[0001] This invention relates to a booster station of sewage water, in which the startings
and stoppings of pumps installed in it are controlled by means of pressure prevailing
on the suction side of the pumps or by means of frequencies in frequency converter
drives.
[0002] Recently, the treatment of sewage has been started to concentrate on larger and more
effective treatment plants, whereby smaller ones have been closed down. Furthermore,
buildings farther and farther from the treatment plant have been started to be taken
within the drainage system. As a result of these changes, there has occurred a need
to make so-called transfer sewers which can be extremely long. Long pressure lines
with a cost-effective flow velocity cause great flow losses, whereby the pumps are
required a great lifting height usually with relatively small volume flows. If there
also exist bottom and top dead centres in the pressure line, air or gas in the water
stays in the top dead centre and, when the pump operates, it transfers between the
top dead centre and the bottom dead centre causing an additional lifting height requirement.
Thus, a situation has arrived in which the sewage pump is required a very great lifting
height compared to the volume flow. Then, a centrifugal pump should flow-technically
be a multistage pump which includes several impellers connected in series. Such sewage
pumps are not manufactured due to clog-proofness required of them.
[0003] In a known arrangement, the transfer sewer contains several pumping stations suitably
located successively and each pump station has a suction basin in which the level
controls the startings and stoppings of the pump. Disadvantages of such an arrangement
are, inter alia, the odour problem causing inconvenience to the environment of the
pumping station, which is caused by sewage water in the suction basin in connection
with open air. This is particularly emphasised with long pressure lines in which the
retention times of water are long, whereby hydrogen sulphide is able to build up in
the wastewater. Another problem is that the suction basin increases the manufacturing
costs of the pumping station, particularly if the pumps are wished to be in a separate
dry space. Additionally, the suction basin or the whole pumping station has to be
in practice below the ground surface, which can limit their location and/or cause
digging and possibly quarrying costs. Furthermore, hydrogen sulphide or some other
gas built up in the suction basin of the pumping station causes a decline in the oxygen
content, which endangers the work safety of maintenance persons.
[0004] Another known arrangement is to connect the pumps of the same pumping station in
series. A disadvantage of this is, inter alia, that the reliability of pumping operation
decreases, because if one of the pumps is out of order, pumping does not operate at
all. A further disadvantage is that the subsequent pump has to operate with high inlet
pressure, whereby the leak possibility and leak speed of its shaft seals are increased.
Furthermore, the pumping station has to have a separate dry space for the subsequent
pump, which increases the building costs of the pumping station.
[0005] Additionally is known an arrangement in which there is no suction basin in the booster
station and in which in the previous pumping station there are two pumps which have
their own pressure pipes for the suction pipes of the pumps of the booster station.
Then, the startings and stoppings of the pumps occur according to pressures prevailing
in the suction pipes. When pumping sewage, a system of two alternating pumps is used
and the pumps are selected such that the output of one pump is always sufficient.
This way, pumping is ensured also in a case of one pump being out of order or being
serviced. In this known arrangement, the reliability of pumping however suffers, because
if in one line one of the pumps is e.g. locked or damaged and one pump similarly in
the other line, pumping does not operate and the reliability of operation is halved.
[0006] The object of this invention is to provide a novel kind of a sewage booster station
which does not pertain disadvantages occurring in known prior art. The booster station
according to the invention is characterised by the pumps of the booster station having
a common inlet pipe on the suction side which pipe branches from a previous pumping
station or an equivalent incoming inlet pipe.
[0007] An advantageous embodiment of the booster station according to the invention is characterised
by that in the inlet pipe between the inlet pipe and the pumps is located a pressure
measuring sensor suitable for sewage water.
[0008] Another advantageous embodiment of the booster station according to the invention
is characterised by that the starting and stopping of the pumps are controlled by
means of pressure prevailing in the inlet pipe.
[0009] A further advantageous embodiment of the booster station according to the invention
is characterised by that the pumps of the previous pumping station are selected such
that the lifting height of the pumps is greater than the requirement with its own
pipeline curve and desired volume flow.
[0010] As advantages of the invention, it can be mentioned that disadvantages of known prior
art have been eliminated. The booster station according to the invention requires
no suction basin. An additional advantage of the arrangement according to the invention
is that the pumps can be selected more freely as long as the lifting height requirement
of the previous pump is fulfilled, because its lifting height can also be greater
than the minimum requirement for the lifting height. It is then possible to select
the pumps such that they provide as good as possible total efficiency. Furthermore,
it is possible to select suitable pump types. When required, it is also possible to
select in the booster station a large number of different pumps. It also enables pressure
pipes incoming from several previous pumping stations.
[0011] Next, the invention is described in more detail by referring to the accompanying
drawings in which
Fig. 1 shows a cross-sectional view of two successive booster stations.
Fig. 2 shows the booster station 5 of Fig. 1 in a larger scale.
Fig. 3 shows a top view of the booster station of Fig. 2.
Fig. 4 shows a booster station installed above ground.
Fig. 5 shows pipeline curves of the pumps.
[0012] In a first pumping station 1, there is a suction basin 2 in which there are e.g.
a submersible pump or pumps 3 which pump sewage through a pressure pipe 4 to a booster
station 5. In the booster station according to the invention, there thus is no suction
basin in connection with air space.
[0013] The starting and stopping of a pump or pumps 6 of the booster station 5 are controlled
by means of pressure prevailing in an inlet pipe 7. Another possibility is to control
the starting and stopping with remote control in accordance with the starting and
stopping of the pumps 3 of the previous pumping station. When using frequency converters
in the pumping stations, the frequency of the booster station is controlled by means
of pressure prevailing in the inlet pipe 7. When further using frequency converters
in the pumping stations, the frequency of the pumps 6 of the booster station 5 is
controlled in accordance with the previous pumping station with remote control.
[0014] In the inlet pipe 7 between the inlet pipe 4 and the pump or pumps 6 is located a
pressure measuring sensor 8 suitable for sewage water. As a result of possible clogging
of the pumps or pipeline of the previous pumping station or some other reason lowering
the pressure, minimum pressure is defined for the pressure of the pressure sensor
8 in which pressure the pumps 6 will stop (to avoid cavitation) and possibly the minimum
pressure in which the pumps 3 will stop with remote control.
[0015] As a result of possible clogging of the pump 6 or its pressure pipe or some other
reason, maximum pressure is defined for the pressure of the pressure sensor 8 when
the pump is operating in which the pump 6 will stop, or maximum pressure in which
the pump 3 will stop with remote control.
[0016] In the embodiment example of Fig. 4, the booster station 5 is located above the ground
surface.
[0017] The pumps 6 are selected such that the lifting height of the previous pump is greater
than the requirement with its own pipeline curve and desired volume flow Q and the
lifting height of the pump 6 of the booster station is the common lifting height of
the pipeline curves of both pumping stations with the same Q, the lifting height of
the pump 3 of the previous pumping station deducted. The selected lifting height of
the pump 3 can also be about 15-30% greater than the requirement with its own pipeline
curve.
[0018] It is possible to locate the pressure sensor 8, which enables also the measurement
of underpressure, on the side of the pipe 7, whereby no solid matter heavier or lighter
than water will accumulate in it. The pressure of the pressure sensor 8 is monitored,
whereby changes occurring in the pumps 3 and 6 and their pressure pipelines will be
observed in time.
[0019] It is also possible that pressure pipes of several previous pumping stations arrive
in the booster station. It is also possible that the previous pumping station is in
accordance with the invention.
[0020] The lifting height requirement for the previous pump ensures that sufficient inlet
pressure is provided to the subsequent pump to avoid cavitation. In practice, the
minimum pressure can be set a little on the side of underpressure when considering
the NPSH
r value (suction capacity) of the pump. Lifting height inaccuracy is caused by the
tolerances of the Q/H curves of the pumps and the calculation inaccuracy of the pressure
pipe. It is also good to have safety margin in case the previous pump wears faster.
[0021] By the pressure of the pressure sensor 8, it is also possible to monitor the changes
of the subsequent pump and pipeline for if the pressure increases it means that changes
have occurred in the subsequent pumps or pipeline.
[0022] The lifting height (H
1) of the pumps of the previous pumping station is selected with desired volume flow
Q such that it is in the design stage between about 1.2 times a calculated lifting
height (H
3) of its own pipeline and about 0.95 times a total lifting height (H
4) of the pumps of both pumping stations and the lifting height of the pump of the
booster station is selected such that it is greater than or equal to (H
4)-(H
1). Then, it can be ensured that, due to the +/- tolerances of the pump curves and/or
the calculation inaccuracy of the pipeline curve, pressure in the suction pipe can
be increased sufficiently compared to the static state in order for the pumps of the
booster station to start and operate without the danger of cavitation. Furthermore,
the lifting heights of the pumps of the previous pumping station can in practice decrease
due to momentary clogging or water containing air, particularly if the incoming water
falls in the previous pumping station. If there are top dead centres in the pressure
line of the previous pumping station where air or some other gas can remain or accumulate,
it increases the lifting height requirement, whereby pressure can decrease in the
suction pipe. It can also decrease due to the wear of the pumps of the previous pumping
station. Then, safety margin is provided with the selection coefficient of H
1. The selection possibility of the pumps of the above-mentioned first pumping station
enables the selection of pump models good and suitable of their efficiencies.
[0023] The invention also enables combining pressure pipes incoming from several previous
pumping stations in a distributor pipe. If required, there can be several pumps connected
to the distributor pipe in the booster station. The stoppings and startings of the
pumps occur in accordance with the pressure of the distributor pipe.
[0024] If e.g. the pump of the subsequent pumping station is damaged or clogged, a maximum
value has been set for the pressure of the distributor pipe which stops the pumps
of both the booster and the previous pumping station with remote control. Then, the
pumps will not remain rotating in vain in the pumping station badly or at all.
[0025] Also pressure measurement can be installed and certain maximum pressure can be set
for the pumps of the previous pumping station, e.g. 30 s after starting, which stops
the pump if the subsequent pump is damaged or gets locked.
[0026] In the frequency converter drives, the frequencies can be set mutually suitable such
that the total efficiency on the whole frequency range can be maximised.
[0027] The booster station can be located either under or above ground.
[0028] It is well known by those skilled in the art that the invention does not limit to
the embodiment examples described above, but it may vary within the scope of the enclosed
patent claims.
1. A booster station (5) of sewage water, in which the startings and stoppings of pumps
(6) installed in it are controlled by means of pressure prevailing on the suction
side of the pumps or in frequency converter drives by means of frequencies, characterised in that the pumps (6) of the booster station (5) have a common inlet pipe (7) of the suction
side which branches from a previous pumping station (1) or an equivalent incoming
inlet pipe (4).
2. A booster station according to claim 1, characterised in that in the inlet pipe (7) between the inlet pipe (4) and the pumps (6) is located a pressure
measuring sensor (8) suitable for sewage water.
3. A booster station according to claim 1 or 2, characterised in that the starting and stopping of the pumps (6) are controlled by means of pressure prevailing
in the inlet pipe (4, 7).
4. A booster station according to any one of claims 1-3, characterised in that pumps (3) of the previous pumping station (1) are selected such that a lifting height
(H1) of the pumps (3) is greater than the requirement with its own pipeline curve and
desired volume flow.
5. A booster station according to claim 4, characterised in that the lifting height (H1) is selected such that it is in the design stage between about 1.2 times a calculated
lifting height (H3) of its own pipeline and about 0.95 times a total lifting height (H4) of the pumps of both pumping stations.
6. A booster station according to claim 5, characterised in that the lifting height of the pumps (6) is selected such that it is greater than or equal
to (H4)-(H1).
7. A booster station according to any one of claims 1-6, characterised in that in a distributor pipe (7) of the pumps (6) of the booster station (5) are combined
inlet pipes incoming from several previous booster stations.
8. A booster station according to any one of claims 1-7, characterised in that the previous booster station(s) is/are also in accordance with the invention.
9. A booster station according to any one of claims 1-8, characterised in that the booster station (5) is located above ground.
10. A booster station according to any one of claims 1-8, characterised in that the booster station (5) is located under ground.