[0001] A refrigeration plant comprising at least one compressor, which compressor is delivering
compressed refrigerant to at least one condenser, from which condenser liquid refrigerant
is led to at least one evaporator through at least one restriction element, where
the compressor is connected to the evaporator, and where a defroster circuit is arranged
for selectively supplying hot refrigerant to said evaporator equipment for defrosting
purposes.
[0002] Defrosting is necessary to remove ice built up on a freezer or a cooler. In most
cases it is a question of proper and efficient function of the equipment, but in some
cases it is a vital part of the function. One of the latter cases is a plate freezer,
where the product is frozen between two metal plates wherein refrigerant is circulated.
To be able to remove the product it is necessary to defrost the plates.
[0003] Defrosting can be done in several ways, with the most common being:
- Spraying with hot water, which is very common but not very practical due to hygienic
considerations.
- Electrical defrosting by means of electrical heating rods placed near the cooling
surface. The main disadvantage is that when compared to the hot gas defrost, the power
consumption is much higher. Because of the defrost compressors COP (cooling capacity
kW per power consumption kW) the power fed to the defrost system is 4-5 times higher
with electrical defrost for the same defrost capacity. Another disadvantage is that,
when using electrical defrosting, the ice is melted from the outside, which means
that more ice has to be melted before the remaining ice falls from the cooler and
that the power consumption is to high.
- Circulation of a hot liquid (usually a glycol/water mix) in a separate circuit within
the cooler/freezer. When defrosting from the inside the ice on the surface melts first
enabling the ice to fall off as soon as possible.
- Hot gas defrosting where gas is condensed in the cooler/freezer at a temperature above
the freezing point. Condensing takes place in the same circuit that is used for cooling/freezing.
In some types of evaporators e.g. plate freezers hot gas defrost is the only possible
solution for defrosting
[0004] Where ever possible hot gas defrosting is used. Hot gas defrosting is very efficient
as heat is delivered where the ice has built up and it is very economical since the
heat used is present in the system. Electrical and hot liquid defrosting requires
an external power source which hot gas defrosting does not. During hot gas defrosting
the cooler/freezer acts as a secondary condenser dispersing the heat otherwise dispersed
in the cooling media (usually water or air).
[0005] With the reintroduction of CO
2, cascade systems are becoming more frequent. Due to the high saturation pressure
of CO
2, it is not possible to keep the pressure within the range normally encountered in
refrigeration plants while still condensing it against air or water at ambient temperatures.
Thus a cascade system is used, wherein a secondary refrigeration plant cools the CO
2 condenser. The secondary refrigeration plant condenses against the available cooling
media. The condensing temperature of the CO
2 is usually in the range of-20°C to -5°C.
[0006] If a traditional approach for hot gas defrosting was to be used, the gas, otherwise
to be condensed in the cascade cooler, would be led to the evaporator. But in the
case of CO
2 the condensing temperature is, as mentioned above, in the range of -20°C to -5°C,
which is not sufficiently hot to remove ice from the evaporator. When defrosting a
cooler it is, of cause, necessary to get the temperature of the cooler (well) above
0°C.
[0007] One solution to this problem could be to raise the temperature in the cascade cooler
(e.g. refrigeration compressor outlet) to a level above the freezing point. This is
possible, but several disadvantages arise from this solution. The overall energy efficiency
of the system drops, and more important, components to handle the increased pressure
are, at best, expensive or not available. Also a very large part of the plant would
be subjected to very high pressures.
[0008] Often a valve in the outlet controls the defrosting pressure in the evaporator. This
valve will close when the pressure is lower than the desired pressure. However, this
restricts the liquid condensed during the defrosting from leaving the evaporator,
thus resulting in a build up of liquid in the evaporator. The build up of liquid reduces
the surface inside the evaporator available for condensing and as such reduces the
overall effect of the defrosting.
[0009] As a refrigerant CO
2 gives some general advantages:
- Highly efficient system, both with regard to component sizing and energy consumption.
- Efficient to low evaporating temperatures. Other refrigerants become inefficient below
-40°C, but CO2 is efficient down to -55°C, limited only by the triple point (-56,6°C)
- A CO2 leak will not destroy the product in the processing area affecting not only the yield
but also the insurance costs.
- CO2 is considered a safe refrigerant. It is non-flammable, non-explosive and it is considerably
safer to the crew than other refrigerants.
- The low evaporating temperature yields a higher capacity of the production equipment,
usually resulting in a faster freezing. The faster freezing has a positive effect
on product quality.
- CO2 is a natural refrigerant with none of the environmental problems associated with
older refrigerants such as CFC's and HCFC'S. CO2 is not harmful to the environment ensuring unrestricted use in the future from the
environmental point of view.
[0010] The patent application DK 2001 00310 describes a plant and a process using CO
2 for defrost. This system is a unit that delivers both defrosting and standstill cooling,
e.g. keeping system pressure down during standstill. In a combined system like in
DK 2001 00310, failure of the defrost system would mean that no standstill cooling
is available and it is from some classification societies a demand that the standstill
cooling is performed by a separate unit as a part of the safety system.
[0011] The above-mentioned system is connected to the "distribution system", defined as
a vessel with gas/liquid equilibrium along with the piping to the consumers e.g. the
evaporators. From the application and its definitions it appears that the possible
connection points are: A pump separator, a high-pressure receiver, and the piping
to the consumers.
[0012] Connecting the defrosting compressor to the refrigeration cycle's low-pressure side
results in a very large pressure difference, which most industrial refrigeration compressors
cannot handle. Furthermore a defrosting compressor connected to the low pressure side
needs to be about 4 times bigger (by swept volume) than one connected to the high
pressure side to deliver the same defrosting capacity. Standard refrigeration equipment
can be used when connecting to the high-pressure side, while this is not the case
when connecting to the low-pressure side.
[0013] If connecting the defrosting compressor to the high-pressure receiver it is very
doubtful if sufficient gas is available in the receiver. The receiver essentially
collects liquid from the condenser and will normally not contain the large amounts
of gas necessary for defrosting.
[0014] In the DK 2001 00310 system the suction gas for the compressor is saturated, necessitating
a liquid separation. Ensuring that the suction gas contains no liquid is essential
for safe compressor operation - especially when using reciprocating compressors.
[0015] US 4,962,647 comprises a refrigerating circuit apparatus includes a two stage compressor
having an upper stage compressing cylinder and a lower stage compressing cylinder,
a heat storage tank, an upper stage side variable opening expansion valve and a lower
stage side variable opening expansion valve. The upper stage side variable opening
expansion valve is controlled towards its closed position for executing a heat storing
operation in which heat is discharged from refrigerant to the heat storage tank. The
upper stage side variable opening expansion valve is opened and the lower stage side
variable opening expansion valve is closed for carrying out a defrosting operation.
Heat stored in the heat storage tank is used in the defrosting operation for removing
frost accumulated on an external heat-exchanger during the heating operation.
[0016] In this way only a restricted part of the refrigerant leaving the upper stage of
the compressor is used for defrost, part of the refrigerant is sent to a condensing
unit and liquefied before it is lead to a separator. From the separator gaseous refrigerant
is drawn through a heat storage tank to the inlet to the upper compressor stage. The
refrigerant is at fist cooled and liquefied in the condenser and later heated and
evaporated in the heat storage tank. At the inlet the refrigerant flow is combined
with the outlet from the lower compressor stage. The two compressor stages are never
operating in parallel. An increase in the total compressor capacity by parallel operation
is not possible.
[0017] It is the purpose of the invention to define a system that can perform a hot gas
defrosting a refrigeration plants, where the system can deliver efficient defrosting
while offering noticeable benefits in terms of lower overall power consumption of
the plant and a high degree of use of standard refrigeration components.
[0018] The present invention comprises a refrigeration plant as the one described in the
opening paragraph, operating with at least one compressor which comprises at least
a first compressor section and a second compressor section, which first and second
compressor sections can be operating in serial connection during defrost, where the
first and second compressor sections can be operating in parallel during normal operation,
where the pressure outlet of the second compressor section during defrost is connected
to a gas pipe connection which is connected to a refrigerant channel system of said
evaporator equipment.
[0019] In this way a compressor build in sections, maybe with a common motor, can operate
very flexibly because defrost of evaporators is only necessary in a few minutes with
an interval of several hours. The compressor section can operate in parallel in periods
with no defrost. If the refrigeration plant operates as a heat pump, defrost may only
be necessary in the coldest winter.
[0020] The second compressor section is being operable to supply defrost gas at elevated
pressure and temperature governed by preset or presetable discharge pressure/temperature
requirements. In this way special requirements for the cooling plant can bee fulfilled.
Defrost can take place in a form depending on the use of the cooling plant. In one
situation rapid defrost with a high temperature is the best solution, but in other
situations the defrost temperature needs to bee low in order not to damage the food,
but the defrost period can bee longer.
[0021] This invention also relates to a refrigeration system of the cascade type where said
defroster circuit comprises a defrost compressor section arranged in a gas pipe connection
from the discharge side of said one or more refrigeration compressors or compressor
sections to the refrigerant channel system of said evaporator equipment, said defrost
compressor being operable to supply defrost gas at elevated pressure and temperature
governed by preset or preset able discharge pressure/temperature requirements. At
+10°C the CO
2 pressure is 45 bar, which calls for a separate dedicated defrost system.
[0022] The system according to the invention limits the high pressure to an absolute minimum
number of components while employing as many standard components as possible. Using
a dedicated defrosting compressor section another pressure level is created with the
sole purpose of defrosting. In this way the high pressure can be limited to the defrosting
compressor section, the defrost pipe, the evaporator to be defrosted and a few valves
at the evaporator. The cascade cooler, refrigeration compressor and associated equipment
can be held at the temperature/pressure yielding the most overall efficient plant
and still be standard refrigeration components. The defrosting compressor section
is connected to the refrigeration compressor outlet.
[0023] A system according to the invention has an especially dedicated compressor section
for defrosting. This defroster compressor section suction gas is the refrigeration
compressor discharge gas. The gas has been desuperheated before entering the defrost
compressor to avoid too high discharge temperature that could create a problem with
lubrication of the defrost compressor. Furthermore the COP (cooling capacity kW per
power consumption kW) of the defrost compressor would be lower and oil cooling would
be necessary.
[0024] Desuperheating (cooling) of the suction gas to the defrosting compressor section
has an effect on the overall power consumption of the plant. Two methods of cooling
are the most likely; the first one being cooling with the same media used in the secondary
systems condenser (air or water) and the other method is using the cascade cooler.
[0025] Normally a cascade cooler would desuperheat the gas before condensing, so introducing
a nozzle in the appropriate place in the cascade cooler would yield a supply of cooled
gas. In the cascade cooler the cooling is performed by the secondary system so power
will be required by the secondary system. Also it is of very high importance that
the gas supplied to the defrosting compressor does not contain liquid. A positive
superheat is required to avoid liquid hammer (attempting to compress liquid) in the
compressor.
[0026] The other option, the air/water cooled cooler, offers some advantages. As mentioned
earlier, it is not practically possible to condense the CO
2 against air/water at a normal ambient temperature, but it is possible to use it to
cool the gas before entry into the cascade cooler and defrosting compressor. The benefit
is that every kW cooled by the cooler does not have to be removed in the cascade cooler.
This results in a reduction of both the size, and power consumption of the secondary
system. In such a cooler the gas can be cooled to a temperature very close to the
ambient temperature, but since the saturation (condensing) temperature is much lower,
the gas is still sufficiently superheated to avoid liquid hammer. The selection of
one of these two systems will be a question of installation costs versus the savings
in running costs.
[0027] The defrost compressor section can comprise capacity regulation. The condensing temperature
determines the suction pressure in the cooling cycle. This pressure is kept constant
by the "hot" refrigeration cycle.
[0028] To avoid excessive changing of the compressor capacity steps and an unintended pressure
rise at the end of the defrost period when defrost capacity demand is low, a controllable
bypass valve is used to bypass hot gas back to the cascade cooler. The bypass valve
is arranged in a connection from the discharge side of the defrost compressor section
and the discharge side of the one or more refrigerating compressors. A precise control
of the defrost pressure and temperature is thereby enabled and the bypass valve will
smoothen the capacity steps and secure that the pressure does not exceed the maximum
design pressure. This control method makes it unnecessary to mount control valves
on each cooler to control the pressure during defrost. All defrost control is done
by the compressor section and the bypass valve.
[0029] The defrost pressure/temperature can be set individually for each evaporator by changing
the defrost compressor section. In this way the defrost can be optimised for the individual
type of evaporator. Some applications can benefit from a more gradual defrost while
some need a fast defrost. Considerations when selecting defrosts temperature will
include heat loss into the surroundings, water/steam contents in the room air and
product quality.
[0030] On a system according to the invention the refrigerant outlet from the evaporator
equipment can be connected to the suction side of the one or more refrigeration compressors
through a liquid operated liquid draining device.
[0031] Draining the cooler during defrost is a very important issue. When the cooler fills
with liquid the surface available for condensing (defrost) becomes smaller and consequently
the possible capacity drops meaning a slower defrost. The system according to the
invention has for this purpose employed a thermodynamic liquid drain designed for
steam and compressed air application. This device allows liquid to pass and stops
gas in much the same way as a float valve mechanism. Float valve mechanisms employ
a floating ball but these have been difficult or expensive to get for the high pressure
needed. The liquid drain used is simple and can accept the pressures. The benefit
is that when the compressor controls the pressure completely, the liquid drain only
needs to drain the liquid in the freezer and not concern itself with regulating the
pressure. The result is an extremely simple system with an efficient operation.
[0032] A system as described, wherein the entire gas conductor system from the defrost compressor
section through the evaporator equipment and to the drain pipe of the evaporator can
generally be without pressure regulating means and will preferably be laid out for
operating at pressures not exceeding 50 bar.
[0033] It can, however, not be excluded that a higher pressure, for instance 55 bar, will
be more suitable in a alternative embodiment of the invention.
[0034] All together the installation is considerably simpler, less expensive and more secure
compared to known solutions.
[0035] The system according to the invention described herein has a plurality of benefits
compared to the alternative systems:
- Except for the defrost compressors' oil separator there are no vessels in the high-pressure
system. The oil separator has a very low volume. Large volumes under high pressure
present a safety hazard due to the high energy content.
- The defrost pressure/temperature is controlled by the compressor section. The compressor
section can regulate its discharge pressure rather than the traditional suction pressure
regulation. It is possible to regulate the compressor section either by the normal
compressor capacity step supplemented by a bypass valve to achieve a finer regulation
or by using a frequency converter on the compressor motor to regulate the compressor
RPM. This can be necessary because of the high capacity of a single capacity step
on reciprocating compressor section.
- It is not necessary with regulating valves for the cooler. The compressor does all
pressure/temperature regulation.
- When the defrost pressure is controlled by the compressor it is only necessary to
drain the cooler of liquid. When liquid is drained the maximum surface is available
for condensing.
- The drainage is secured by a thermodynamic liquid drain, a commonly available component
for compressed air and for steam or by a high-pressure float valve.
- High-pressure is only present while the compressor is running. In effect all pressure
will equalize when a critical situation occurs (e.g. a power failure, wrong valve
position) or when the compressor emergency stop is pressed.
- By taking the discharge gas from the refrigeration compressors and not from the pump
separator the COP (cooling capacity kW per power consumption kW) is greatly enhanced
offering a much better economy. Furthermore the requirement for the compressor size
is greatly decreased.
- In systems where the need for defrosting is not continuous, but rather at discrete
intervals, the defrost compressor could be used as a normal refrigeration compressor.
The compressor used for defrosting can be a dedicated defrost compressor section,
but can also be combined with anyone of the refrigeration compressors. A system according
to the invention can be designed with the possibility to use one or more sections
of a plurality of compressors in the system as defrost compressor sections. In this
way an increased safety and reliability of the system is achieved. The performance
of the compressor in the two running conditions is well matched. That is, when running
in the defrost condition the compressor yields 3-5 times as much as when in the refrigeration
condition. This ratio is deemed suitable for defrosting in a reasonable time. Thus,
when a cooler is taken out of operation to be defrosted, the excess compressor capacity
at cooling level matches the need for defrost capacity.
- The gas for defrosting is greatly superheated which, apart from the actual gain in
heating capability, secures the system against condensation in pipes and valves before
entering the cooler. If liquid enters a low-pressure area from a high-pressure area
it can be "shot" into the low-pressure area and considerable damage can occur from
this.
- The compressor is able to start the defrost "gently" while running up the pressure
at the start of the defrost. This reduces the risk of pressure surges and liquid hammer.
- It is possible to make individual defrost conditions for different evaporators to
suit the individual needs.
[0036] Power consumption of the system is considerably affected if the system according
to the invention is employed. Heat absorbed in the evaporators will, along with the
CO
2 compressor motor heat, be delivered to the secondary (usually R717) refrigeration
system in the cascade cooler. Even though the cascade temperatures have been fixed
at the overall most efficient point, the secondary system accounts for 60-70% of the
overall power consumption. But when the defrosting compressor is in action the defrost
compressor suction gas need not be condensed by the secondary system resulting in
a drop in required cooling capacity of the secondary system.
[0037] The gas will, after compression in the defrosting compressor, be condensed in the
evaporator to be defrosted. However, the COP (cooling capacity kW per power consumption
kW) is much higher in the defrosting compressor than in the secondary systems compressor.
The difference is naturally dependent on the type (refrigerant etc) of the secondary
system and running conditions, but in general terms a factor of two is realistic.
This means that for every 100 kW used by the defrosting compressor, the power consumption
of the secondary system drops with 200 kW with a resulting overall drop of 100 kW.
[0038] With 100 kW power consumption, the defrost compressor employed in this system will
deliver approximately 600 kW heating. If electrical defrosting is to be used, all
600 kW is needed in electricity, so the comparison is really an increase of 600 kW
compared to a drop of 100 kW. If hot glycol is to be used the heating could be extracted
in the system (most likely the secondary system's hot side) so the power consumption
only increases with the pump power. However, no gain similar to the one described
above is achieved.
[0039] On a plant according to the invention it has been discovered that there is a large
over all efficiency benefit during defrosting, as mentioned above. For the understanding
of the invention it has to be mentioned that the compressors used are mainly large
industrial compressors for industrial cooling purposes, but that the invention can
also be used in connection with plants comprising commercial compressors capable of
handling the given pressure and temperature. As an example cooling and freezing plants
in butcher shops, in supermarkets or in other retail shops can be mentioned as places
to use the system.
[0040] To save even more energy using the system according to the invention it is possible
to use the defrost compressor capacity to supply hot gas to other elements than to
a traditional evaporator e.g. to elements consisting of heating/evaporator pipes placed
in areas where ice otherwise will built up. As an alternative the hot gas could also
be used for heating.
[0041] Freezers that need defrosting are often used onboard fishing vessels, and in such
plants heating/evaporator pipes can be installed in the floor in the freezing area.
In this area there will typically be ice formations, which today is removed or controlled
by electrical heating elements. By replacing these elements with heating/evaporator
pipes less electrical power is needed and the defrost compressor is used more efficiently
whereby energy is saved in the second condensing unit.
[0042] CO
2 hot gas from the defrost compressor can be used for traditional defrosting, for heating
and for defrosing in all places where the temperature is below 10 °C.
[0043] In the following the invention will be described with reference to the drawing where:
Fig. 1 shows a system according to the invention,
Fig. 2 shows a system comprising more compressors, and
Fig. 3 shows a log(P)-H diagram of defrost according to the invention in cascade systems.
[0044] Referring to fig. 1, which shows a system according to the invention, the system's
function will be described. Please note that the figure is simplified to ease the
understanding.
[0045] The freezing system 2 is executed in the traditional manner. The pump separator 4
contains liquid refrigerant at the evaporating temperature. The pumps 6 pump refrigerant
liquid to at least one evaporator 8 through the valve station 10.
[0046] In the evaporator 8 the refrigerant liquid is partially or completely evaporated
and returned through a line 26 to the pump separator 4. The gas generated in the evaporator
8 is removed by at least one refrigeration compressor 12, which compresses the gas
to the condensing pressure. From the refrigeration compressor 12 the gas is primarily
led to the cascade cooler 14 where the gas is condensed before being led back to the
pump separator 4. A secondary condensing unit 16 provides cooling for the cascade
cooler 14. The freezing system 2, as described here, is prior art technology and is
as such not interesting, but the defrosting system is the essence of the invention
described here.
[0047] The compressor 12 is a two section compressor, comprising a common motor 50 connected
to a primary compression section 52 and to a defrosting section 54. The defrost compressor
section 54 takes suction from the discharge of the refrigeration compressor section
52 (e.g. at condensing pressure) and compresses it to the desired defrost pressure.
Please note that the gas from the refrigeration compressor section 52 is significantly
superheated. To avoid too high discharge temperature (oil problems) from the defrost
compressor section 52, it could be necessary to desuperheat (cool) the gas before
entry into the defrost compressor section 54. This cooler has not been included on
the sketch, because the function is not vital to the principal function of the defrost
system. The gas cooling could take place in an external heat exchanger or it could
take place in the cascade cooler 14. As mentioned this gas cooling is not essential
for the principal function of the system 2, but since some energy efficiency issues
arise from this, it will be discussed later in detail.
[0048] From the defrost compressor section 54 the gas is led to the evaporator 8. In fig.
1 the gas is led through a conduit 56 comprising a magnetic valve 58 to the liquid/gas
"outlet" 22 of the evaporator 8, resulting in a defrosting flow backward in the evaporator
8. Considerable differences of opinion exist about defrosting forward or backward,
but in this case backward defrosting is considered most efficient and thus it is outlined
here. Furthermore backward defrosting is safer since the risk of liquid bullets being
shot through the system is reduced. In the evaporator 8 the defrost gas condenses
and it is led out through the liquid "inlet" 24 of the evaporator 8. Returning this
(for now high-pressure) liquid is done in the normal return line 26 to the pump separator
4, however, the pressure needs to be reduced to the evaporating pressure before entering
the return line 26. This is done in a high-pressure float valve 28 or a component
with the same characteristics. The purpose of this component 28 is both to reduce
the pressure, but also to allow all liquid to drain from the evaporator 8, but not
allowing any gas to pass during defrosting. With the use of this float valve 28 (or
like) the evaporator 8 will always be completely drained during defrosting resulting
in an efficient defrost. Furthermore, since the evaporator 8 will be full of liquid
from the freezing cycle at the beginning of the defrosting, a fast and efficient drainage
is secured with the float valve system 28.
[0049] One small thing needs to be observed with this arrangement. During the freezing cycle
the float valve 28 could act as a short circuit and bypass all the liquid pumped to
the evaporator 8 back to the return line 26. This is avoided by adding a valve 30
in series with the float valve 28. This valve 30 has an opening pressure that is larger
than the pressure loss in the evaporator 8 and will thus remain closed during the
freezing cycle.
[0050] Regulation of the pressure during defrosting is performed by the compressor section
54 capacity regulation. The compressor section 54 capacity regulation will regulate
according to the discharge pressure as opposed to the "normal" suction pressure regulation.
This method of regulation is common in heat pumps. The suction pressure for the defrosting
compressor section 54 (e.g. the condensing pressure in the CO
2 circuit) is kept constant by the secondary condensing unit 16. Regulating the pressure
with the compressor section 54 while the float valve 28 drains the evaporator 8 (regardless
of the pressure) has some benefits:
- Rather than using a regulating valve for each evaporator 8, the control is at one
point only resulting in a more simple control. Furthermore pressure regulators for
50 bars pressure are not standard refrigeration equipment.
- Changing the compressor discharge pressure set point makes it possible to adapt the
defrosting to the component to be defrosted. For instance in a plate freezer 8 the
defrosting time is very important and thus the maximum temperature would be specified
to the compressors control system, while in an air cooler in a freezing storage room
it could be desirable to minimize the heat ingress into the room. This could be done
with a defrosting at a lower temperature for a longer time.
- The evaporator 8 is, as mentioned, completely drained and thus offering the maximum
surface area for condensing. Once the gas has condensed, e.g. given off its latent
heat, it is of little use in the defrosting process. Removing the liquid enables the
maximum defrosting capacity to be achieved.
- The defrosting compressor section 54 can bee coupled in a parallel mode by opening
and closing of magnetic valves 58, 60, 62, 64 when no defrost is required, thus reducing
wear from excessive start-stop situations. In defrost mode magnetic valves 58 and
60 are open. The valves 62 and 64 are closed. Regulation of the compressor section
54 can take place by valve 64, which valve 64 can bee opened partly by modulation
and a controllable bypass connection 66 around the compressor section is formed to
bypass hot gas back to the cascade cooler 14.
[0051] Fig. 2 shows an alternative embodiment for the invention, where the figure differs
in having more compressors 70 and 72. These compressors are always operating as cooling
compressors, where defrost is carried out by the compressor section 54.
[0052] Fig. 3 is showing a log (P)-H diagram of defrost according to the invention in cascade
systems. The diagram shows the normal refrigeration cycle (34). From evaporating pressure
(36) the refrigerant is compressed (38) up to the condensing pressure (40). From the
compressor discharge (42) the gas is cooled and eventually condensed before it is
flashed back to the evaporating pressure (36). The system according to the invention
connects the defrosting compressor section (54) after the refrigeration compressors
discharge port (42) and before condensing takes place (44) in the condenser/cascade
cooler. The compressor section (54) is compressing (39) the refrigerant to the defrost
pressure (45), where the refrigerant remains at a nearly constant pressure (45) during
defrost of an evaporator. After end of defrost the pressure of the refrigerant is
reduced (43) to the normal condensation pressure (40).
[0053] On other known systems for CO
2 defrosting the defrost compressor is connected at the refrigeration compressors suction
side (46) or after the condenser/cascade cooler (48).
1. A refrigeration plant comprising at least one compressor unit (12), which compressor
unit (12) is delivering compressed refrigerant to at least one condenser(14), from
which condenser liquid refrigerant is led to at least one evaporator (8) through at
least one restriction element, where the compressor is connected to the evaporator,
and where a defroster circuit (56) is arranged for selectively supplying hot refrigerant
to said evaporator equipment (8) for defrosting purposes, characterized in, that at least one compressor unit (12) comprises at least a first compressor section (52)
and a second compressor section(54), which first and second compressor sections (52,
54) are operating in serial connection during defrost, where the first and second
compressor sections (52, 54) are operating in parallel during normal operation, where
the pressure outlet of the second compressor section (54) during defrost is connected
to a gas pipe connection (56) which is connected to a refrigerant channel system of
said evaporator equipment (8)
2. A refrigeration plant according to claim 1, characterized in, that the second compressor section (54) being operable to supply defrost gas at elevated
pressure and temperature governed by preset or presetable discharge pressure/temperature
requirements.
3. A refrigeration plant according to claim 1 or 2, characterized in, that the suction side of the second compressor section (54) is connected to the discharge
side of the first compressor section (52) or one or more refrigerator compressors
70 through a desuperheater unit, preferably constituted by said condenser unit (14).
4. A refrigeration plant according to one of the claims 1-3, characterized in, that a controllable bypass valve (64) is arranged in a connection from the discharge side
(56) of the second compressor section and the discharge side the first compressor
section or of one or more refrigerating compressors (12).
5. A refrigeration plant according to one of the claims 1-4, characterized in, that the refrigerant outlet from the evaporator equipment (8) is connected to the suction
side of one or more refrigeration compressor units (12) through a liquid operated
liquid draining device (28).
6. A refrigeration plant according to one of the claims 1-5, characterized in, that the entire gas conductor system between the second compressor section (54) through
the evaporator equipment (8) and to the drain pipe (24) of the evaporator (8) is generally
without pressure regulating means and is laid out for operating at pressures not exceeding
50 bar.
7. A refrigeration plant according to one of the claims 1-6, characterized in, that the discharge side (56) of the second compressor section (54) is selectively connectable
to any one or more of a number of evaporator units (8) in said evaporator equipment,
while the remaining units are still operable in refrigeration mode.
8. A refrigeration plant according to one of the claims 1-7, characterized in, that at least one refrigeration compressor section (54) in parallel with one or more refrigeration
compressor sections (52, 70) is connectable so as to temporarily operate as a defrost
compressor section.