[0001] This invention relates to the monitoring of flare stack pilot burners to check that
they are lit.
[0002] A flare stack (sometimes called a 'gas flare' or simply 'flare') is an upwardly directed
duct, open at its top end, for disposing of unwanted gases released from petrochemical
plants, oil and gas processing fields and other facilities, for instance to avoid
over-pressure conditions. The released gases are both flammable and environmentally
damaging, and to prevent their escape to the atmosphere they are burned before being
discharged from the top of the flare stack. To this end a pilot burner is located,
near the top of the stack, to ignite the released gases.
[0003] The pilot burner commonly comprises a plurality of burner elements, to provide backup
in case of failure, and such arrangements have proved effective over many years -
but only, of course, as long as the pilot burner is lit.
[0004] Pilot burners have very many different applications: boiler installations, for instance,
both domestic and industrial, commonly use a pilot burner to ignite the boiler fuel.
In most applications the pilot burner is not problematic. Thus in a boiler installation
it is usually easy to monitor the status of the pilot burner, eg by visual inspection,
and to relight it if necessary, eg by manual operation of an electronic igniter. Further,
boiler installations are routinely arranged, typically by means of a thermocouple
device responsive to the heat of the pilot burner, to shut off the supply of boiler
fuel if the pilot burner goes out.
[0005] In a flare stack, the provision of a pilot burner presents a variety of problems
as follows. First, the pilot burner is in a very exposed position, at the top of the
flare stack, where it may be extinguished, for instance by a strong gust of wind or
an updraught. Any local monitor such as a thermocouple is also exposed, and the effects
of weather etc may cause it to degrade over time. Next, unlike boiler fuel, the gas
delivered to a flare stack cannot be switched off to allow servicing unless the whole
plant is shut down for a period; and economics means that this can be afforded only
very infrequently, perhaps at three year intervals. Also, between scheduled services,
all personnel are generally forbidden to enter an exclusion zone surrounding the flare
stack, for safety reasons. Finally, the elevated location of the pilot light, which
may be as much as 200m from the ground, makes it difficult to clean, repair or replace
the pilot burner assembly and any local monitor even when access is permitted.
[0006] For these reasons arrangements for monitoring pilot burners in boilers and the like
operating in a substantially stable environment in an accessible location are not
applicable to the monitoring of flare stack pilot burners, which are exposed to a
harsh and greatly varying environment in an inaccessible location.
[0007] This combination of problems can be tackled by monitoring the status of the pilot
burner at a remote location conveniently sited, eg at ground level and outside an
exclusion zone, where the monitoring system can be readily serviced as and when required,
and relighting the pilot burner automatically whenever the monitoring system detects
that it has gone out. (For completeness it may be noted that arrangements of this
kind may include local pilot burner monitors such as thermocouples as well, to maximise
overall reliability).
[0008] It is an object of the present invention to provide remote monitoring of a flare
stack pilot burner.
[0009] Thus according to a first aspect of the invention there is provided a flare stack
comprising a gas discharge duct, a pilot burner operative at a burner location to
ignite gas discharged by way of the duct, sampling means operative to sample gases
at the burner location and deliver a sample thereof to a monitoring location remote
from the burner location, a sensor at the monitoring location responsive to a parameter
of the sample indicative of combustion at the burner location and a signalling device
operatively associated with the sensor and arranged to provide a signal automatically
if the sensor does not detect said parameter in said sample.
[0010] The flare stack may include an igniter activated automatically in response to said
signal to relight the pilot burner, although in many situations it may be enough for
an operative to institute reignition action when said signal appears.
[0011] Preferably the monitored parameter is the proportion of a selected constituent of
the sample and said signal is provided automatically if the sensor detects that said
proportion differs from a predetermined reference value therefor.
[0012] The reference value may be an average from measurement of said proportion over time,
said signal being provided automatically if the sensor detects a change from the average.
[0013] Alternatively the reference value may be a predicted value for said proportion. With
this arrangement (a) the reference value may be the proportion of carbon monoxide
in the sample and said signal provided automatically if the sensor detects that the
proportion thereof in the sample is above the reference value or (b) the reference
value may be the predicted proportion of oxygen in the sample and said signal provided
automatically if the sensor detects that the proportion thereof in the sample is above
the reference value or (c) the reference value may be the predicted proportion of
carbon dioxide in the sample and said signal provided automatically if the sensor
detects that the proportion thereof in the sample is below the reference value or
(d) the reference value may be the predicted proportion of oxides of nitrogen in the
sample and said signal provided activated automatically if the sensor detects that
the proportion thereof in the sample is below the reference value.
[0014] The sensor may comprise an electrochemical cell or it may comprise other means such
as a non-dispersive infrared (NDIR) sensor.
[0015] The sampling means preferably comprises a conduit extending from the burner location
to the monitoring location. The sampling means may comprise an aspirator operative
to draw the sample through the conduit from the burner location to the monitoring
location and the aspirator may operate substantially continuously or periodically.
[0016] The igniter may comprise a flame front generator at the monitoring location operative
when activated to propagate a flame through the conduit to the burner location. Alternatively
the igniter may comprise a high energy electrical igniter at the burner location.
[0017] As a supplement to the remote sensor, the flare stack may also include a flame sensor
such as a thermocouple at the burner location, the igniter being operatively associated
with the flame sensor and arranged to ignite the pilot burner automatically if the
flame sensor does not detect a flame, and for increased reliability the pilot burner
may comprise a plurality of burner elements.
[0018] Preferably the gas discharge duct extends upwardly from ground level to an open end
with the burner location adjacent the open end of the duct.
[0019] It is preferred that the monitoring location be remote from the duct, preferably
at ground level for ease of monitoring and servicing, and the monitoring location
may include a display operatively associated with the or each sensor and arranged
to indicate the status of the pilot burner.
[0020] According to a second aspect of the invention there is provided a method of disposing
of unwanted gas released from oil or gas production facilities, which method comprises
providing a duct for discharge of the unwanted gas, providing a pilot burner at a
burner location to ignite gas discharged by way of the duct, sampling gases at the
burner location, delivering the sample to a monitoring location remote from the burner
location, testing the sample at the monitoring location to detect a parameter indicative
of combustion at the burner location and providing a signal automatically if said
parameter is not detected in the sample.
[0021] The pilot burner may be reignited automatically when said parameter is not detected
although in many situations it will be enough for an operative to institute reignition
when said signal appears.
[0022] In this method of disposing of unwanted gases said parameter is preferably the proportion
of carbon monoxide and/or oxygen and/or carbon dioxide and/or oxides of nitrogen in
the sample, measured against a predetermined reference value for the parameter. The
reference value may be either a time-averaged empirical value or a predicted value
for the flare stack.
[0023] The invention will now be described by way of example only with reference to the
accompanying drawings which are purely schematic and not to scale and in which -
Figure 1 shows in side elevation a flare stack embodying the invention;
Figure 2 shows a monitoring system of the flare stack of Figure 1;
Figure 3 shows a second monitoring system;
Figure 4 shows a third monitoring system; and
Figure 5 shows a fourth monitoring system.
[0024] The specific embodiments of the invention shown in the drawings are hereinafter described
in relation to their use in an oil production facility but for the avoidance of doubt
it should be noted that the invention is not so limited. The invention may be used
in gas production facilities, in oil or gas processing facilities and in industrial
premises quite unrelated to oil or gas production or processing such as steelworks.
[0025] Referring first to Figure 1, this shows a duct 10 extending upwardly from ground
level 12 in an oil production facility. The nature of oil (and gas) production is
such that from time to time unwanted gas ― generally hydrocarbons - needs to be discharged,
for instance to avoid excess pressure. The duct 10 therefore provides a discharge
path for the unwanted gas, which is delivered to the duct 10 by way of a pipe 14.
[0026] The duct 10 is open at its upper end but the unwanted gas, which is mostly methane,
cannot be released into the air because it is inflammable, toxic and environmentally
damaging. Accordingly the unwanted gas is ignited so that it is burnt before being
released. To this end a pilot burner 16 is positioned at a burner location near the
top of the duct 10 to ignite gas discharged by way of the duct 10.
[0027] It is not necessary here to detail the form of the pilot burner 16. It comprises
a plurality of burner elements fuelled by way of a gas line 18 and kept alight to
ignite any unwanted gas discharged through the duct 10. In common fashion, a local
thermocouple sensor is arranged to detect the flame from the burner element, so that
if the flame should be extinguished for any reason it can be reignited automatically
by a local high energy electrical igniter.
[0028] The very exposed location of the pilot burner 16 means not only that it may be extinguished
but also presents serious problems in monitoring and maintaining the flame. Both the
thermocouple sensor and the local electrical igniter are subject to severe and widely
varying weather conditions which cause them to degrade and possibly become inoperative
over the period of time - say three years - for which the flare stack is required
to function without servicing or repair. But for all that period, unwanted gas may
need to be discharged, at indeterminate moments - and it is therefore not acceptable
for the pilot burner 16 to be out of action at any time. It will also be understood
that the pilot burner 16 cannot be serviced or repaired during the period of operation
because for safety reasons personnel cannot access it. (Apart from the difficulty
and danger of carrying out repair work at the top of the duct 10, which may be 200m
high, in practice the duct 10 is surrounded by an exclusion zone which personnel are
not permitted to enter during the period of operation).
[0029] The invention provides a monitoring station 20 for monitoring the pilot burner 16
at a location remote therefrom and reigniting it whenever necessary. As can be seen
from Figure 1, the location of the monitoring station 20 is at ground level and outside
an exclusion zone indicated at fence 22, so the monitoring and associated systems
at the monitoring station 20 can be readily inspected and serviced as required.
[0030] A conduit 24 extends from the burner location at the top of the duct 10 to the monitoring
station 20. Gas samples from the burner location (ie just above the pilot burner 16)
are delivered by way of the conduit 24 to the monitoring station 20 where they are
tested for indications of combustion. If a sample shows no indication of combustion
when tested at the monitoring station 20, a flame front generator (not detailed in
Figure 1) fuelled from a gas supply 26 is automatically activated to reignite the
pilot burner 16. This is conveniently done by way of the conduit 24, but it will be
understood that a separate path may be provided and that some means other than a flame
front generator may be activated to reignite the pilot burner 16.
[0031] The gas samples may be tested at the monitoring station 20 for various parameters
indicative of combustion including the proportions of carbon monoxide (CO) and/or
carbon dioxide (CO
2) and/or oxygen (O
2) and/or oxides of nitrogen (NO
x) in the samples, and test arrangements for these will now be described with reference
to Figures 2 to 5.
[0032] Thus, referring next to Figure 2, this shows the monitoring station 20 to include
a non-dispersive infrared (NDIR) sensor indicated at 30 for detecting the presence
of carbon dioxide in a sample. An aspirator 32 draws sampled air through the conduit
24 as indicated by arrows A.
[0033] Whilst for ease of identification the aspirator 32 is illustrated with a fan in Figures
2 to 5, it is to be understood that a pump or other aspiration means may be provided,
and it may alternatively be possible to blow the atmospheric samples through the conduit
24 from the burner location rather than drawing them through by aspiration at the
monitoring location. Whatever kind of aspiration is used it should be dimensioned
appropriately and otherwise configured and arranged to suit the form of the conduit
24 and the mode of operation. For instance, if samples are to be taken periodically,
say once an hour, the aspirator 32 must have sufficient capacity to pass at least
the volume of air in the conduit within a few minutes, suggesting a required throughput
of some tens of litres per minute. However, if the sampling is continuous, a throughput
of two or three litres per minute may be to be sufficient.
[0034] Aspirator capacity and other factors will affect the choice of continuous or periodic
sampling at any particular site. Consider a conduit 24 of length L m and internal
cross-sectional area A m. Then if the aspirator 32 is operated for 5 minutes every
hour it must be able to pass at least the internal volume of the conduit 24 within
5 minutes, and so it must have a throughput of at least AU300 m
3/s. To secure the same response time of 1 hour with continuous sampling, the aspirator
32 must pass the internal volume of the conduit 24 within 1 hour, and so it must have
a throughput of AU3600 m
3/s. It follows that, other things being equal, hourly sampling requires an aspirator
some 12 times more powerful than continuous sampling. Overall, power consumption should
be about the same but serviceability and noise levels are likely to be different.
Another factor that may affect the choice between continuous and periodic sampling
is the possibility with periodic sampling that carbon dioxide, being heavier than
air, may pool at a low point of the conduit 24 and give rise to misleading tests at
the monitoring station 20.
[0035] Returning now to Figure 2, the NDIR sensor 30, which is a spectroscopic device, comprises
a sample chamber 34 extending transversely across the conduit 24 and having an infrared
lamp 36 at one end, an infrared detector 38 at the other end and an optical filter
40 between the lamp 36 and the detector 38. The filter 40 absorbs all radiation from
the lamp 36 except in the absorption band for CO at 4.67 µm. If CO is present in the
chamber 34, the radiation reaching the detector 38 is attenuated, and the amount of
attenuation is related to the concentration of carbon dioxide. (From Beer's Law, l
= 1
oe
kP, where I is the intensity of light reaching the detector 36, l
o is the intensity measured with an empty sample chamber 32, P is the concentration
of gas under test and k is a constant).
[0036] Thus the NDIR sensor 30 measures the proportion of CO in the atmospheric sample A
drawn through the conduit 24 and passing through the chamber 34. And because the presence
of CO in a proportion greater than in free air is an indicator of combustion, the
sensor 30 detects whether the pilot burner 16, from which the atmospheric sample A
is obtained, is alight. If the sensor 30 records a proportion of CO below a predetermined
threshold it delivers a signal by way of a control line 42 to activate a flame front
generator 44 which is supplied with gas at B and when activated causes a flame to
be propagated up the conduit 24 - that is, in a direction opposite to the arrows A
- to reignite the pilot burner 16. (Although not detailed in the drawings, the aspirator
32 may be switched off while the flame front generator 44 is activated). For monitoring
purposes the output of the sensor 30 is also delivered, by way of a monitoring line
46, to a visual display unit (VDU) 48.
[0037] Since CO is present only in extremely small amounts in free air (usually not more
than 100 parts per billion) any CO detected by the sensor 30 can be taken to be indicative
of combustion.
[0038] As an alternative to the NDIR CO monitor 30 of Figure 2, the proportion of CO
2 in the sample A may be detected by an electrochemical cell 50 as shown in Figure
3. The sensor 50 is shown much enlarged in Figure 3a and comprises a substrate 52,
a heating element 54, a dielectric sealing element 56, a metallic anode 58, a solid
electrolyte 60 of CO
2―sensitive material and a metallic cathode 62. Electrochemical cells like the sensor
50 are well known and do not need detailed description here. Briefly, in the presence
of CO
2 the CO
2―sensitivity of the electrolyte 60 causes an electromotive force (EMF) to be generated
between the anode 58 and the cathode 62, and the change in EMF is related to the change
in CO
2 concentration. Thus a drop in EMF as measured at 64 indicates a reduction in the
proportion of CO
2 in the sample A which in turn indicates that the pilot burner 16 has been extinguished.
Then the flame front generator 44 can be activated to reignite the pilot burner 16.
[0039] The heating element 54 maintains the electrolyte 60 at a temperature at which its
CO
2-sensitivity is maximised. It functions satisfactorily in a range from 0.035% CO
2 (which is just below the average concentration of CO
2 in free air) to 5% CO
2 and thus provides an ample margin for measuring changes in CO
2 concentration around 1%. CO
2 threshold value for activation of the flame front generator 44 can be determined
empirically for any given flare stack from actual measurement over time.
[0040] A solid-state device like the CO
2 sensor 50 may be cheaper than an NDIR sensor as shown in Figure 2. However, it may
be prone to degradation over time, although this can be countered by periodically
purging it, by a free air line (not shown) from the aspirator 32 or possibly by running
the aspirator in reverse.
[0041] Figure 4 illustrates the use of an oxygen sensor 70. The sensor 70 comprises a tube
72 formed of yttria-stabilised zirconia (YSZ) and extending transversely across the
conduit 24. The exterior of the YSZ tube 72, which is heated by a heater 74, is thus
exposed to the sample flow A through the conduit 24. The interior of the YSZ tube
72 is exposed to a flow of free air C. A metallic reference electrode 76 is deposited
on the inner surface of the YSZ tube 72 and a gas electrode 78 is deposited on its
outer surface. A difference in partial pressure of oxygen between the inside and the
outside of the YSZ tube 72 gives rise to an EMF which is measured at 64 and displayed
for monitoring purposes at 48. As long as the pilot burner 16 is alight the proportion
of oxygen in the sample A flowing through the conduit 24 is substantially less than
that in the air C flowing through the YSZ tube 72 and the EMF stays substantially
constant. If the pilot burner 16 is extinguished, there is a change in EMF and this
provides a signal for automatic activation of the flame front generator 44.
[0042] Figure 5 illustrates the use of an electrochemical sensor 80 for detecting nitric
oxide (NO) or nitrogen dioxide (NO
2 or nitrous oxide (N
2O), all of which are indicators of combustion and are commonly known collectively
as NO
x. The sensor 80, which is shown greatly enlarged in Figure 5a, comprises a body 82
formed of solid YSZ electrolyte positioned in the wall of the conduit 24 adjoining
the aspirator 32. The YSZ body 82 is formed with an inner passage 84 inside the conduit
24 and communicating with the aspirator 32 so that sample A passes therethrough. The
body 80 is formed with an outer passage 86 outside the conduit 24 and open to the
air surrounding the conduit 24. The inner passage 84 contains a measuring electrode
88 and pumping electrodes 90 and the outer passage 86 contains a reference electrode
92 and pumping electrodes 94. A heating element 96 is embedded in the body 82.
[0043] Devices like the sensor 80 are well known and do not need detailed description here.
Briefly, an oxygen pumping action is set up by energising the pumping electrodes,
so giving rise to an EMF related to the relative difference in partial pressure of
oxygen between the sample A in the inner passage 84 and the free air in the outer
passage 86. Beyond this, however, one of the pumping electrodes 90 in the inner passage
84 is coated with rhodium and this subjects NO
x in the inner passage 84 to a reducing action so that the EMF measured at 64 is related
to the concentration of NO
x in the conduit 24 and can thus provide a signal for activating the flame front generator
44.
[0044] It should be understood from the foregoing that the essence of the invention is automatic
provision of a signal at a remote location if a parameter of combustion is absent
at the burner location.
[0045] Tests indicate that the most effective parameter for monitoring the status of the
pilot burner 16 is the proportion of CO in the sample. However it should be understood
both that other parameters may be sensed and that, if the presence of CO is to be
tested, means other than an NDIR monitor may be used. Examples of sensors that might
be used in the invention include the C series CO sensor available from Alphasense
of Great Notley, UK, the TGS 4160 hybrid O
2 sensor unit available from Figaro Engineering Inc of Osaka, Japan and the Smart NO
x sensor available from Continental AG of Frankfurt, Germany. Notwithstanding these
available sensors and the details of sensing systems outlined above, those skilled
in the art should be well able to construct any of the sensing systems shown in Figures
2 to 5, or other systems able to detect products of combustion at a location remote
from the burner location of a flare stack.
[0046] Variations on the embodiments of the invention particularly described hereinbefore
will be apparent to those skilled in the art and in particular it is pointed out that,
although the flare stack described provides for automatic reignition it may simply
provide a signal to operatives for manual action.
1. A flare stack comprising a gas discharge duct (10) and a pilot burner (16) operative
at a burner location to ignite gas discharged by way of the duct (10), characterised in that said flare stack comprises: sampling means operative to sample gases at the burner
location and deliver a sample thereof to a monitoring location (20) remote from the
burner location; a sensor (30/50/70/80) at the monitoring location (20) responsive
to a parameter of the sample indicative of combustion at the burner location; and
a signalling device (38/64) operatively associated with the sensor (30/50/70/80) and
arranged to provide a signal automatically if the sensor (30/50/70/80) does not detect
said parameter in said sample.
2. A flare stack as claimed in Claim 1 characterised in that said flare stack includes an igniter (44) activated automatically in response to
said signal to relight the pilot burner (16).
3. A flare stack as claimed in Claim 1 or Claim 2 characterised in that said parameter is the proportion of a selected constituent of the sample and said
signal is provided automatically if the sensor (30/50/70/80) detects that said proportion
differs from a predetermined reference value therefor.
4. A flare stack as claimed in Claim 3 characterised in that the reference value is an average from measurement of said proportion over time and
said signal is provided automatically if the sensor (30/50/70/80) detects a change
from the average.
5. A flare stack as claimed in Claim 3 characterised in that the reference value is a predicted value for said proportion.
6. A flare stack as claimed in Claim 5 characterised in that the reference value is the predicted proportion of oxygen and/or carbon monoxide
and/or carbon dioxide and/or oxides of nitrogen in the sample.
7. A flare stack as claimed in any preceding claim characterised in that the sensor comprises an electrochemical cell (50/70/80) or a non-dispersive infrared
(NDIR) sensor (30).
8. A flare stack as claimed in any preceding Claim characterised in that the sampling means comprises a conduit (24) extending from the burner location to
the monitoring location (20) and an aspirator (32) operative to draw the sample through
the conduit (24) from the burner location to the monitoring location (20).
9. A flare stack as claimed in Claim 8 characterised in that the aspirator (32) operates substantially continuously.
10. A flare stack as claimed in Claim 8 characterised in that the aspirator (32) operates periodically.
11. A flare stack as claimed in any of Claims 2 to 10 characterised in that said flare stack includes at the burner location a flame sensor (17) operatively
associated with the pilot burner (16) and arranged to ignite the pilot burner (16)
automatically if the flame sensor (17) does not detect a flame.
12. A flare stack as claimed in any preceding claim characterised in that said flare stack includes a display (48) at the monitoring location, which display
(48) is operatively associated with the or each sensor (30/50/70/80) and arranged
to indicate the status of the pilot burner (16).
13. A method of disposing of unwanted gas released from oil or gas production facilities,
wherein the unwanted gas is discharged by way of a duct (10) and ignited by a pilot
burner (16) at a burner location, characterised in that said method comprises: sampling gases at the burner location; delivering the sample
to a monitoring location (20) remote from the burner location; testing the sample
at the monitoring location (20) to detect a parameter indicative of combustion at
the burner location; and providing a signal automatically if said parameter is not
detected in the sample.
14. A method of disposing of unwanted gases as claimed in Claim 13 characterised in that said method comprises reigniting the pilot burner (16) automatically in response
to said signal.
15. A method of disposing of unwanted gases as claimed in Claim 13 or Claim 14 characterised in that said parameter is the proportion of oxygen and/or carbon monoxide and/or carbon dioxide
and/or oxides of nitrogen in the sample and the test measures such proportion against
a predetermined reference value for the parameter.
16. A method of disposing of unwanted gases as claimed in Claim 15 characterised in that the reference value is a time-averaged empirical value for the sample.
17. A method of disposing of unwanted gases as claimed in Claim 15 characterised in that the reference value is a predicted value for the sample.