the remote communication system to provide hoistway status information
to the location remote from the building.
22. The building of claim 20 wherein the transport controller moves the transportation
unit to a parked, out-of-service position in response to the transport controller
receives the deactivation signal.
23. The building of claim 7 wherein the vertical transportation system includes a hoistway
within which the transport unit is movably positioned, and a transport detector mounted
on the transport unit, the transport detector being operatively connected to the control
unit and adapted to send an emergency detection signal to the control unit when the
transport detector detects the emergency condition, the control unit sending a deactivation
signal to the transport controller to deactivate the transport unit in response to
the control unit receiving the emergency detection signal, the transport controller
moving the transport unit to a parked, out-of-service position in the hoistway in
response to the deactivation signal.
24. The building of claim 23 wherein the transport detector sends the emergency detection
signal to the signal control system, and the communication mechanism sends the emergency
detection signal to the remote communication system to provide transport unit status
information to the location remote from the building.
25. The building of claim 7 wherein a plurality of the floors each have a floor lobby,
and each of the floor lobbies has a floor lobby detector, the floor lobby detectors
being coupled to the control unit, each floor lobby detector providing an emergency
signal to the control unit when the floor lobby detector detects the emergency condition
in the floor lobby, the control unit in response thereto sending a by-pass signal
to the transport controller that prevents the transport unit from being used to evacuate
building occupants from the floor with the floor lobby detector which detected the
emergency condition.
26. The building of claim 25 wherein the floor lobby detector provides the emergency signal
to the signal control system when one of the floor lobby detectors detects the emergency
condition in the floor lobby, and the communication mechanism sends the emergency
signal to the remote communication system.
27. A method of evacuating building occupants from a building having a plurality of floors,
including a building exit floor (188), and an elevator system (6) having an elevator
car that is positionable at locations adjacent to selected ones of the floors, comprising:
detecting an emergency condition on a signaling floor (206) in the building;
characterized by :
defining an evacuation zone (202) in a portion of the building during the emergency
condition, the evacuation zone including the signaling floor and an evacuation assistance
floor (214) that is a selected number of floors away from the signaling floor and
that is not the building exit floor, the evacuation zone being defined not to include
floors considered to be non-emergency floors other than the evacuation assistance
floor;
sending a plurality of status signals to a signal control system (26), the status
signals providing data of status of the building systems, the plurality of status
signals including a first status signal from the signaling floor to the signal control
system identifying which floor is the signaling floor; and a second status signal
from the elevator system to the signal control system providing status information
about the elevator system;
sending the plurality of status signals from the signal control system to a remote
communication system at a location remote from the building to provide building status
information; and
evacuating with the elevator car one or more building occupants from the evacuation
zone to the evacuation assistance floor.
28. The method of claim 27 wherein sending the first and second status signals includes
sending the first and second status signals to a fire department remote from the building.
29. The method of claim 27 wherein sending the plurality of status signals includes sending
the status signals by a modem over telephone lines to the remote communication system.
30. The method of claim 27 wherein evacuating with the elevator car the one or more building
occupants includes automatically evacuation the building occupants independent upon
arrival of emergency assistance personnel to the building.
31. The method of claim 27 wherein evacuating the one or more building occupants includes:
moving the elevator car to the signaling floor to allow the building occupant to enter
the elevator car from the signaling floor;
moving the elevator car from the signaling floor after at least one of the building
occupants from the signaling floor has entered the elevator car, to the evacuation
assistance floor to allow the building occupant from the signaling floor to exit the
elevator car onto the evacuation assistance floor; and
restricting the movement of the elevator car to not include movement of the elevator
car to the non-emergency floors other than the evacuation assistance floor while the
building occupant is being evacuated from the signaling floor.
32. The method of claim 27 wherein detecting an emergency condition includes detecting
smoke with a smoke detector on the signaling floor.
33. The method of claim 27 wherein defining the evacuation zone includes defining the
evacuation zone as including the signaling floor, a first evacuation priority floor
located one floor away from the signaling floor in a first direction, a second evacuation
priority floor located one floor away from the signaling floor in a second direction,
and a third evacuation priority floor located two floors away from the signaling floor
in the first direction, and the method further includes moving the elevator car to
one of the first, second, and third evacuation priority floors and the signaling floor
to allow building occupants to enter the elevator car therefrom and next moving the
elevator car to the evacuation assistance floor.
34. The method of claim 33, further including identifying a plurality of elevator call
signals initiated from at least two different ones of the first, second, and third
evacuation priority floors and the signaling floor, and wherein moving the elevator
car to the one of the first, second, and third evacuation priority floors and the
signaling floor, includes moving the elevator car to the one of the identified floors
from which the elevator call signals were initiated with the highest evacuation priority
first, considering the signaling floor as having the first highest evacuation priority,
the first evacuation priority floor having the second highest evacuation priority,
the second evacuation priority floor having the third highest evacuation priority,
and the third evacuation priority floor having the fourth highest evacuation priority.
35. The method of claim 27 for use when the building has a hoistway and the elevator car
is movably positioned in the hoistway, the method further including monitoring the
hoistway for an emergency condition, and upon detection of an emergency condition
in the hoistway, sending a hoistway emergency signal to the remote communication system
indicating the emergency condition in the hoistway.
36. The method of claim 27, further including monitoring the elevator car for an emergency
condition, and upon detection of an emergency condition at the elevator car, sending
an elevator car emergency signal to the remote communication system indicating the
emergency condition in the elevator car.
1. Ein Multi-Stockwerkgebäude (2), umfassend:
- eine Vielzahl von Stockwerken (21);
- eine Vielzahl von Detektoren (22), wobei sich wenigstens einer der Detektoren in
einem jeweiligen Stockwerk befindet und jeder Detektor zum Erfassen einer ausgewählten
Notsituation positioniert ist, wobei der Detektor, der die Notsituation erfasst, ein
meldender Detektor ist, der bei Erfassen der Notsituation ein Detektorsignal erzeugt;
- ein vertikales Transportsystem (6), das bei einer Notsituation zum Fortbewegen von
Gebäudenutzern zwischen ausgewählten Stockwerken genutzt werden kann, wobei das vertikale
Transportsystem ein erstes Statussignal bereitstellt;
- ein mit dem vertikalen Transportsystem gekoppeltes Klimatisierungssystem, wobei
das Klimatisierungssystem ein zweites Statussignal bereitstellt;
gekennzeichnet durch:
- ein Notunterdrückungssystem mit Unterdrückungselementen in ausgewählten Stockwerken,
wobei das Notunterdrückungssystem ein drittes Statussignal bereitstellt; und
- ein mit den Detektoren gekoppeltes Signalsteuersystem (26) zum Empfang des Detektorsignals
von dem meldenden Detektor, wobei das Signalsteuersystem mit einem von dem vertikalen
Transportsystem, dem Klimatisierungssystem und dem Notunterdrückungssystem gekoppelt
ist und eines der ersten, zweiten und dritten Statussignale empfängt, das Signalsteuersystem
über einen Kommunikationsmechanismus verfügt, der mit einem Fernkommunikationssystem
an einem von dem Gebäude entfernten Ort verbunden ist, der Kommunikationsmechanismus
das Detektorsignal und eines der ersten, zweiten und dritten Statussignale an das
Fernkommunikationssystem sendet, um Gebäudestatusinformationen an den von dem Gebäude
entfernten Ort zu liefern, und der Kommunikationsmechanismus konfiguriert ist, ein
Signal von dem Fernkommunikationssystem zu empfangen, um wenigstens eines von dem
vertikalen Transportsystem, dem Klimatisierungssystem und dem Notunterdrückungssystem
zu steuern.
2. Multi-Stockwerkgebäude nach Anspruch 1, wobei das Signalsteuersystem die ersten, zweiten
und dritten Statussignale empfängt und die ersten, zweiten und dritten Statussignale
an das Fernkommunikationssystem liefert.
3. Multi-Stockwerkgebäude nach Anspruch 1, wobei der Kommunikationsmechanismus ein Modem
ist.
4. Multi-Stockwerkgebäude nach Anspruch 1, wobei das Notunterdrückungssystem ein Brandunterdrückungssystem
ist.
5. Multi-Stockwerkgebäude nach Anspruch 1, wobei das Klimatisierungssystem ein Schachtdrucksystem
umfasst.
6. Multi-Stockwerkgebäude nach Anspruch 1, wobei das vertikale Transportsystem ein Aufzugssystem
mit einer Aufzugskabine und einer Aufzugssteuerung ist.
7. Multi-Stockwerkgebäude nach Anspruch 1, wobei die Vielzahl von Stockwerken ein Gebäudeausgangsstockwerk
umfasst und das vertikale Transportsystem Folgendes umfasst:
- eine Transporteinheit, die so bemessen ist, dass wenigstens ein Gebäudenutzer aufgenommen
werden kann, und die vertikal in dem Gebäude bewegt werden kann, wobei die Transporteinheit
an Orten positioniert werden kann, die an ausgewählte Stockwerke in dem Gebäude angrenzen;
- eine mit der Transporteinheit gekoppelte Transportsteuerung zum Bewegen der Transporteinheit
an die Orte, die an die ausgewählten Stockwerke angrenzen; und
- eine mit der Transportsteuerung gekoppelte Steuereinheit zum Senden eines ausgewählten
Steuersignals an die Transportsteuerung, um die Transporteinheit an einen ausgewählten
der Orte, die an die ausgewählten Stockwerke angrenzen, zu bewegen, wobei die Steuereinheit
mit den Detektoren gekoppelt ist, um das Detektorsignal von dem meldenden Detektor
zu empfangen, die Steuereinheit als ein meldendes Stockwerk dasjenige definiert, wo
der meldende Detektor angeordnet ist, ein Evakuierungshilfsstockwerk definiert, das
nicht das Gebäudeausgangsstockwerk ist und sich in einem Abstand zu dem meldenden
Stockwerk befindet, und Stockwerke definiert, die als Nichtnotfallstockwerke erachtet
werden, wobei der Transporteinheit nicht gestattet wird, in der Notsituation Gebäudenutzer
aufzunehmen, während Gebäudenutzer aus dem meldenden Stockwerk evakuiert werden, wobei
die Steuereinheit konfiguriert ist, das Steuersignal an die Transportsteuerung zu
senden, um während der Notsituation die Bewegung der Transporteinheit zwischen dem
meldenden Stockwerk und dem Evakuierungshilfsstockwerk und nicht zu den Nichtnotfallstockwerken
zu veranlassen, um während der Notsituation Gebäudenutzer aus dem meldenden Stockwerk
in das Evakuierungshilfsstockwerk zu evakuieren.
8. Gebäude nach Anspruch 7, wobei das erste Statussignal Daten umfasst, die einen Ort
des Notevakuierungshilfsstockwerks definieren, das von der Steuereinheit definiert
wurde.
9. Gebäude nach Anspruch 7, wobei das erste Statussignal Daten umfasst, die einen Ort
des ersten meldenden Stockwerks definieren.
10. Gebäude nach Anspruch 7, wobei die Steuereinheit konfiguriert ist, um eine Evakuierungszone
festzulegen, die das meldende Stockwerk als ein Stockwerk erster Evakuierungspriorität
und ein Stockwerk zweiter Evakuierungspriorität, das ein Stockwerk von dem meldenden
Stockwerk entfernt ist, umfasst, wobei die Steuereinheit bestimmt, welches der Stockwerke
erster und zweiter Evakuierungspriorität eine höchste Priorität hat, und die Transportsteuerung
steuert, um die Transporteinheit so zu bewegen, dass das Stockwerk höchster Evakuierungspriorität
zuerst evakuiert wird.
11. Gebäude nach Anspruch 10, wobei das erste Statussignal Daten umfasst, die einen Ort
der Evakuierungszone definieren.
12. Gebäude nach Anspruch 10, wobei das Stockwerk erster Evakuierungspriorität ein Stockwerk
höherer Evakuierungspriorität ist als das Stockwerk zweiter Evakuierungspriorität.
13. Gebäude nach Anspruch 10, wobei das Stockwerk zweiter Evakuierungspriorität in einer
ersten Richtung ein Stockwerk von dem meldenden Stockwerk entfernt ist, und die Evakuierungszone
ein Stockwerk dritter Evakuierungspriorität aufweist, das in einer zweiten Richtung
ein Stockwerk von dem meldenden Stockwerk entfernt ist, und die Steuereinheit konfiguriert
ist, das Steuersignal an die Transportsteuerung zu senden, um die Transporteinheit
zwischen den Stockwerken erster, zweiter und dritter Evakuierungspriorität und dem
Evakuierungshilfsstockwerk zu bewegen, um Gebäudenutzer aus den Stockwerken erster,
zweiter und dritter Evakuierungspriorität in das Evakuierungshilfsstockwerk zu evakuieren.
14. Gebäude nach Anspruch 7, wobei das meldende Stockwerk ein Stockwerk erster Evakuierungspriorität
ist und das Gebäude darüber hinaus ein Stockwerk zweiter Evakuierungspriorität, das
sich ein Stockwerk über dem meldenden Stockwerk befindet, ein Stockwerk dritter Evakuierungspriorität,
das sich ein Stockwerk unter dem meldenden Stockwerk befindet, und ein Stockwerk vierter
Evakuierungspriorität, das sich zwei Stockwerke über dem meldenden Stockwerk befindet,
umfasst, wobei die Steuereinheit konfiguriert ist, das Steuersignal an die Transportsteuerung
zu senden, um die Transporteinheit zwischen den Stockwerken erster, zweiter, dritter
und vierter Evakuierungspriorität und dem Evakuierungshilfsstockwerk zu bewegen, um
Gebäudenutzer aus den Stockwerken erster, zweiter, dritter und vierter Evakuierungspriorität
zu dem Evakuierungshilfsstockwerk zu evakuieren.
15. Gebäude nach Anspruch 14, wobei die Steuereinheit konfiguriert ist, das Steuersignal
an die Transportsteuerung zu senden, um Gebäudenutzer aus den Stockwerken mit der
höheren Priorität vor den Stockwerken mit einer niedrigeren Priorität zu evakuieren,
wobei das Stockwerk erster Evakuierungspriorität das Stockwerk der höchsten Evakuierungspriorität
ist, das Stockwerk zweiter Evakuierungspriorität das Stockwerk der zweithöchsten Evakuierungspriorität
ist, das Stockwerk dritter Evakuierungspriorität das Stockwerk der dritthöchsten Evakuierungspriorität
ist und das Stockwerk vierter Evakuierungspriorität das Stockwerk der vierthöchsten
Evakuierungspriorität ist.
16. Gebäude nach Anspruch 14, wobei das erste Statussignal Daten umfasst, die Ort und
Priorität der Stockwerke erster, zweiter, dritter und vierter Evakuierungspriorität
definieren.
17. Gebäude nach Anspruch 7, wobei die Transporteinheit eine Aufzugskabine ist und die
Transportsteuerung eine Aufzugssteuerung ist.
18. Gebäude nach Anspruch 1, wobei die Detektoren Rauchdetektoren sind.
19. Gebäude nach Anspruch 7, wobei das Signalsteuersystem eine Feueralarmkonsole ist,
mit der die Detektoren betriebsbereit verbunden sind, und die Steuereinheit eine Zusammenschaltungsvorrichtung
ist, die mit den Detektoren und der Transportsteuerung kommuniziert, wobei die Zusammenschaltungsvorrichtung
eine Zentraleinheit aufweist, die bei Erfassen der Notsituation eine Evakuierungszone
einrichtet, die das meldende Stockwerk und wenigstens ein zusätzliches Stockwerk umfasst,
aus dem die Transporteinheit während der Notsituation Gebäudenutzer zum Evakuieren
in das Evakuierungshilfsstockwerk aufnimmt.
20. Gebäude nach Anspruch 7, das darüber hinaus einen Schachtdetektor umfasst, der die
Notsituation erfasst, wenn er sich in einem Schacht befindet, in dem die Transporteinheit
vertikal beweglich ist, wobei der Schachtdetektor mit der Steuereinheit gekoppelt
und angepasst ist, ein Schachterfassungssignal an die Steuereinheit zu senden, wenn
der Schachtdetektor die Notsituation in dem Schacht erfasst, und die Steuereinheit
ein Deaktivierungssignal an die Transportsteuerung sendet, um als Reaktion auf den
Empfang des Schachterfassungssignals durch die Steuereinheit die Transporteinheit
außer Betrieb zu nehmen.
21. Gebäude nach Anspruch 20, wobei der Schachtdetektor ein Schachterfassungssignal an
das Signalsteuersystem sendet und der Kommunikationsmechanismus das Schachterfassungssignal
an das Fernkommunikationssystem sendet, um Schachtstatusinformationen an den von dem
Gebäude entfernten Ort zu liefern.
22. Gebäude nach Anspruch 20, wobei die Transportsteuerung als Reaktion auf den Empfang
des Deaktivierungssignals durch die Transportsteuerung die Transporteinheit in eine
geparkte Außerbetriebsposition bewegt.
23. Gebäude nach Anspruch 7, wobei das vertikale Transportsystem einen Schacht umfasst,
in dem die Transporteinheit beweglich positioniert ist, und ein Transportdetektor
auf der Transporteinheit montiert ist, wobei der Transportdetektor betriebsbereit
mit der Steuereinheit verbunden und angepasst ist, ein Notfalterfassungssignal an
die Steuereinheit zu senden, wenn der Transportdetektor die Notsituation erfasst,
die Steuereinheit ein Deaktivierungssignal an die Transportsteuerung sendet, um als
Reaktion auf den Empfang des Notfallerfassungssignals durch die Steuereinheit die
Transporteinheit zu deaktivieren, und die Transportsteuerung als Reaktion auf das
Deaktivierungssignal die Transporteinheit in eine geparkte Außerbetriebsposition in
dem Schacht bewegt.
24. Gebäude nach Anspruch 23, wobei der Transportdetektor das Notfallerfassungssignal
an das Signalsteuerungssystem sendet und der Kommunikationsmechanismus das Notfallerfassungssignal
an das Fernkommunikationssystem sendet, um Transporteinheitsstatusinformationen an
den von dem Gebäude entfernten Ort zu liefern.
25. Gebäude nach Anspruch 7, wobei eine Vielzahl der Stockwerke jeweils eine Stockwerksvorhalle
hat und jede der Stockwerksvorhallen einen Stockwerksvorhallendetektor aufweist, wobei
die Stockwerksvorhallendetektoren mit der Steuereinheit gekoppelt sind, jeder Stockwerksvorhallendetektor
ein Notsignal an die Steuereinheit liefert, wenn der Stockwerksvorhallendetektor die
Notsituation in der Stockwerksvorhalle erfasst, und die Steuereinheit als Reaktion
darauf ein Umgehungssignal an die Transportsteuerung sendet, das verhindert, dass
die Transporteinheit dazu verwendet wird, Gebäudenutzer aus dem Stockwerk mit dem
Stockwerksvorhallendetektor, der die Notsituation erfasst hat, zu evakuieren.
26. Gebäude nach Anspruch 25, wobei der Stockwerksvorhallendetektor das Notsignal an das
Signalsteuerungssystem liefert, wenn einer der Stockwerksvorhallendetektoren die Notsituation
in der Stockwerksvorhalle erfasst, und der Kommunikationsmechanismus das Notsignal
an das Fernkommunikationssystem sendet.
27. Verfahren zum Evakuieren von Gebäudenutzern aus einem Gebäude mit einer Vielzahl von
Stockwerken, die ein Gebäudeausgangsstockwerk (188) und ein Aufzugssystem (6) mit
einer Aufzugskabine umfassen, die an Orten positioniert werden kann, die an ausgewählte
Orte in den Stockwerken angrenzen, umfassend:
- Erfassen einer Notsituation in einem meldenden Stockwerk (206) in dem Gebäude;
gekennzeichnet durch:
- Definieren einer Evakuierungszone (202) in einem Teil des Gebäudes während der Notsituation,
wobei die Evakuierungszone ein meldendes Stockwerk und ein Evakuierungshilfsstockwerk
(214) umfasst, das eine ausgewählte Anzahl von Stockwerken von dem meldenden Stockwerk
entfernt ist und das nicht das Gebäudeausgangsstockwerk ist, und die Evakuierungszone
so definiert ist, dass keine Stockwerke enthalten sind, die als Nichtnotfallstockwerke
erachtet werden und nicht das Evakuierungshilfsstockwerk sind;
- Senden einer Vielzahl von Statussignalen an ein Signalsteuersystem (26), wobei die
Statussignale Daten zu dem Status des Gebäudesystems bereitstellen und die Vielzahl
von Statussignalen ein erstes Statussignal von dem meldenden Stockwerk an das Signalsteuersystem
umfasst, das angibt, welches Stockwerk das meldende Stockwerk ist, und ein zweites
Statussignal von dem Aufzugssystem an das Signalsteuersystem umfasst, das Statusinformationen
zu dem Aufzugssystem bereitstellt;
- Senden der Vielzahl von Statussignalen von dem Signalsteuersystem an ein Fernkommunikationssystem
an einem von dem Gebäude entfernten Ort, um Gebäudestatusinformationen bereitzustellen;
und
- Evakuieren von einem oder mehreren Gebäudenutzern mit der Aufzugskabine aus der
Evakuierungszone in das Evakuierungshilfsstockwerk.
28. Verfahren nach Anspruch 27, wobei das Senden der ersten und zweiten Statussignale
das Senden der ersten und zweiten Statussignale an eine von dem Gebäude entfernte
Feuerwehr umfasst.
29. Verfahren nach Anspruch 27, wobei das Senden der Vielzahl von Statussignalen das Senden
der Statussignale mit einem Modem über Telefonleitungen an das Fernkommunikationssystem
umfasst.
30. Verfahren nach Anspruch 27, wobei das Evakuieren von einem oder mehreren Gebäudenutzern
mit der Aufzugskabine automatisch das Evakuieren der Gebäudenutzer unabhängig von
dem Eintreffen von Notfallhilfspersonal am Gebäude umfasst.
31. Verfahren nach Anspruch 27, wobei das Evakuieren von einem oder mehreren Gebäudenutzern
Folgendes umfasst:
- Bewegen der Aufzugskabine zu dem meldenden Stockwerk, um dem Gebäudenutzer zu ermöglichen,
aus dem meldenden Stockwerk in die Aufzugskabine einzutreten;
- Bewegen der Aufzugskabine von dem meldenden Stockwerk, nachdem wenigstens einer
der Gebäudenutzer aus dem meldenden Stockwerk in die Aufzugskabine eingetreten ist,
zu dem Evakuierungshilfsstockwerk, um dem Gebäudenutzer aus dem meldenden Stockwerk
zu ermöglichen, die Aufzugskabine in dem Evakuierungshilfsstockwerk zu verlassen;
und
- Beschränken der Bewegung der Aufzugskabine, um die Bewegung der Aufzugskabine zu
den Nichtnotfallstockwerken außer dem Evakuierungshilfsstockwerk auszuschließen, während
der Gebäudenutzer aus dem meldenden Stockwerk evakuiert wird.
32. Verfahren nach Anspruch 27, wobei das Erfassen einer Notsituation das Erfassen von
Rauch mit einem Rauchdetektor in dem meldenden Stockwerk umfasst.
33. Verfahren nach Anspruch 27, wobei das Definieren der Evakuierungszone beinhaltet,
dass die Evakuierungszone so definiert wird, dass sie das meldende Stockwerk, ein
in einer ersten Richtung ein Stockwerk von dem meldenden Stockwerk entferntes Stockwerk
erster Evakuierungspriorität, ein in einer zweiten Richtung ein Stockwerk von dem
meldenden Stockwerk entferntes Stockwerk zweiter Evakuierungspriorität und ein in
der ersten Richtung zwei Stockwerke von dem meldenden Stockwerk entferntes Stockwerk
dritter Evakuierungspriorität umfasst, und das Verfahren darüber hinaus beinhaltet,
dass die Aufzugskabine zu einem der Stockwerke erster, zweiter und dritter Evakuierungspriorität
und des meldenden Stockwerks bewegt wird, um den Gebäudenutzern zu ermöglichen, aus
diesem in die Aufzugskabine einzutreten, und danach die Aufzugskabine zu dem Evakuierungshilfsstockwerk
bewegt wird.
34. Verfahren nach Anspruch 33, das darüber hinaus das Erkennen einer Vielzahl von Aufzugrufsignalen
umfasst, die von wenigstens zwei verschiedenen der Stockwerke erster, zweiter und
dritter Evakuierungspriorität und des meldenden Stockwerks ausgelöst wurden, wobei
das Bewegen der Aufzugskabine zu einem der Stockwerke erster, zweiter und dritter
Evakuierungspriorität und des meldenden Stockwerks beinhaltet, dass die Aufzugskabine
zuerst zu dem einen der erkannten Stockwerke bewegt wird, von dem die Aufzugrufsignale
mit der höchsten Evakuierungspriorität ausgelöst wurden, wobei das meldende Stockwerk
als das Stockwerk mit der höchsten Evakuierungspriorität, das Stockwerk erster Evakuierungspriorität
als das Stockwerk mit der zweithöchsten Evakuierungspriorität, das Stockwerk zweiter
Evakuierungspriorität als das Stockwerk mit der dritthöchsten Evakuierungspriorität
und das Stockwerk dritter Evakuierungspriorität als das Stockwerk mit der vierthöchsten
Evakuierungspriorität erachtet wird.
35. Verfahren nach Anspruch 27 zum Verwenden, wenn das Gebäude einen Schacht hat und die
Aufzugskabine beweglich in dem Schacht positioniert ist, wobei das Verfahren darüber
hinaus das Überwachen des Schachts im Hinblick auf eine Notsituation und, bei Erfassen
einer Notsituation in dem Schacht, das Senden eines Schachtnotsignals an das Fernkommunikationssystem
umfasst, um die Notsituation in dem Schacht anzuzeigen.
36. Verfahren nach Anspruch 27, das darüber hinaus das Überwachen der Aufzugskabine im
Hinblick auf eine Notsituation und, bei Erfassen einer Notsituation an der Aufzugskabine,
das Senden eines Aufzugskabinennotsignals an das Fernkommunikationssystem umfasst,
um die Notsituation in der Aufzugskabine anzuzeigen.
1. Bâtiment multi-niveaux (2), comprenant :
une pluralité d'étages (21) ;
une pluralité de détecteurs (22), au moins un des détecteurs étant situé sur un respectif
parmi les étages, chaque détecteur étant positionné pour détecter une condition d'urgence
sélectionnée, le détecteur qui détecte la condition d'urgence étant un détecteur émettant
un signal qui génère un signal de détecteur à la détection de la condition d'urgence
;
un système de transport vertical (6) pouvant être utilisé pour déplacer des occupants
du bâtiment entre des étages sélectionnés au cours d'une condition d'urgence, le système
de transport vertical fournissant un premier signal de condition ;
un système de traitement de l'air couplé au système de transport vertical, le système
de traitement de l'air fournissant un deuxième signal de condition ;
caractérisé par :
un système de suppression d'urgence ayant des éléments de suppression sur des étages
sélectionnés, le système de suppression d'urgence fournissant un troisième signal
de condition ; et
un système de commande de signal (26) couplé aux détecteurs pour recevoir le signal
de détecteur provenant du détecteur émettant un signal, le système de commande de
signal étant couplé à un parmi le système de transport vertical, le système de traitement
de l'air, et le système de suppression d'urgence et recevant un parmi les premier,
deuxième, et troisième signaux de condition, le système de commande de signal ayant
un mécanisme de communication connecté à un système de communication à distance à
un emplacement éloigné du bâtiment, le mécanisme de communication envoyant le signal
de détecteur et un parmi les premier, second et troisième signaux de condition au
système de communication étant à distance pour fournir des informations de condition
concernant le bâtiment à l'emplacement éloigné du bâtiment, et le mécanisme de communication
étant configuré pour recevoir un signal provenant du système de communication à distance
pour commander au moins un parmi le système de transport vertical, le système de traitement
de l'air, et le système de suppression d'urgence.
2. Bâtiment multi-niveaux selon la revendication 1 dans lequel le système de commande
de signal reçoit les premier, second et troisième signaux de condition et fournit
les premier, second et troisième signaux de condition au système de communication
à distance.
3. Bâtiment multi-niveaux selon la revendication 1 dans lequel le mécanisme de communication
est un modem.
4. Bâtiment multi-niveaux selon la revendication 1 dans lequel le système de suppression
d'urgence est un système de suppression des incendies.
5. Bâtiment multi-niveaux selon la revendication 1 dans lequel le système de traitement
de l'air comprend un système de mise sous pression de cage.
6. Bâtiment multi-niveaux selon la revendication 1 dans lequel le système de transport
vertical est un système d'ascenseur ayant une cabine d'ascenseur et une commande d'ascenseur.
7. Bâtiment multi-niveaux selon la revendication 1 dans lequel la pluralité d'étages
comprend un étage de sortie du bâtiment, et le système de transport vertical comprend
:
une unité de transport dimensionnée pour contenir au moins un occupant du bâtiment
et mobile verticalement dans le bâtiment, l'unité de transport pouvant être positionnée
à des emplacements adjacents à des étages sélectionnés dans le bâtiment ;
une commande de transport couplée à l'unité de transport pour déplacer l'unité de
transport jusqu'aux emplacements adjacents aux étages sélectionnés ; et
une unité de commande couplée à la commande de transport pour envoyer un signal de
commande sélectionné à la commande de transport pour déplacer l'unité de transport
jusqu'à un sélectionné parmi les emplacements adjacents aux étages sélectionnés, l'unité
de commande étant couplée aux détecteurs pour recevoir le signal de détecteur provenant
du détecteur émettant un signal, l'unité de commande définissant un étage où le détecteur
émettant un signal est situé en tant qu'étage émettant un signal, définissant un étage
d'assistance d'évacuation qui est différent de l'étage de sortie du bâtiment et qui
est espacé de l'étage émettant un signal, et définissant des étages considérés comme
étant des étages de non-urgence où l'unité de transport sera empêchée de recevoir
des occupants du bâtiment au cours de la condition d'urgence alors que les occupants
du bâtiment sont en train d'être évacués de l'étage émettant un signal, l'unité de
commande étant configurée pour envoyer le signal de commande à la commande de transport
pour entraîner le mouvement de l'unité de transport entre l'étage émettant un signal
et l'étage d'assistance d'évacuation et non les étages de non-urgence au cours de
la condition d'urgence pour évacuer les occupants du bâtiment de l'étage émettant
un signal vers l'étage d'assistance d'évacuation au cours de la condition d'urgence.
8. Bâtiment selon la revendication 7 dans lequel le premier signal de condition comprend
des données définissant un emplacement de l'étage d'assistance d'évacuation d'urgence
défini par l'unité de commande.
9. Bâtiment selon la revendication 7 dans lequel le premier signal de condition comprend
des données définissant un emplacement du premier étage émettant un signal.
10. Bâtiment selon la revendication 7 dans lequel l'unité de commande est configurée pour
établir une zone d'évacuation qui comprend 'l'étage émettant un signal en tant qu'un
premier étage d'évacuation prioritaire et un second étage d'évacuation prioritaire
un étage plus loin que l'étage émettant un signal, l'unité de commande déterminant
lequel des premier et second étages d'évacuation prioritaires a une priorité plus
importante et commandant la commande de transport pour déplacer l'unité de transport
pour évacuer l'étage d'évacuation ayant la priorité la plus importante en premier.
11. Bâtiment selon la revendication 10 dans lequel le premier signal de condition comprend
des données définissant un emplacement de la zone d'évacuation.
12. Bâtiment selon la revendication 10 dans lequel le premier étage d'évacuation prioritaire
est un étage d'évacuation ayant une priorité plus importante que le deuxième étage
d'évacuation prioritaire.
13. Bâtiment selon la revendication 10 dans lequel le deuxième étage d'évacuation prioritaire
est un étage plus loin que l'étage émettant un signal dans une première direction,
et la zone d'évacuation a un troisième étage d'évacuation prioritaire situé un étage
plus loin que l'étage émettant un signal dans une seconde direction, et l'unité de
commande étant configurée pour envoyer le signal de commande à la commande de transport
pour déplacer l'unité de transport entre les premier, deuxième et troisième étages
d'évacuation prioritaires, et l'étage d'assistance d'évacuation pour évacuer les occupants
du bâtiment à partir des premier, deuxième, et troisième étages d'évacuation prioritaires
vers l'étage d'assistance d'évacuation.
14. Bâtiment selon la revendication 7 dans lequel l'étage émettant un signal est un premier
étage d'évacuation prioritaire, et le bâtiment comprend en outre un deuxième étage
d'évacuation prioritaire situé un étage plus haut que l'étage émettant un signal,
un troisième étage d'évacuation prioritaire situé un étage plus bas que l'étage émettant
un signal, et un quatrième étage d'évacuation prioritaire situé deux étages plus haut
que l'étage émettant un signal, l'unité de commande étant configurée pour envoyer
le signal de commande à la commande de transport pour déplacer l'unité de transport
entre les premier, deuxième, troisième, et quatrième étages d'évacuation prioritaires,
et l'étage d'assistance d'évacuation pour évacuer les occupants du bâtiment à partir
des premier, deuxième, troisième, et quatrième étages d'évacuation prioritaires vers
l'étage d'assistance d'évacuation.
15. Bâtiment selon la revendication 14 dans lequel l'unité de commande est configurée
pour envoyer le signal de commande à la commande de transport pour évacuer les occupants
du bâtiment à partir des étages avec la priorité la plus importante avant les étages
avec une priorité moins importante, et dans lequel le premier étage d'évacuation prioritaire
est l'étage d'évacuation ayant la priorité la plus importante, le deuxième étage d'évacuation
prioritaire est l'étage d'évacuation ayant la deuxième priorité la plus importante,
le troisième étage d'évacuation prioritaire est l'étage d'évacuation ayant la troisième
priorité la plus importante, et le quatrième étage d'évacuation prioritaire est l'étage
d'évacuation ayant la quatrième priorité la plus importante.
16. Bâtiment selon la revendication 14 dans lequel le premier signal de condition comprend
des données définissant un emplacement et une priorité des premier, deuxième, troisième,
et quatrième étages d'évacuation.
17. Bâtiment selon la revendication 7 dans lequel l'unité de transport est une cabine
d'ascenseur, et la commande de transport est une commande d'ascenseur.
18. Bâtiment selon la revendication 1 dans lequel les détecteurs sont des détecteurs de
fumée.
19. Bâtiment selon la revendication 7 dans lequel le système de commande de signal est
un tableau d'alarme d'incendie auquel les détecteurs sont connectés de façon à fonctionner,
et l'unité de commande est un dispositif d'interconnexion qui communique avec les
détecteurs et la commande de transport, le dispositif d'interconnexion ayant une unité
centrale de traitement qui établit une zone d'évacuation à la détection de la condition
d'urgence qui comprend l'étage émettant un signal et au moins un étage supplémentaire
à partir duquel l'unité de transport recevra des occupants du bâtiment au cours de
la condition d'urgence pour évacuation vers l'étage d'assistance d'évacuation.
20. Bâtiment selon la revendication 7, comprenant en outre un détecteur situé dans la
cage qui détecte la condition d'urgence si celle-ci est située dans une cage à l'intérieur
de laquelle l'unité de transport est verticalement mobile, le détecteur dans la cage
étant couplé à l'unité de commande et adapté pour envoyer un signal de détection de
la cage à l'unité de commande lorsque le détecteur situé dans la cage détecte la condition
d'urgence dans la cage, l'unité de commande envoyant un signal de mise hors service
à la commande de transport pour rendre l'unité de transport hors service en réponse
à l'unité de commande recevant le signal de détection de la cage.
21. Bâtiment selon la revendication 20 dans lequel le détecteur situé dans la cage envoie
le signal de détection de la cage au système de commande de signal, et le mécanisme
de communication envoie le signal de détection de la cage au système de communication
à distance pour fournir des informations concernant la condition de la cage à l'emplacement
éloigné du bâtiment.
22. Bâtiment selon la revendication 20 dans lequel la commande de transport déplace l'unité
de transport jusqu'à une position d'arrêt, hors service en réponse à la commande de
transport recevant le signal de mise hors service.
23. Bâtiment selon la revendication 7 dans lequel le système de transport vertical comprend
une cage à l'intérieur de laquelle l'unité de transport est positionnée de façon mobile,
et un détecteur de transport monté sur l'unité de transport, le détecteur de transport
étant connecté, de manière à fonctionner, à l'unité de commande et adapté pour envoyer
un signal de détection d'urgence à l'unité de commande lorsque le détecteur de transport
détecte la condition d'urgence, l'unité de commande envoyant un signal de désactivation
à la commande de transport pour mettre hors service l'unité de transport en réponse
à l'unité de commande recevant le signal de détection d'urgence, la commande de transport
déplaçant l'unité de transport jusqu'à une position d'arrêt, hors service dans la
cage en réponse au signal de mise hors service.
24. Bâtiment selon la revendication 23 dans lequel le détecteur de transport envoie le
signal de détection d'urgence au système de commande de signal, et le mécanisme de
communication envoie le signal de détection d'urgence au système de communication
à distance pour fournir des informations de condition concernant l'unité de transport
à l'emplacement éloigné du bâtiment.
25. Bâtiment selon la revendication 7 dans lequel une pluralité des étages ont chacun
un vestibule d'étage, et chacun des vestibules d'étage a un détecteur situé dans le
vestibule d'étage, les détecteurs situés dans les vestibules d'étage étant couplés
à l'unité de commande, chaque détecteur situé dans un vestibule d'étage fournissant
un signal d'urgence à l'unité de commande lorsque le détecteur situé dans le vestibule
d'étage détecte la condition d'urgence dans le vestibule d'étage, l'unité de commande
en réponse à ceci envoyant un signal de dérivation à la commande de transport qui
empêche l'unité de transport d'être utilisée pour évacuer des occupants du bâtiment
à partir de l'étage avec le détecteur situé dans le vestibule d'étage qui a détecté
la condition d'urgence.
26. Bâtiment selon la revendication 25 dans lequel le détecteur situé dans le vestibule
d'étage fournit le signal d'urgence au système de commande de signal lorsqu'un des
détecteurs situés dans les vestibules d'étage détecte la condition d'urgence dans
le vestibule d'étage, et le mécanisme de communication envoie le signal d'urgence
au système de communication à distance.
27. Procédé d'évacuation des occupants de bâtiment à partir d'un bâtiment ayant une pluralité
d'étages, comprenant un étage de sortie du bâtiment (188), et un système d'ascenseur
(6) ayant une cabine d'ascenseur qui peut être positionnée à des emplacements adjacents
à ceux sélectionnés parmi les étages, comprenant :
le fait de détecter une condition d'urgence sur un étage émettant un signal (206)
dans le bâtiment ;
caractérisé par :
le fait de définir une zone d'évacuation (202) dans une partie du bâtiment au cours
de la condition d'urgence, la zone d'évacuation comprenant l'étage émettant un signal
et un étage d'assistance d'évacuation (214) qui est un nombre sélectionné d'étages
plus loin que l'étage émettant un signal et qui n'est pas l'étage de sortie du bâtiment,
la zone d'évacuation étant définie pour ne pas comprendre les étages considérés comme
étant des étages de non-urgence autres que l'étage d'assistance d'évacuation ;
le fait d'envoyer une pluralité de signaux de condition à un système de commande de
signal (26), les signaux de condition fournissant des données de condition des systèmes
du bâtiment, la pluralité de signaux de condition comprenant un premier signal de
condition provenant de l'étage émettant un signal au système de commande de signal
identifiant quel étage est l'étage émettant un signal ; et un second signal de condition
provenant du système d'ascenseur au système de commande de signal fournissant des
informations de condition concernant le système d'ascenseur ;
le fait d'envoyer la pluralité de signaux de condition provenant du système de commande
de signal à un système de communication à distance à un emplacement éloigné du bâtiment
pour fournir des informations de condition concernant le bâtiment ; et
le fait d'évacuer avec la cabine d'ascenseur un ou plusieurs des occupants du bâtiment
à partir de la zone d'évacuation vers l'étage d'assistance d'évacuation.
28. Procédé selon la revendication 27 dans lequel le fait d'envoyer les premier et second
signaux de condition comprend le fait d'envoyer les premier et second signaux de condition
à un service d'incendie éloigné du bâtiment.
29. Procédé selon la revendication 27 dans lequel le fait d'envoyer la pluralité de signaux
de condition comprend le fait d'envoyer les signaux de condition par l'intermédiaire
d'un modem par l'intermédiaire de lignes téléphoniques au système de communication
à distance.
30. Procédé selon la revendication 27 dans lequel le fait d'évacuer avec la cabine d'ascenseur
l'un ou plusieurs occupants du bâtiment comprend automatiquement le fait d'évacuer
les occupants du bâtiment indépendamment de l'arrivée du personnel d'assistance d'urgence
au bâtiment.
31. Procédé selon la revendication 21 dans lequel le fait d'évacuer l'un ou plusieurs
occupants du bâtiment comprend :
le fait de déplacer la cabine d'ascenseur jusqu'à l'étage émettant un signal pour
permettre à l'occupant du bâtiment d'entrer dans la cabine d'ascenseur à partir de
l'étage émettant un signal ;
le fait de déplacer la cabine d'ascenseur à partir de l'étage émettant un signal après
qu'au moins un des occupants du bâtiment de l'étage émettant un signal est entré dans
la cabine d'ascenseur, jusqu'à l'étage d'assistance d'évacuation pour permettre à
l'occupant du bâtiment de l'étage émettant un signal de sortir de la cabine d'ascenseur
au niveau de l'étage d'assistance d'évacuation ; et
le fait de limiter le mouvement de la cabine d'ascenseur pour ne pas comprendre le
mouvement de la cabine d'ascenseur jusqu'aux étages de non-urgence autres que l'étage
d'assistance d'évacuation alors que l'occupant du bâtiment est en train d'être évacué
de l'étage émettant un signal.
32. Procédé selon la revendication 27 dans lequel le fait de détecter une condition d'urgence
comprend le fait de détecter de la fumée avec un détecteur de fumée sur l'étage émettant
un signal. 27 dans lequel
33. Procédé selon la revendication 27 dans lequel le fait de définir la zone d'évacuation
comprend le fait de définir la zone d'évacuation comme comprenant l'étage émettant
un signal, un premier étage prioritaire d'évacuation situé un étage plus loin que
l'étage émettant un signal dans une première direction, un deuxième étage prioritaire
d'évacuation situé un étage plus loin que l'étage émettant un signal dans une seconde
direction, et un troisième étage prioritaire d'évacuation situé deux étages plus loin
que l'étage émettant un signal dans la première direction, et le procédé comprend
en outre le fait de déplacer la cabine d'ascenseur jusqu'à un des premier, deuxième,
et troisième étages prioritaires d'évacuation et de l'étage émettant un signal pour
permettre aux occupants du bâtiment d'entrer dans la cabine d'ascenseur à partir de
celui-ci et ensuite le fait de déplacer la cabine d'ascenseur jusqu'à l'étage d'assistance
d'évacuation.
34. Procédé selon la revendication 33, comprenant en outre le fait d'identifier une pluralité
de signaux d'appel d'ascenseur émis à partir d'au moins deux différents parmi les
premier, deuxième, et troisième étages prioritaires d'évacuation et l'étage émettant
un signal, et dans lequel le fait de déplacer la. cabine d'ascenseur jusqu'à celui
parmi les premier, deuxième, et troisième étages prioritaires d'évacuation et l'étage
émettant un signal, comprend le fait de déplacer la cabine d'ascenseur jusqu'à celui
parmi les étages identifiés à partir duquel les signaux d'appel d'ascenseur ont été
émis avec la priorité d'évacuation la plus importante en premier, considérant l'étage
émettant un signal.comme ayant la priorité d'évacuation la plus importante, le premier
étage prioritaire d'évacuation ayant la deuxième priorité d'évacuation la plus importante,
le deuxième étage prioritaire d'évacuation ayant la troisième priorité d'évacuation
la plus importante, et le troisième étage prioritaire d'évacuation ayant la quatrième
priorité d'évacuation la plus importante.
35. Procédé selon la revendication 27 destiné à être utilisé lorsque le bâtiment a une
cage et la cabine d'ascenseur est positionnée de façon mobile dans la cage, le procédé
comprenant en outre le fait de surveiller la cage pour détecter une condition d'urgence,
et au moment de la détection d'une condition d'urgence dans la cage, le fait d'envoyer
un signal d'urgence de cage au système de communication à distance indiquant la condition
d'urgence dans la cage.
36. Procédé selon la revendication 27, comprenant en outre le fait de surveiller la cabine
d'ascenseur pour détecter une condition d'urgence, et au moment de la détection d'une
condition d'urgence au niveau de la cabine d'ascenseur, le fait d'envoyer un signal
d'urgence de cabine d'ascenseur au système de communication à distance indiquant la
condition d'urgence dans la cabine d'ascenseur.