[0001] The present invention regards a programmable system for stabilising and regulating
voltage, in particular for the improved management of lighting units using fluorescent
bulbs and more generally those of the gas discharge type.
[0002] It is known that this type of bulb, to be switched on, requires a predetermined ignition
voltage and that, when it has been switched on, after a period of heating which depends,
amongst other things, upon the environment temperature, the supply voltage can be
substantially reduced, still being kept above a predetermined minimum, which is necessary
to avoid the light turn off.
[0003] It is also known that the light flow of this type of bulb is not directly proportional
to the supply voltage and to the power taken up and that the maximum lighting efficiency
is obtained in a range of supply voltages lower than the voltage needed to switch
it on.
[0004] In such a range the light flow can be regulated, by varying the supply voltage, to
adapt it to the user's requirements.
[0005] Finally, it is known that the application of excessive voltages does not give a significant
increase in the light flow and substantially reduce the useful life of the bulb.
[0006] Therefore, management systems have been designed which take care of supplying such
types of bulb with a regulated voltage, obtained from the mains, modulated to carry
out the switching on and the heating of the bulbs in optimal conditions, then reduced
and kept constant, independently from variations in the mains voltage, to obtain a
predetermined light flow (also variable in time according to suitable programs) in
conditions of optimal efficiency.
[0007] An example of this type of system is provided by document EP0753986.
[0008] Basically, in these systems the regulated supply voltage of the lighting unit is
obtained with an autotransformer with many taps, selectively connected to the output
one at a time, through switches controlled from a control and supervision station.
Even if the use of solid state switches has been proposed, for reasons of cost and
of safety the use of electromagnetic relays is generally preferred.
[0009] The choice of this type of regulation has numerous advantages with respect to alternative
solutions, like the use of variable coupling transformers or completely electronic
regulators, but at the same time brings a plurality of problems to be tackled and
solved.
[0010] First of all, the fine regulation of the output voltage requires, also by exploiting
the known expedient of the reversing device, a high number of taps and of corresponding
connection relays which it is desirable to reduce to the minimum.
[0011] Then the switching of the taps must be able to take place under load, to avoid the
bulbs turn off. Therefore, by-pass circuits are necessary controlled by further relays
to ensure the load supply during the switching transient of the taps.
[0012] Indeed, it is materially impossible to obtain a switching with electromagnetic relays
which is rapid and at the same time synchronous with the transition to zero of the
alternating current applied to the load.
[0013] The by-pass circuits must dissipate the minimum power possible and at the same time
ensure a voltage near to and preferably within the voltages which are switched, without
for this reason requiring the use of a number of by-pass relays equal to the number
of tap switching relays.
[0014] Finally, to avoid short circuits and at the same time to ensure the load supply without
gaps in voltage/current it is necessary to verify, with reliable control systems,
the open and closed state of every switching device before carrying out switching
operations which could cause a short circuit, with catastrophic effects on the apparatus.
[0015] These problems are solved by the system object of the present invention as defined
in the claims.
[0016] The characteristics and advantages of the present invention will become clearer from
the following description of a preferred embodiment, with reference to the attached
drawings wherein:
- figure 1 is a block diagram of the whole of a system for the optimised management
of a lighting unit and of equipment comprising many systems;
- figure 2 is a power module circuit diagram for the system of figure 1;
- figure 3 is a circuit diagram of the detector devices of the state of the electromagnetic
switches of the power module;
- figure 4 is an exemplifying diagram of voltage/lighting which represents a preferred
management method of the lighting in a tunnel with the equipment of figure 1;
- figure 5 is an electrical diagram of a preferred embodiment of a photoresistor based
brightness sensor and an auxiliary A/D conversion module for the system and equipment
of figure 1.
With reference to figure 1 the system essentially comprises a control unit 1, with
a microprocessor, a power module 2, with power section 2A and control section 2B,
and a visualisation and command module 3, with luminous indicators, display and keyboard.
[0017] Through a manual or remote control switch 4 and a magnetothermic protection switch
5 the alternating voltage of the mains, in the figures nominally 225 V, is applied
to the system.
[0018] In the control unit 1 an AC/DC power supply feeder 7, connected to the mains through
a transformer 6, supplies the control unit 1 and the control section 2B (through feed
wires 80) with the required stabilised continuous service voltages (±5V, +12V). The
feeding of the control section is thus subordinated to the prior feeding of the control
unit 1 which can verify the presence of the correct service voltage value applied
to section 2B before controlling its intervention.
[0019] The mains voltage, input to the power section 2A, is regulated so as to obtain in
output a predetermined voltage value which is applied to a load Z, consisting of a
bulb set, with the closing of an electromagnetic switch 18, controlled by the control
unit 1.
[0020] The control unit 1 and the control section 2B communicate through a channel 8, with
serial or parallel interface.
[0021] According to the switching commands received from the command module 3, of the room
temperature detected by a sensor 9, and possibly of the external lighting conditions
detected by a sensor 10 and transferred to the control unit through an auxiliary module
130, the control unit 1 instructs the control section 2B so that the voltage to be
applied to the load takes on an appropriate value, for switching on, heating and maintaining
such as to ensure a predetermined level of lighting, detected by a sensor 11.
[0022] For safety the different sensors and the possible auxiliary module are electrically
decoupled from the control unit, both in terms of the power supply and in terms of
the output signal, transmitted to the control unit 1 through optoelectronic devices
12,13,14.
[0023] The control section 2B, as a function of the actual mains voltage, measured through
a measuring transformer 15, and of the desired output voltage value, commands the
power section to regulate the output voltage to the desired value and it controls
it by means of a measuring transformer 16 which ensures the necessary feedback.
[0024] It also ensures, through a transformer 17, that the current and therefore the power
absorbed does not exceed predetermined values beyond which it is necessary to activate
the ventilation system and, at worst, to shut down the system. An inner overheating
protector, not illustrated, can also be foreseen.
[0025] Although it is "intelligent", section 2B operates as a slave to the commands of the
control unit 1, to which all the necessary information is transferred.
[0026] Although it is not illustrated in figure 1, it is clear that the control unit 1 can
be, and in general is, also equipped with communication interfaces (modem and/or serial
ports) to receive commands or transmit data to a remote supervision centre.
[0027] It must be noted that in regulation systems fed by a three-phase network three identical
power modules can be present, controlled by a common control unit 1 through the channel
8 (in this case a BUS)or channels dedicated to and possibly provided with many sensors,
to independently monitor the state of three distinct lighting sets.
[0028] For this, as well as the power module 2, two further modules 102, 103, identical
to module 2 and obviously fed by the other two phases of the network, respectively,
are represented in figure 1.
[0029] Other aspects of figure 1 shall be considered further on.
[0030] Figure 2 represents the structure of the power module 2A, 2B of figure 1 in greater
detail, wherein the main (even if not exclusive) innovative aspects of the present
invention are actually to be found.
[0031] The power module comprises an inlet autotransformer 19 with inlet terminals N (neutral)
and F (phase) to which the mains voltage, for example with a nominal value of 225
V, is applied.
[0032] The autotransformer is equipped with an output terminal U to supply a load with a
somewhat reduced nominal voltage equal to about 200 V which defines the average value
of the regulation range in which the output voltage can be varied.
[0033] It is also equipped with a first group of M taps referenced in order as 20,21,22
(four in the represented preferred embodiment) upon which is available a nominal voltage
referred to the neutral feeding potential equal to 0, 15, 30 and 45 V, respectively.
[0034] The autotransformer is further equipped with a second group of N taps referenced
in order as 24,25,26,27 (four in the preferred embodiment) upon which is available
a nominal voltage, referred to the neutral potential, equal to 105,165,225,285V, respectively.
[0035] It should immediately be noted that the voltage between adjacent taps of the first
group is nominally equal to 15V whereas the voltage between adjacent taps of the second
group, as well as between the tap of the second group adjacent to the tap of the first
group, is equal to M • 15V, that is 60 nominal volts.
[0036] In other words and more generally, if the taps of the first group are electrically
spaced out on the winding of the autotransformer by K turns, the taps of the second
group are electrically spaced out by M • K turns, as are the electrically adjacent
taps 24 and 23 of the first and of the second group respectively.
[0037] It is therefore clear that by selectively connecting a tap of the first group and
a tap of the second group, or else two taps of the first group, to the terminals of
a load of the first group, it is possible to feed the load with a discreet voltage
which can be varied in multiples of 15V, between a minimum of 15 nominal volts and
a maximum of 285 nominal volts.
[0038] Finally, by connecting the load terminals to the same tap, and from this point of
view it does not matter which, it is possible to apply a zero voltage to the load.
[0039] Therefore with only M+N taps it is possible to apply to the load any of M • (N+1)
distinct alternate voltages, of which one is zero.
[0040] It is clear that significant advantages with respect to the known solutions are only
provided by M and N >2 and preferably with M=N.
[0041] In figure 2 the voltages available at the M+N output taps are selectively connected
to the primary 28 of a voltage reducing auxiliary transformer 29, conveniently but
not necessarily with a turn ratio close to 1/7, by means of two groups of electromagnetic
switches 30, 31 and through a DPDT (Double Pole Double Throw) relay 32 with the function
of reversing switch.
[0042] The secondary 33 of the transformer 29 is connected in series between the output
terminal U of the autotransformer and the switch 18 for connecting to the load Z.
[0043] Therefore, it is clear that to the load Z can be applied a base voltage (200 nominal
volts present at terminal U) increased or decreased (according to the closing position
of the switch 32) by the voltage induced in the secondary 33 which varies from 0 to
285/7 V, that is about 40.7 V, in steps of about 2.1 nominal volts.
[0044] The (nominal) range of variability of the regulated feed voltage of the load thus
extends from about 159V to about 241V, which is more than sufficient to ensure an
effective and regulated output voltage of between 175 and 215V also in the case of
variations in the mains voltage of up to ± 10% of the nominal voltage.
[0045] The first group 30 of electromagnetic switches, of the SPDT type, comprises M (M=4)
relays 34,35,36,37 with the common pole connected to the sockets 20,21,22,23 respectively
of the first group and the normally open contact(that is with the relay de-energised)
collectively connected to a pair of contacts of the reversing switch 32.
[0046] The second group 31 of electromagnetic switches, of the SPDT type, comprises N+1
(N=4) relays, 38,39,40,41,42 with the common pole connected to the sockets 27,26,25,24
respectively, of the first group and to the socket 23 of the second group and with
the normally open contact collectively connected to the other pair of contacts of
the switch 32.
[0047] Obviously only one relay at a time of each of the two groups must be energised into
closing to avoid the short circuit of a part of the autotransformer and the switching
closed of any one of the relays must take place only when it is certain that the other
relays of the same group, therefore all of those in the same group, are open.
[0048] Later on we shall see how this problem is solved in an innovative manner.
[0049] Here, to conclude the description of figure 2, it should be observed that to ensure
the supply continuity of the load and at the same time to avoid short-circuiting,
it is necessary to foresee by-pass devices and circuits.
[0050] Advantageously, the number of these circuits is less than the number of relays of
each group: for the first group these consist of a single by-pass circuit, consisting
of a relay 43 with the common pole connected to an intermediate tap 22 of the first
group of tap and the contact which is normally open connected to the output node of
the first group of relays through a current-limiting resistor 44.
[0051] For the second group of relays are foreseen, on the other hand, with rounding off
in defect to the nearest integral number, (N+1)/2 by-pass circuits (thus in the figures
2 circuits) with the common pole respectively connected to taps of the second group
separated by one tap, in figure 2 the intermediate tap 26,24, and with the contact
which is normally open connected to the output node of the second group of relays
through a common current-limiting resistor 47.
[0052] The value of the limiting resistors is suitably chosen to limit both the circulating
current to acceptable values when a by-pass circuit is closed together with a relay
of the corresponding group, and the voltage drop on the resistor, when the only by-pass
circuit is closed and crossed by the feed current of the primary winding of the transformer
29 (which in the example described is a function of the load current in the ratio
1/7).
[0053] Therefore, for example, if the maximum current foreseen in the primary 28 is 4A the
resistor 47 can indicatively have a value of 20Ω and the resistor 44 a value of 10Ω.
[0054] In addition the by-pass relays 43,45,46, which collectively constitute a third group
73 of relays, a further relay 48, which is normally open, is foreseen to short circuit
the primary winding 28 of the transformer when the inverter switch is activated.
[0055] The inverter switch is activated when the voltage applied to the primary 28 is zero,
that is when the relays 37 and 42 are closed and consequently the primary is in short
circuit. In this condition the primary 28 and the secondary 33 reverse their roles:
the transformer is fed with current through the winding 33 which functions as a primary.
Since the winding 28, which functions as a secondary, is in short circuit, the drop
in voltage on the winding 33 is negligible (due only to resistance and dispersion
reactance).
[0056] If, however, the winding 28 is open, as happens during the course of the switching
of the relay 32 (unless a mechanically polarised relay is foreseen which closes before
opening and which is intrinsically slow and not very reliable) the transformer 29
behaves like an idle transformer, fed with current, that is as a reactance which introduces,
as a function of the feed current, a high and unacceptable drop in voltage, at most
limited by the saturation of the magnetic core, which significantly reduces the voltage
applied to the load.
It is, therefore, appropriate that during the course of the switching of the inversion
relay 32 the short circuit of the winding 28 be ensured.
[0057] Having described the structure of the power module one can immediately understand
its function, as it is commanded by the control section 2B which comprises a microprocessor
49 with relative memory, driving circuits of the different relays and communication
port with the control unit 1 (Fig.1).
[0058] To start up the system the control unit 1 firstly asks for a predetermined voltage
to be supplied in output.
[0059] The control section 2B, after having measured the actual mains voltage available,
determines, upon the basis of stored information, which of the relays of the first
and of the second group must be closed and the position which the switch 32 must be
in to obtain the desired voltage in output. Therefore, it commands their closing with
a possible switching of the relay 32.
[0060] All of these operations are carried out at no load, preferably but not necessarily
in sequence.
[0061] Through the closing of a pair of relays, at the output of the power section a voltage
is made available which is measured and compared to the desired one.
[0062] If the differential is less than a certain value (also programmable) it is indicated
to the control unit 1 that it can proceed to the connection of the load with the closing
of the switch 18. Otherwise it is necessary to modify the output value, in general
with just the opening of a relay of the first group and the subsequent closing of
another relay of the same group.
[0063] For this adjustment, even if it is carried out at no load, a rigorous ordering must
be respected between the opening of the first switch and the closing of the second.
In other words the control section 2B must verify, by means of circuits discussed
later on, that the first switch is actually open before putting the second relay into
closed state.
[0064] The same condition must be verified also in the case where it is necessary to open
(even simultaneously) both a switch of the first group and of the second. The closing
of the switches which replace the first in closed state must take place subsequently.
This is necessary to avoid the short-circuiting of portions of the autotransformer's
windings.
[0065] More complex is the procedure to be followed to modify the output voltage under load,
that is when the switch 18 is closed, both to keep the output voltage constant as
the mains voltage varies, as well as to obtain in output a voltage which can vary
according to a predetermined time profile established by the control unit 1 (ignition
ramp, heating voltage, voltage reduction ramp, maintenance voltage).
[0066] In this case, before opening a relay, either of the first or of the second group,
it is necessary to close a by-pass circuit, to make sure that the by-pass circuit
is closed and, only after having carried out this check, to open the relay. After
having checked that the relay to be opened is actually open one can proceed to the
closing of the relay which must replace in closed position the one just opened. Finally,
the by-pass circuit can only be opened after having checked that the relay already
moved closed is actually closed.
[0067] The same procedure must be repeated, in sequence and after the first, in the case
that to regulate the voltage to the desired value it is necessary to switch a relay
both of the first and of the second group.
[0068] The procedure to be followed for the activation of the reversing switch 32 is entirely
analogous.
[0069] Firstly, it is necessary to move closed the two relays 42,37, if they were not already
closed, respecting the procedure already seen and to check that they are closed.
[0070] In this condition the voltage set for the primary 28 is zero. It is necessary to
then move closed the short circuit relay 48 and preferably, even if not necessarily,
check the state thereof.
[0071] Indeed, since the short circuit relay switches to a zero voltage between the contacts,
there is no risk of electric arcs which could damage the contacts and cause, by welding,
the jamming of the relay.
[0072] With the short circuit relay closed it is then possible to actuate the inverter switch
32 and finally to reopen the short circuit relay.
[0073] Also this opening switching takes place with zero voltage between the contacts and
the current is switched onto the parallel short circuit path formed by the relays
37,42, which are closed, therefore without the development of an electric arc.
[0074] In this condition, with the procedures already seen it is then possible to establish
a non -zero voltage in the primary 28 with the opening of one or other of the switches
37,42 or of both, and the closing of corresponding switches of the first and/or second
group, taking care to activate the necessary by-pass circuits.
[0075] It is therefore clear, keeping in mind that the switching time of an electromagnetic
relay is in the order of 10 ms, that switching procedures where a load is present
require a non-negligible time, no less than 40 ms and than 80 ms when the switching
of two relays of the first and of the second group is necessary.
[0076] In the absence of a check on the state of the relay, this time, for safety and to
take account of the inevitable dispersions of the switching times, must necessarily
be increased, separating the different operations in time, increasing the intervention
times of the by-pass circuits and consequently the amount of energy dissipated and
the duration of the voltage transients, reducing the regulation speed.
[0077] It is, therefore, desirable to have control circuits which allow the execution time
of the procedures to be reduced to the minimum and which rapidly provide information
that the different switching operations commanded have actually taken place.
[0078] This is even more important since, whereas the contacts of the inverter switch and
of the short circuit relay open and close without the development of electrical arcs,
the contacts of the other relays switch under a load, which is inductive what's more,
with a non-zero voltage between the open contacts and consequently with the development
of electrical arcs which can cause the welding and the jamming of the contacts which
no longer obey the electromagnetic command of the relay.
[0079] From this point of view, more than desirable, it is mandatory to foresee control
systems which provide the direct information of the contact switching having taken
place, not mediated by the behaviour of auxiliary contacts, the behaviour of which
does not necessarily reflect that of the contacts which must be monitored.
[0080] In this manner it is possible to avoid that a relay failure has catastrophic effects,
timely blocking the further development of the switching procedures upon the first
detection of the failure, carrying out attempts at repeating the command and, after
a suitable number of attempts, for example three, having checked that the defect is
permanent, definitively blocking the operation and indicating the failure.
[0081] Figure 3 shows a preferred embodiment of the circuits for checking the open/closed
state of the switch contacts.
[0082] Firstly, let us consider the second group 31 of electromagnetic switches, comprising
switches 38,39,40,41,42, with the common pole connected to the autotransformer tap
at which there is the nominal voltage of 285,225,165,105 and 45V respectively.
[0083] The contacts which are normally closed or inactive of the two switches 38,39 are
connected to the inputs of a detector circuit 50 which provides in output a logic
signal 1 asserted (for example a voltage of about 5V) when both of the switches are
in rest position and a logic signal 0 when even only one of the switches 38,39 is
switched with the common pole closing on the active pole.
[0084] The structure of the detector circuit is very simple and comprises a rectifying bridge
51 connected to the inactive poles, which are normally closed, of relays 38,39, through
a resistor 52 of a suitable value. The bridge feeds, in voltage rectified and filtered
by a capacitor 72, through a second resistor 53, the light emitting diode of an optoelectronic
coupler 54 whose phototransistor, connected between a suitable voltage (+5V) and ground,
with a suitable resistance 55 in series with the emitter, imposes at the output, connected
to the node between emitter and resistor 55, a logic signal 1 when the detector circuit
is fed (that is, the switches 38,39 are both switched to open the active pole and
to close the inactive pole) and a logic signal 0 when even only one of the switches
is switched to close onto the active pole and therefore the detector circuit is not
powered.
[0085] The value of the resistor 53 and of the capacitor 72 is chosen so that the time constant
RC of the circuit has a predetermined value, in the order of 5ms.
[0086] The value of the resistor 52, in relation to that of the resistor 53 is chosen according
to the feed voltage (in our case 60 nominal volts being the effective value) so that
the light emitting diode is energised with a suitable current, for example 10mA.
[0087] Identical to that described is the structure of the detector circuit 56, with two
inputs respectively connected to the inactive pole of the switches 40,41. The detector
56 recognises the open state (level 1 as output) of both of the switches or the closed
state (level 0 as output) of even only one of the switches.
[0088] Substantially identical is also the structure of the detector circuit 57, with the
only difference in the (lower) value of the resistor 52 within the circuit, to take
account of the fact that the circuit has inputs connected respectively to the inactive
pole of the switch 42 and to the tap with a nominal voltage of 30V so as to be fed
(when the switch 42 is open) with a voltage of 15V.
[0089] This circuit reveals the open or closed state of the only switch 42.
[0090] The outputs of the detector circuits 50,56,57 are connected to the inputs of a NAND
gate 58 which outputs a logic signal 0 when all of the switches of the first group
31 are open and a logic signal 1 when one of the group switches is closed.
Since only one of the group switches can and must be closed at once (otherwise a short
circuit forms) the information in output from the gate 58 and applied in input to
the microprocessor 49 (Fig.2) is adequate to check the open/closed state of the switches
and to verify if a switch (activated one at a time) has correctly responded to the
closing and opening commands.
[0091] Incidentally, it is suitable to note that to achieve maximum safety, the commands
to close the switches of the same group are obtained by decoding a binary code, so
as to rule out any possibility of commanding more than one switch of the same group
to close simultaneously, due to an error or to a failure developed upstream of the
decoder.
[0092] The information received from the microprocessor is not just adequate but is also
rapid.
[0093] Indeed, when a switch is closed, the feeding of the detector circuit, which corresponds
to the input signal, switches as soon as the inactive contact opens and before the
closing onto the active pole takes place. The time constant of the detector circuit
replaces the flight and bounce time of the mobile armature and ensures that the closing
signal is received when the switching is definitely taking place and is about to be
completed, without significant delays. In the same way, when the switch is opened,
the detector circuit is supplied with current as soon as the common pole closes on
the inactive contact and the switching has definitely taken place.
[0094] Therefore, it is not at all necessary to take account of the response time of the
relay and of the possible dispersions thereof.
[0095] Totally identical to the structure of the detector circuit 57 is the structure of
the detector circuits 59,60 with inputs connected to the inactive poles of the relays
37,36 and 35,34 respectively and outputs connected to the inputs of a NAND gate 61.
[0096] The NAND gate 61, like the gate 58, has in output a logic signal 0 when all of the
relays of the group 30 are de-energised, thus open, and a logic signal 1 when one
of the relays responds correctly to an energise command, closing itself.
[0097] Totally similar to the previous ones is the structure of the detector circuits 62,
63 which respectively monitor the state of the by-pass relays 45,46 and the state
of the by-pass relay 43.
[0098] In particular circuit 63 is identical to circuit 57 already described, receiving
in input a voltage of 15V, and circuit 62, receiving in input a voltage of 120V, differs
from circuit 50 only for the fact that it has a higher value of the internal resistance
52.
[0099] The outputs of circuits 62,63, arranged in logic NAND from gate 64, provide a logic
signal 0 when all of the by-pass circuits are open and a logic signal 1 when one of
the by-pass circuits is closed.
[0100] Although it is not indispensable, it is also possible to foresee a circuit 65 to
detect the open or closed state of the short circuit switch 48.
[0101] The structure of the detector circuit 65, a diagram of which is shown in the figures,
is similar to that of circuit 50 and differs from the latter only because the former
foresees, as well as the inversion of the output signal (obtained with the grounding
of the phototransistor emitter and the connection of the output to the collector),
a Zener diode 66 in parallel with the capacitor 52. The Zener diode limits the current
injected into the light emitting diode.
[0102] Indeed, in this case the voltage applied in input, according to the different working
conditions of the regulation system, can vary from 0 to 165V (a voltage of 165V is
applied to one input and a variable voltage from 0 to 285V is applied to the other).
[0103] It should immediately be noted that the response of circuit 65 is ambiguous: the
outlet signal depends not just upon the open or closed state of switch 48 but also
on the input voltage which can be 0 or so low (15÷45V) as not to lead to the energising
of the optoelectronic device.
[0104] The ambiguity can be solved remembering that the short circuit relay can and must
be moved closed only when switches 42 and 37 are both closed and the voltage of 45V
referring to the neutral is applied to both of the poles of the inverter switch 32.
[0105] In this condition the circuit receives in input a voltage of 120V, which is more
than adequate.
[0106] This condition can be taken account of directly by the microprocessor 49 (which knows
when switches 42 and 37 are closed because it is the microprocessor itself which commands
its closing) and in this case the output of circuit 64 can be connected to an input
gate of the microprocessor.
[0107] Yet more advantageously, as represented in figure 3, it is possible to connect the
output of circuit 65 to an input of NAND gate 64, with the intermediary of a NAND
gate 67 with a masking function.
[0108] Two signals CL42 and CL37 (available in output from the microprocessor 49) which
close the two switches 42 and 47 are applied to two inputs of NAND gate 67.
[0109] The state 1 present at the output of circuit 65 is transferred (with inversion) to
the input of NAND 64, only if CL42 and CL37 are at 1. Otherwise NAND gate 67 applies
the logic signal 1 in input to gate 64 and masks the ambiguous states of the detector
circuit 65.
[0110] It must also be noted that the closing of the short circuit relay does not take place
at the same time as the intervention of the by-pass relays, for which reason the information
in output from the NAND gate 64 can be interpreted without any ambiguity and referring
to the particular relay which is activated from time to time.
[0111] In conclusion, with the described detector circuits it is possible to recognise the
switching of all of the switches of the power section, detecting it directly on the
contacts, in a reliable and rapid manner, without delays to ensure a safety margin
for dispersions in behaviour.
[0112] Only the behaviour of the reversing switch 32 cannot be monitored with detector circuits
of the type described because at the intervention step all of the contacts have the
same potential.
[0113] This does not constitute a problem because the lack of switching does not carry the
risk of catastrophic failures and ends up with the impossibility of obtaining the
desired variation of the output voltage.
[0114] It is therefore possible to detect the non-operation of the switch, straight afterwards,
by simply verifying if the variation in voltage which comes about from an immediately
subsequent procedure of switching the group relays is in the desired direction or
else the opposite direction.
[0115] In the previous description the optimised management system was essentially considered
as a voltage regulation system.
[0116] From this point of view the system described, thanks to the fineness of regulation
which is allowed (furthermore capable of being incremented even only slightly increasing
the number of taps of the autotransformer and the corresponding number of relays)
and thanks to the speed of response, can be conveniently used as a voltage stabiliser
for the feeding of whatever type of load, as well as a programmable voltage regulator
for feeding whatever type of load, the voltage of which must be regulated and possibly
modified for whatever reason (for example for "margining" operations in a laboratory
or to regulate the speed of motors fed in alternating current, replacing TRIAC partialising
devices which do not allow the mains voltage to be increased and in particular have
the serious drawback of introducing high width harmonics in the developed waveform.
[0117] However, it is clear, as has been highlighted, that the described system can also
operate as a brightness regulator, keeping in mind that the light emission is to a
great extent dependent upon the feed voltage of the bulbs and the brightness of an
environment also depends upon the possible variable light contribution coming from
the outside. Therefore, a direct relationship between feed voltage and brightness
of the room does not exist.
[0118] For this purpose it is sufficient to foresee a brightness sensor 11 (Fig.1) and to
slave the operation of the system to the signal emitted by the sensor, conveniently
converted into digital form and compared with a desired brightness value.
[0119] The brightness sensor can also carry out a twilight function and the system can be
programmed, obviously with suitable hysterisis, to switch on a light bulb when the
brightness falls below a certain level, to keep the lighting at a desired level, in
case variable according to time bands, and to switch off the light bulb if the brightness
goes above another predetermined level.
[0120] A specific application of this type consists of the regulation of lighting in tunnels.
[0121] It is known that current lighting units for tunnels can consist of a line which is
always switched on, known as "permanent" lighting, of a second low consumption line
which is always switched on even in the case of a power cut since it is fed from UPS
(Uninterrupted Power Supply), known as tracing, and of a certain number of intensifying
circuits (generally from 1 to 3, according to the length of the tunnel) which switch
on or off in relation to the brightness outside, to reduce glaring effects when leaving
the tunnel and to allow the gradual adaptation to the lighting inside upon entering.
[0122] This solution offers only four brightness values and cannot adapt to all the intermediate
conditions.
[0123] The system which has been described, appropriately replicated to constitute a piece
of equipment, also effectively solves this problem and allows the brightness to be
regulated gradually, with a high resolution, by controlling the selective intervention
of the intensifying circuits according to the brightness outside.
[0124] To better understand this aspect it is suitable to refer to figure 1.
[0125] In figure 1, as well as the base system which has been described, hereafter known
as unit A, two other units B and C, identical to the previous one, are present.
[0126] For simple reasons of constructive modularity and of programming, units B and C are
each equipped, like unit A, with a central unit, such as 1, with at least one power
module, such as 2, and with a keyboard, such as 3, so as to be able to be programmed
individually in a coordinated manner.
[0127] However, it is obvious that a single keyboard, with a bus connection, represented
by the dashed line 104 can be used to program the operation of the three units.
[0128] The element common to the three units which completes the equipment consists of an
auxiliary module 130 and of a brightness sensor 10 which, through the auxiliary module
130, sends a binary code, representing the level of brightness outside, to the three
units on respective optoinsulated serial ports.
[0129] It should be noted that, in place of the bus 104 and of a keyboard dedicated to each
unit A, B and C the auxiliary module 130 could allow the exchange of information between
the different units A, B, C and the programming thereof with a single keyboard.
[0130] Unit A can be programmed to manage the permanent line, unit B to manage the intensifying
line or lines and unit C to manage the tracing line, all according to the brightness
outside, measured with a single sensor 10.
[0131] Figure 4 represents in a voltage V/external brightness level L qualitative diagram,
a preferred form of regulation of the voltage for the different lighting lines.
[0132] For external brightness values less than L1 units A and C supply to the permanent
line (P) and to the tracing line (T) a feed voltage which increases with the external
brightness. The voltage can be different for the two lines but, for clearness of representation
it is represented as equal.
[0133] When the external brightness is greater than L1 unit B activates the feed of a first
intensifying line RNF1, whereas the feed of the permanent line and of the tracing
remain unchanged, as represented in the figures. If so desired, for very long tunnels
or for particular requirements the feed voltage of the permanent and tracing lines
could also be reduced and subsequently incremented.
[0134] It is clear that initially the voltage necessary for switching on and heating is
applied to the intensifying line, said voltage then being reduced to a suitable value.
[0135] As the brightness outside increases, the feed voltage of the intensifying line is
increased from L1 and L2.
[0136] When the external brightness is greater than L2, with the same criterion, the second
intensifying line RNF2 is activated and the feed voltage of the other intensifying
line is reduced.
[0137] Finally, if the external brightness is greater than L3, the third intensifying line
RNF3, if present, is activated with the same criteria.
[0138] The same criteria is followed, with a suitable hysterisis, to reduce and remove the
feed to the intensifying lines, in the case of reduction of external brightness.
[0139] Basically, at the entrance and at the exit of the tunnel a lighting LTOT which can
be varied gradually, without substantial discontinuities, with the level of brightness
outside L, is obtained.
[0140] To achieve a precise regulation of brightness, according to one aspect of the present
invention and unlike prior art systems which use photovoltaic cells and expensive
equipment, the system object of the present invention uses a photoresistor, which
is more cost-effective, more reliable and, being appropriately driven, allows greater
precision of measurement and of regulation in all possible ranges of brightness.
[0141] Figure 5 schematically represents the brightness measuring apparatus adopted.
[0142] A photoresistor 10, remote from the regulation system, is connected to the auxiliary
module 130 with a screened cable 78 which protects it to a large extent from disturbances
and atmospheric discharges.
[0143] The photoresistor 10, in parallel with a resistor 70 and in series with a resistor
71 which functions as a voltage divider, is fed by a continuous regulated and constant
voltage of -5V.
[0144] The node which is common to the photoresistor and to the resistor 71 is connected
to the inverting input of an operational amplifier 74, with suitable feedback provided
by a trimming resistor 75, to ensure a predetermined gain.
[0145] Two diodes 72,73 connected between the inverting input and voltages of +5V and -5V
respectively, ensure the protection of the amplifier against overvoltages taken on
through the input cable 78.
[0146] Not-shown capacitors, in a known way, filter the transient noise and cutting the
frequency response of the amplifier.
[0147] The output of the amplifier 74 is connected to an analogic input port of an integrated
circuit for the acquisition and A/D conversion of signals which circuit outputs, on
three serial ports, and sends to units A,B,C a binary code representing the input
signal, in turn representing the resistance of the photoresistor 10 and, fundamentally,
the measured level of brightness outside.
[0148] Through serial input ports, not illustrated, the circuit can be programmed, to assign
and characterise the ports with which it is equipped as analogue or digital input
ports.
[0149] Other aspects of the integrated circuit are not essential.
[0150] The auxiliary module 130 is fed by an AC/DC power supply 79, connected to the output
of the transformer 6 (Fig.1) and buffered by a battery 77 which ensures the powering
of the module even when there is a main shut down. The power supply 79 supplies the
necessary continuous feed voltages to the module.
[0151] In this way all of the functions necessary for acquiring the brightness value, which
is indispensable for the control of the lighting of tunnels and more generally of
units dependent upon conditions of brightness outside are gathered in an auxiliary
module and do not burden the cost of the base system which in many cases must only
operate as a programmable voltage stabiliser or regulator.
[0152] In relation to the use of the described system for the optimised management of a
lighting unit of the gas discharge type it is interesting to note a special function,
capable of being achieved with the system, consisting of testing the unit to identify
bulbs which are defective and/or nearly run out.
[0153] It is known that when a gas discharge bulb has nearly reached the end of its useful
life, it finds it difficult to keep its switched on state and is particularly sensitive
to rapid reductions in the feed voltage up to a minimum necessary value, to remain
switched on.
[0154] The described system, indeed, allows these rapid variations in voltage to be obtained
through a command made manually from keyboard 3 (fig.1).
[0155] Indeed, it is possible to command a switching on and warming up sequence, and with
this having been carried out a rapid reduction in the maintenance voltage can be commanded,
in quick succession switching the relays of the second group (31, Fig. 2) so as to
impose relatively wide variations in voltage, in the described example in the order
of 8.4V without passing through the selective activation of the relays of the first
group.
[0156] This operation can be carried out in a very brief space of time, in the order of
100 ms, and it can be followed, in an equivalent time, by the restoration of the normal
switching on conditions.
[0157] As a result of this rapid voltage variation, which substantially consists of a margining
operation during the course of the exercise, the bulbs which are defective and/or
nearly run out remain switched off.
[0158] This allows the programmed replacement, following the testing operation or even at
an appropriate subsequent time, of all of the bulbs which are defective and/or have
nearly run out.
[0159] In this way the number of necessary maintenance operations is reduced, to the great
advantage of the operative state of the equipment in the cases in which it is intended
to operate in continuous duty.
[0160] The previous description refers to a preferred embodiment of a system for the optimised
management of lighting units and it is clear that many variants, in addition to those
already indicated, can be made.
[0161] For example, the different switching relays can all be individually equipped with
a switch detecting circuit, as is the case for relays 57 and 63 of figure 3, with
outputs of the detector circuits arranged by groups in logic NAND or else connected
directly to corresponding ports of the microprocessor, or even connected to a reduced
number of ports and at the extreme to only one, through a multiplexer.
1. Programmable voltage stabiliser and regulator system, in particular for the optimised
management of a load (Z), consisting of bulbs of the gas discharge type, comprising
a control unit (1), sensors of the mains voltage (15) and of the regulated output
voltage (16), and a power module (2A,2B) with autotransformer with a plurality of
taps (20,21,...27), selectively connected to the inputs of the primary winding (28)
of an auxiliary transformer (29), having the secondary (33) in series with the load
(Z), through a plurality of electromagnetic relays and with the interposition of an
inverter switch (32), characterised in that:
said autotransformer is equipped with a first group of M ordered taps (20,21,22,23),
where M>2, spaced apart by K turns, and with a second group of N ordered taps (24,25,26,27),
where N>2, spaced apart by K • M turns, the tap (23) of the first group and that (24)
of the second group which are electrically closest to each other being spaced apart
by K • M turns,
and in that said plurality of electromagnetic relays comprises a first group (30) of M relays,
with a common output node, for the selective connection, one at a time, of the taps
of said first group to a terminal of said primary winding (28) of said auxiliary transformer,
and a second group (31) of N+1 relays, with a common output node, for the selective
connection to the other terminal of said primary (28), one at a time, of the taps
of said second group and of the tap of the first group which is electrically closest
to those of the second group.
2. System according to claim 1 wherein M=4 and N=4.
3. System according to claim 1 or 2 comprising only one first resistive by-pass route
(43,44) of said first group of relays (30), controlled by a first electromagnetic
by-pass relay (43), to connect an intermediate tap of the first group of taps to the
common output node of the relays of said first group (30), and at least one second
resistive by-pass route (45,46,47) of said second group of relays (31), controlled
by a second electromagnetic by-pass relay (45,46), to connect at least one intermediate
tap of the second group to the common output node of the relays of said second group
of relays (31).
4. System according to claim 3 comprising:
- a first group of circuit means (59,60) connected to the normally open inactive pole
of each of the relays of said first group (30) to detect the open/closed state of
said relays and to produce in output corresponding signals,
- a second group of circuit means (50,56,57) connected to the normally open inactive
pole of each of the relays of said second group (31) to detect the open/closed state
of said relays and to produce in output a corresponding signal, and
- a third group of circuit means (62,63) connected to the normally open inactive pole
of each of the by-pass relays of said third group (73) to detect the open/closed state
of said by-pass relays and to produce in output a corresponding signal.
5. System according to claim 4 wherein said circuit means comprises an optoelectronic
device for electrically insulating the output from the input connections.
6. System according to claim 4 or 5 comprising a first (58), second (61) and third (64)
logic gate which receive in input the output signals of said first, second and third
group of circuit means, respectively, and produce in output, for each group of relays
respectively, a signal representing the open state of all of the relays of the group,
or the closed state of at least one of the relays of the group.
7. System according to claim 4,5 or 6 comprising a short circuit relay (48) of said primary
(28) of the auxiliary transformer, and circuit means (65) connected to the normally
open inactive pole of said short circuit relay to detect the open/closed state of
said relay and to produce in output a corresponding signal.
8. System according to claim 4,5,6 or 7 comprising logic control means (49) receiving
in input said signals representing the open/closed state of said relays of the first,
second and third group, to subordinate, for each group, the closing of one of the
relays to the prior detection of the open state of all of the relays of the group,
to subordinate the opening of one of the relays of the first or second group to the
prior detection of the effective closing of a corresponding by-pass relay, and to
subordinate the opening of said corresponding by-pass relay to the detection of the
effective closing of a relay of the first or second group.
9. System according to any one of the previous claims comprising a photoresistor (10)
and an auxiliary module to convert the variations in resistance of said photoresistor
into a binary code sent to said control unit (1).
10. Equipment for the regulation of the lighting in tunnels comprising at least one system
according to any one of claims from 1 to 8 and a system according to claim 9.
11. Method for testing a bulb unit managed by a system or equipment according to any one
of the previous claims, consisting of performing a rapid reduction in the feed voltage
with the selective closing of only the relays of said second group (31).