[0001] The present invention refers to a compact apparatus for picking up current in a medium-voltage
line suitable for being connected to a protection relay, which drives a medium-voltage
automatic switch.
[0002] Medium-voltage switches for indoors are currently known which use air or gas (usually
sulphur hexafluoride, SF
6) to extinguish the electric arc and as insulating means between fixed and mobile
main contacts.
[0003] Medium-voltage automatic tri-polar switches, with a nominal voltage of up to 24 kV,
are used in all applications of the secondary distribution of medium voltage and in
medium-voltage/low-voltage transformation substations in buildings, offices in the
industrial sector in general and in tertiary industry.
[0004] In particular, sulphur hexafluoride (SF
6) switches are particularly suitable for service in primary and secondary distribution
stations, where there is the need to carry out fast shut down cycles in overhead and
cable distribution lines, for manoeuvring industrial power factor correction units
with heavy-duty operation and limited maintenance, for the command of motors and,
in general, for high reliability and long lifetime applications.
[0005] The interruption of the arc is normally realised through self-pneumatic blow out
of SF
6 gas combined with the contribution of self-generation and, therefore, with limited
absorption of mechanical energy.
[0006] The system operates normally sealed under pressure and is suitable for repeated fast
shut downs, operating with limited overvoltages also in the manoeuvre of small inductive
and capacity voltages.
[0007] The poles, placed in cylinders of casting resins with gas sealing systems, and the
support and command structures of the tri-polar switch can realise fixed or removable
front and/or side operations.
[0008] Moreover, the aforementioned automatic switches are equipped with current sensors
and/or circuit-breakers or electronic maximum current relays, powered by themselves,
which allow use in unmanned mediumvoltage/low-voltage transformation substations without
auxiliary power supply.
[0009] Currently, electronic relays for protecting the maximum current power themselves
with current reducers (transformer, 1, 2, 3, 4), which are applied on board the switch,
so as to guarantee the maximum homopolar and directional safety protection and protection
from overcurrents in relation to all types of data which can be detected inherent
to the protection problems.
[0010] The two or three transformers applied to the switch supply the energy necessary for
the operation of the relay and for the switching off of the switch through a demagnetisation
actuator group applied to the command, which allows overloads (at long reverse time
and at adjustable fixed time) and short-circuits (at adjustable independent time)
to be detected.
[0011] Alternatively, the maximum power circuit-breakers can be realised with a microprocessor
and are suitable for taking care of the function of protection against overload and
against instantaneous and delayed short-circuit, as well as the function of protection
against grounding failure.
[0012] In general, however, the different forms of protection devices for automatic tri-polar
switches have some drawbacks.
[0013] First of all, in the case in which electronic protection relays are used, it is necessary
to wind a series of toroids on board the switch, with the inevitable consequences
due to problems of electromagnetic interference, which translate into the need to
foresee a specific insulation between each toroid and the respective pole, adding
to the encumbrance, connection time, connection procedures and causing the substantial
lack of practicality and reliability of the entire structure. Then, in the case of
use of microprocessor circuit-breakers, in which the problem of electromagnetic interference
is partially solved, one of the drawbacks encountered most is that of the substantial
production, installation and operating costs.
[0014] The purpose of the present invention is therefore that of avoiding the aforementioned
drawbacks and, in particular, that of realising a compact measurement apparatus for
the protection of medium-voltage lines with medium-voltage automatic switches, which
allows extreme reliability in general to be obtained, capable of being used without
substantial interventions or complex treatments on board the switchboard, at the same
time keeping the possibility of effectively measuring the data relative to the problems
of protection of the electrical lines.
[0015] Another purpose of the present invention is that of realising a compact measurement
apparatus for the protection of medium-voltage lines, which allows the carrying out
of a measurement of the functions or malfunctions of the current circulating in the
medium-voltage lines, of a reading and detection of the grounding currents, of a pinpointing
of short-circuits and of possible unbalances between the phases, without using particularly
expensive components and without foreseeing particular or extremely specific insulation
devices.
[0016] A further purpose of the present invention is that of indicating a compact measurement
apparatus for the protection of medium-voltage lines which is highly precise, stable,
effective and safe.
[0017] The last but not least purpose of the invention is that of realising a compact measurement
apparatus for the protection of medium-voltage lines at a low cost and without using
complex or expensive technologies.
[0018] Such purposes are achieved by a compact measurement apparatus for the protection
of medium-voltage lines, according to claim 1, to which we refer for the sake of brevity.
[0019] Advantageously, the protection apparatus according to the invention includes within
a single epoxy resin block, once enclosed in a container made from thermoplastic material,
a combined series of toroidal windings, having a sufficiently long core to obtain
good electrical performance, and a further winding, suitable for collecting the phase
current, separated from the other windings by the resin insulation.
[0020] The apparatus allows a series of samples of electric current to be taken, in order
to obtain both homopolar and directional protection, thus allowing the function of
protection against overload, against instantaneous and delayed short-circuit and against
grounding failure to be taken care of.
[0021] The detection of the line and grounding currents, both in nominal conditions and
in the presence of disturbances, can be carried out by means of a protection relay,
combined with the apparatus object of the present invention which, thanks to suitable
procedures controlled by an internal microprocessor, allows adequate active current
protection, defined by the prevailing national and international electrotechnical
regulations, to be realised.
[0022] Further purposes and advantages of the present invention shall become clearer from
the following description and from the attached drawings, provided as an example and
not for limiting purposes, in which:
- figure 1 is a schematic front view of a measurement apparatus for the protection of
medium-voltage lines, connected to a medium-voltage automatic tri-polar switch and
realised according to traditional techniques;
- figure 2 is a first perspective view of a compact measurement apparatus for the protection
of medium-voltage lines, realised according to the present invention;
- figure 3 is a second perspective view of a compact measurement apparatus for the protection
of medium-voltage lines, realised according to the present invention;
- figure 4 represents a schematic perspective view of an example of application of the
compact measurement apparatus for the protection of medium-voltage lines, according
to the invention.
[0023] With particular reference to the quoted figure 1, a conventional embodiment of a
medium-voltage automatic tri-polar switch is generically indicated with 10, in which
each apparatus for the protection of medium-voltage lines (in particular, a transformer),
which is generically indicated with 15, is applied directly to each pole 13 of the
switch 10.
[0024] The switch 10 comprises a switchboard 11 fixed to a support base 12 for the poles
13, each of which essentially consists of an insulating cylinder 17, made from casting
resin with gas sealing systems, whereas the protection apparatus 15 in general takes
care of the function of protection against current overload, instantaneous and delayed
short-circuit and grounding failure.
[0025] Figures 2, 3 and 4, respectively, refer to an embodiment of the compact measurement
apparatus for the protection of medium-voltage lines, according to the present invention
(generically indicated with 16 in the figures), and to an example of application of
such an apparatus 16 in a compartment with a bar switch and disconnecting switch.
[0026] In particular, the apparatus 16, object of the invention, foresees the use of three
toroidal transformers 40, 44, 47, one for each phase, which are installed above an
attachment support 46 and inside an insulating casing 20, as illustrated in detail
in figures 2 and 3.
[0027] The toroidal transformers 40, 44, 47 are combined together and have a core with a
substantially largediameter. Moreover, according to the invention, it is foreseen
to couple a homopolar transformer, schematically indicated with 39, for the collection
of the three phases.
[0028] The homopolar transformer 39 is separated from the other three toroidal transformers
40, 44, 47 by means of a resin insulation and allows the grounding failure current
to be detected through the execution of a vector sum of the phase currents.
[0029] Referring, in particular, to figure 4, the compact protection apparatus 16 can be
applied with undoubted advantages in a compartment 21 inside of which is housed a
bar switch and disconnecting switch, of the tripolar type, according to a preferred
but not limiting embodiment of the present invention, generically indicated with 22
in figure 4.
[0030] In such a case, the cables 23 of the medium-voltage line, which are arranged inside
an underground passage 24, arrive near to the compartment 21 and pass inside the toroidal
transformers 40, 44, 47 of the apparatus 16, which is fixed, inside the compartment
21, to the front of the switch 22.
[0031] One of the medium-voltage cables, specifically indicated with 28 in figure 4, is
used as a cable intended for general use and for input for the general power supply
of the switchboard 27 attached to the compartment 21 of the bar switch and disconnecting
switch 22.
[0032] As can be seen in figure 4, each cable 23, after having crossed the respective toroid,
is connected directly to the switch 22, through a specific lower connector 25, whereas
a series of signals in output from the toroidal transformers 40, 44, 47 (proportional
to the current circulating in the phases) are conducted directly to a protection relay
26 for the switchboard 27. In particular, the three connectors 36, 37, 38, through
the respective outputs 41, 42, 43 of the apparatus 16, send the respective phase signals
of the toroidal transformers 40, 44, 47 to the protection relay 26 in order to detect
the current of the separate phases.
[0033] Moreover, the connector 45, by means of the output 44A, sends a homopolar output
signal, taken directly from the homopolar transformer 39, to the protection relay
26 so as to allow the detection of grounding failures.
[0034] The self-powered relay 26, realised in microprocessor digital technology, is placed
to protect the maximum current values (biphase or triphase) and operates the opening
or switching off of the switch 22 directly on the relative command, in the case of
intervention of the protection functions.
[0035] Thanks to the installation of the protection apparatus 16, the correct operation
of the entire switching off unit of the switch 22 is guaranteed in the presence of
a current greater than or equal to 20% of the nominal value on at least one of the
phases.
[0036] Finally, as can be seen clearly in figures 2 and 3, to maximise the compactness of
the structure, the protection apparatus 16 is contained entirely inside a single container
casing 20 made from thermoplastic material, which rests upon the attachment surface
46, whereas, inside the casing 20, an epoxy resin suitable for the necessary insulation
is used.
[0037] In such a way, as well as the possibility of substantially reducing the encumbrance,
with respect to known protection devices (regarding which we emphasise the possibility
of inserting the entire apparatus 16 object of the invention inside the compartments
21 of bar switches and disconnecting switches, as illustrated in figure 4), there
is also greater precision and stability of detected current values and, therefore,
a safer intervention, mainly due to the fact that, in such a way, the protection apparatus
is no longer installed, like in the prior art, on board the switch.
[0038] In fact this particular arrangement of the apparatus inside compartments allows the
problems of interference determined by the electromagnetic flows between toroid and
pole to be eliminated, maintaining high electrical characteristics, differentiated
uses (for variable current intensities between 40 and 630 A), a compact structure
and a substantially low overall production and operating cost, with respect to the
prior art.
[0039] Furthermore, the apparatus according to the invention is suitable for detecting current
signals to realise overload protection at long reverse time and at adjustable fixed
time, short-circuit protection at adjustable independent time and, in general, all
maximum phase current protection (instantaneous, with adjustable delay as well as
with dependent and fixed time), as well as, possibly, maximum grounding failure current
protection (with adjustable delay), calculated as a vector sum of the three primary
phase currents and realised by means of the homopolar toroid 39, which processes the
phase currents.
[0040] From the description which has been made the characteristics of the compact measurement
apparatus for the protection of medium-voltage lines, object of the present invention,
are clear, just as the advantages are also clear.
[0041] In particular, they are represented by:
- precision of interventions;
- wide adjustment ranges;
- ensured operation even with monophase power supply;
- no limitation of the nominal interruption power of the current for a short duration
of the switch;
- single and simultaneous adjustment of the three phases;
- constancy and stability of the characteristics, precision and reliability of operation;
- minimal encumbrance, maximum compactness;
- limited cost.
[0042] Finally, it is clear that numerous variants can be brought to the apparatus in question,
without for this reason leaving the novelty principles inherent to the inventive idea,
just as it is clear that, in the practical embodiment of the invention, the materials,
the shapes and the sizes of the illustrated details can be whatever according to the
requirements and they can be replaced with others which are technically equivalent.
1. Compact measurement apparatus (16) for the protection of medium-voltage lines, of
the type suitable for picking up electrical signals and for carrying out a series
of measurements and processings of said signals, to identify functionalities of malfunctions
of the line currents and taking care of possible. protection interventions against
overload, instantaneous and delayed short-circuit and grounding failure, characterised in that said protection apparatus (16) includes in a single insulating container casing (20),
a plurality of first toroidal windings (40, 44, 47), one for each phase and arranged
in combination with each other, and at least one second winding (39), suitable for
collecting the phases of said switch (10), said second winding being separated from
said first windings by at least one insulating wall.
2. Compact measurement apparatus (16) according to claim 1, characterised in that it can be associated with at least one circuit-breaker relay (26) of the switchboard
(27) of a bar switch and disconnecting switch (22), said relay (26) being suitable,
upon the basis of the line and grounding current detections, both in nominal conditions
and in the presence of disturbances and thanks to suitable procedures controlled by
internal microprocessors, to realise active current protection.
3. Compact measurement apparatus (16) according to claim 2, characterised in that said current detections are carried out passing a series of cables (23) of the medium-voltage
lines inside said first toroidal windings (40, 44, 47), said cables (23) being then
respectively connected to said switch (22), through specific lower connectors (25),
said measurement apparatus (16) supplying in output a series of first signals proportional
to the current circulating in the phases, which are conducted to said circuit-breaker
or protection relay (26).
4. Compact measurement apparatus (16) according to claim 3, characterised in that it sends a further homopolar output signal, taken directly from said second winding
(39), of the homopolar type, to said protection relay (26) to allow the detection
of grounding failures.
5. Compact measurement apparatus (16) according to claim 2, characterised in that at least one (28) of said cables (23) of the medium-voltage line is used as a cable
intended for general use and for input general power supply of said switchboard (27)
attached to the compartment (21) of the bar switch and disconnecting switch (22).
6. Compact measurement apparatus (16) according to claim 2, characterised in that it foresees a series of connectors (36, 37, 38), which allow the apparatus (16),
with its current sensors, to be connected directly to said protection or circuit-breaker
relay (26).
7. Compact measurement apparatus (16) according to claim 1, characterised in that said toroidal windings (39, 40, 44, 47) behave like transformers and have a core
with a substantially large diameter.
8. Compact measurement apparatus (16) according to claim 1, characterised in that said second toroidal winding (39) allows the grounding failure current to be detected,
through the execution of a vector sum of the phase currents.
9. Compact measurement apparatus (16) according to claim 1, characterised in that it is suitable for detecting current signals to realise protection relative to overload
at long reverse time and at adjustable fixed time, short-circuit at adjustable independent
time, maximum phase current and maximum grounding failure current protection.