Introduction
[0001] The invention relates to smoke alarm devices.
[0002] For many years most smoke alarm devices were powered from 9 Volt circuits. Due to
the combined pressures for smaller physical size, greater reliability, extended longevity
and cost there has been a trend in recent years towards smoke alarms operating from
a single 3 Volt lithium cell which is capable of powering the device for over 10 years.
[0003] Using a single 3 Volt cell presents a number of challenges as the device must operate
satisfactorily from about 3.6 Volts down to about 2.2 Volts (this is the typical operating
range of low voltage microcontrollers).
Stable Smoke sensitivity over Voltage range
[0004] A challenge is keeping the smoke sensitivity reasonably constant over the battery
range. This implies keeping a constant current in the infra red diode (IRED) for measuring
the smoke in the sensing chamber. For example, with an IRED forward voltage of 1.6
Volts there is very little "head room" to control this current at the lower operating
voltage of 2.2 Volts.
Wide dynamic range for good stability and dust compensation
[0005] Another challenge with the known smoke sensing circuitry is having a wide dynamic
range as the circuit needs to be able to measure the voltage across the photodiode
for the various conditions such as the following:
|
Photodiode Voltage |
Standby (IRED photons reflected off black walls) |
0.5 mV |
With 0.1 dB/m smoke |
1.5 mV |
With 0.5 dB/m smoke/at hush level |
5.5 mV |
With smoke of 0.1 dB/m and high dust compensation |
9.5 mV |
[0006] In addition, there can be a wide spread in the brightness of the IREDs (i.e. photon
output per milliamp drive current) of typically +/- 50% from the above typical figures.
In this example, this means that the circuit must be able to measure from 0.25mV to
14.25mV - a range ratio of 57 (i.e. 14.25/0.25 = 57).
Temperature Stabilised Smoke Sensitivity
[0007] The circuit must also allow for variations in the IRED output with temperature. Typically
the IRED temperature coefficient is - 0.8% per degree C. Uncorrected, this can allow
for undesirable changes in smoke sensitivity over the operating temperature range
of say-10°C to 55°C.
Reduced sounder current spikes
[0008] The sounder must produce 85dB(A) at 3 metres according to a common standard. A typical
piezoelectric disc sounder requires over 15 Volts peak to peak to achieve this. Designers
commonly use a ringing choke (with step-up turns) approach. This will typically draw
peak currents of about 40mA. It is important to keep this as low as possible, so as
to minimise the load on the lithium cell and so reduce its output voltage drop as
it supplies this current, particularly at low temperatures such as 0°C. If the cell
voltage drops below 2.2 Volts, the devices can stop operating, reset, or in the worst
case latch up (for example if the microcontroller clock stops) with the horn and/or
LEDs on.
[0009] A key drawback of a ringing choke circuit is that it can draw a pulse of current
over twice the normal run current (i.e. about 90mA) on start up for about 1 millisec.
Contamination
[0010] A major problem with many known optical smoke alarms is that eventually many of them
become contaminated and go into continuous alarm as the whitish dust on the black
inside walls of the sensing chamber scatter the light in a similar fashion to smoke.
At present, these would have to be taken down and the power disconnected for them
to be silenced. This requires the user to get a step ladder or similar and this can
be a nuisance, particularly during the night and also dangerous for people such as
the elderly. Our prior European patent specification number
EP 1098284 describes an approach in which sensitivity is increased or decreased in response
to dust build-up or subsequent cleaning.
[0011] The invention is directed towards providing an improved smoke alarm device of the
optical type, in which some or all of the above problems are addressed.
Summary of the Invention
[0012] According to the invention, there is provided a smoke alarm device comprising:
an optical smoke sensor including a light emitting diode and a photo-detector mounted
in a chamber,
a circuit with a processor, a user interface, and a sound emitter, in which the processor
is adapted to cause the light emitter to be pulsed by a drive circuit, and
wherein the processor is adapted to enter a de-sensitized mode for at least a first
and a second period upon receipt of user commands, and the processor is adapted to
automatically perform dust compensation re-calibration in said second or a subsequent
de-sensitized period, wherein the re-calibration is implemented in a duration of less
than twenty minutes, wherein the processor directs emission of an indicator that the
device is de-sensitized while it is in the de-sensitized mode.
[0013] In one embodiment, the processor is adapted to cease alarming for a period in excess
of 4 hours if it performs dust compensation and also receives a hush instruction from
a user.
[0014] In one embodiment, the circuit includes a current source for the light emitter to
maintain a uniform current through said emitter, wherein said current source comprises
a light emitter control switch transistor in series with the light emitter, a resistor
connected between the light emitter switch and ground, a diode providing a voltage
reference for a base of a light emitter switch, and a control switch linked with the
base of the light emitter switch, and means in the processor for activating the control
switch.
[0015] In one embodiment, the circuit includes gain components for providing different gains
from the light detector, and the processor is adapted to choose an appropriate gain,
wherein the gain components include a plurality of inter-connected op-amps, in which
a capacitance across the gain-setting resistor of an op-amp provides attenuation of
high frequency noise and a capacitance in series between two op-amps provides filtering
of DC and low frequency noise caused by ambient light.
[0016] In one embodiment, the processor is adapted to dynamically choose a gain value according
to temperature-induced variations in light output of the light emitter.
[0017] In one embodiment, the gain stage components include four op-amps arranged to amplify
the detector output, in which a full gain is provided by the four stages and a lower
gain is provided by the first three stages, and in which the processor is adapted
to use the high gain until the photo-detector output signal is just below the supply
and to then switch over to the low gain to ensure that the lowest signal to be amplified
has an output from the high gain stages which is large enough to give an target signal
to noise ratio for both internally-generated noise and externally-generated noise.
[0018] In one embodiment, the circuit is adapted to compensate for a reduction of light
emitter photon output as temperature increases, in which the circuit comprises a first
clock having a low temperature variation but high power consumption, and a watchdog
timer which has a higher temperature variation but low power consumption, and the
processor is adapted to normally use the watchdog timer and to switch to use of the
first clock periodically to measure the period of the watchdog timer to deduce the
temperature from the change in this period.
[0019] In one embodiment, the sound emitter includes a piezoelectric membrane, and the processor
is adapted to interrupt a drive to the sound emitter at start-up, wherein the drive
is interrupted for a time duration of approximately the period of the piezo membrane.
[0020] In one embodiment, the processor is adapted to speed up a light emitter activation
rate in response to increased smoke detection.
[0021] In one embodiment, the processor is adapted to trigger a next shorter inter-activation
duration upon smoke level reaching successively higher thresholds until an alarm level
is reached.
[0022] In one embodiment, the processor is adapted to generate an output for identifying
the device from within a group of devices, in which the processor is adapted to turn
on a combination of a sound emitter and two flashing indicators to indicate a low
battery or fault, or a contaminated chamber, or if the device had been in alarm previously
in response to user pressing of a test button, wherein said time period is in the
range of 0.2 seconds to about 0.75 seconds between flashes.
[0023] In one embodiment, the processor is adapted to identify if the device is approaching
a low battery condition or a dust contaminated condition, and to generate an output
indicating this, in which the processor is adapted to generate said output if it is
projected that the condition will arise in a time period of 6 to 24 months, preferably
12 to 18 months.
[0024] In one embodiment, said output is generated in response to user pressing of a test
button.
[0025] In one embodiment, the processor is adapted to apply a more stringent battery test
to determine if the device is approaching a low battery condition.
[0026] In one embodiment, said test is performed only during a user interaction such as
at a button test, thus helping to avoid the problem of a premature indication caused
by low temperature.
Detailed Description of the Invention
[0027] The invention will be more clearly understood from the following description of some
embodiments thereof, given by way of example only with reference to the accompanying
drawings in which:-
Figs. 1 to 4 are diagrams illustrating a circuit of a smoke alarm device of the invention;
Fig. 5 is a plot of op-amp output vs. time illustrating response of the device to
various dust conditions; and
Fig. 6 is a table illustrating parameters for operation of the device.
[0028] Referring to Figs. 1 to 4 a circuit of a smoke alarm device of the invention comprises
a microcontroller U1 (Fig. 2), a smoke sensing chamber with a light emitting diode
IRED (Fig. 2) and a photo detector PD (Figl), a 3V lithium cell (Fig. 4), a piezoelectric
horn HORN (Fig. 4) and LED indicators LED 1 and LED 2 (Fig. 4).
[0029] Additionally:
Fig. 1 shows a gain control circuit U2 which is powered just as required by the collector
of the PNP transistor in QP1 to minimise battery drain.
Fig. 2 shows the processor U1 and a control circuit including transistors QP2 and
Q3 and various other components for driving the IRED in a uniform manner.
Fig. 3 shows interconnect circuitry, in which an interconnect terminal is sensed by
transistor QP7 for an incoming signal, and driven directly by the microcontroller
U1 to provide an outgoing signal.
Fig. 4 shows the 3V cell, drivers for indicating yellow and red LEDs YLW_LED and RED
LED/10_IN, and the horn HORN.
[0030] The main functions programmed into U1 are as follows.
- Driving the light emitter IRED to give a 100 microsecond pulse and measuring the associated
amplified signal from the photo diode PD.
- Turning on the horn to give an alarm or fault beeps.
- Turning on the two indicator red and yellow LEDs as appropriate.
- Measuring the battery voltage using the U3 (Fig. 2) precision voltage reference, while
loading the battery with a suitable pulse current through R31. U3 is drawn as a zener
diode because it behaves similarly to one, but it is not a signal diode, it is a band-gap
precision reference. As shown in Fig. 2 it is connected on the line driving the base
of Q3.
- Interfacing to the radio frequency module through the RF MODULE (Fig. 3) socket such
that when the device senses fire it signals to all the other devices to give an alarm,
and vice versa. It also allows remote testing and controlling of the alarm.
- Interconnect signalling to other smoke/heat alarm devices through the hard wire interconnect
option (IO+ and IO-) such that if one device senses smoke, all of the devices will
alarm.
[0031] Capacitors C1 and C2 as shown give attenuation of high frequency noise (C2) and also
filtering of DC and low frequency noise (C1 with resistor R9A) caused by high levels
of ambient light, for example from sunshine or 100 Hz light from fluorescent tubes
entering the optical chamber. Because C1 and the associated resistor R9A are connected
in series between two op-amps it filters the DC and low frequency noise, and because
C2 is connected across the gain setting resistor of another op-amp it is very effective
at filtering out high frequency noise.
[0032] As shown in Fig. 3 the device also includes an RF module for interconnecting to other
alarms and for user remote control.
[0033] A further feature of the invention is to give fast response to fires but at the same
time to keep the current drawn from the battery to a minimum. Pulsing the IRED with
the high current needed (typically 250 mA or higher) is a major part of the drain
on the battery.
[0034] The IRED is pulsed every 16 seconds. This would therefore be expected to have a response
time of between 3 and 19 seconds. The 19 seconds can be too long in some circumstances
and to overcome this, the IRED pulsing is speeded up as the smoke increases in the
chamber as follows. This ensures that during fire tests, in which the smoke builds
up in times of the order of less than 60 seconds, the device responds rapidly. This
can be very beneficial in a critical fire situation. It is also beneficial in comparison
fire tests between competitive smoke alarms.
Smoke Level IRED Pulse Rate |
dB/m |
Seconds |
0.0 |
16 |
0.025 |
8 |
0.050 |
2 |
0.075 |
1 |
0.100 |
1 (alarm level) |
[0035] The device addresses the problem of achieving stable smoke sensitivity over the voltage
range as follows.
[0036] The IC U2 is a quad operational amplifier (op-amp) and is used to amplify the low
level voltage signal from the photodiode PD (bottom right corner of Fig 1). There
are four op-amps as illustrated, the gain values of which are included in Fig. 1.
The op-amps step up the voltage from one to the other, conditioning the voltage for
U1, particularly for analogue-to-digital conversion. U2 provides two outputs as shown
in the top left corner of Fig. 1, namely O/P 1 and O/P 2. The gains for these two
outputs are 796 and 140.
[0037] The quad op-amp U2 amplifies the photodiode (PD) signal. The full gain of the four
stages is 796 and the lower gain of the first three stages is 140. The microcontroller
uses the high gain until the output signal is just below the supply. It then switches
over to the low gain. This ensures that the lowest signal to be amplified, typically
0.25mV, will have an output from the high gain stages of (796 x 0.25mV) = 0.199 Volts.
This signal is large enough to give an adequate signal to noise ratio for both internally
generated noise and externally generated noise. At the other extreme, the 14.25mV
when amplified by 140 gives a signal of 1.99 Volts which is below lowest supply voltage.
These gains allow the use of low cost 8-bit A-to-D conversion as the above voltages
give sufficient digital bits / resolution for the accuracy required for the calculations.
[0038] Referring to Fig. 2, the circuit addresses the problem of varying battery voltage
(3.6V down to 2.2V) causing differing light output from the IRED. The band gap precision
voltage reference U3, (Fig 2) provides a stable voltage level Vref of 1.22V at the
base of Q3. The capacitor C14 stores the battery voltage. The microcontroller U1,
using pin 3 turns on the PNP transistor in QP2 which in turn biases on the voltage
reference U3 which generates Vref (1.22 Volts) at the base of the IRED driver transistor
Q3. This is configured as a current source as the voltage on its emitter is V
ref - V
be = 0.52 Volts, and the resistor R25 sets the current (typically (0.52 / 1.8 = 288mA).
The current in the IRED will remain stable to V
dd = 2.2 Volts as long as the forward voltage across the IRED is less than 2.2 - 0.52
- 0.05 = 1.63 Volt.
[0039] Regarding the problem of temperature sensitivity, the circuit configuration has the
added benefit that is gives an inherent temperature compensation of close to - 0.8%
per degree C to overcome the reduction in the photon output of the IRED as the temperature
increases (and vice versa).
[0040] If this compensation needs to be increased, then the temperature can be deduced using
just the microcontroller without any additional components as follows. The internal
microcontroller circuit has two clocks. There is a 4MHz clock with a tolerance of
2% which has little temperature variation and draws 0.5mA. This is only turned on
as needed to minimize power utilisation and hence prolong battery life. The second
clock is a watchdog timer which draws less current and is sensitive to temperature
variation. The processor U1 is programmed to normally use the watchdog timer and to
switch to use of the first clock periodically to measure the period of the watchdog
timer to deduce the temperature from the change in this period. If extra temperature
compensation is needed, then the output voltage from the op-amps is multiplied by
an appropriate constant to allow for this, prior to further analysis of the smoke
chamber signal.
[0041] Regarding the problem of sounder current spikes, the problem with the large piezo
current pulse on start-up is solved by the microcontroller turning on the transistor
Q1 for about 300 microseconds (approximately the period of the piezo disc, which has
a nominal resonant frequency of 3000Hz). It then interrupts the drive to Q1 for about
150 microseconds and then turns the drive on continuously thereafter.
[0042] This has the effect of the piezo disc getting its oscillations going more quickly
and, importantly, producing a feedback signal which turns off Q2 in about 600 microseconds
(this is much less than the 1000 microseconds which it takes if Q1 is not pulsed as
described). This has the result that the current pulse on start-up is only about 10%
over the normal run current whereas without the pulse it is about twice the normal
run current.
[0043] Fig. 5 shows the very high level of dust compensation that the invention allows i.e.
it can tolerate 8 times the level of dust that would cause an uncompensated device
to give an alarm. On the other hand a dust compensation of just 2 or 3 are typical
of the present state of the prior art.
[0044] The following is the manner in which the device deals with the problems of nuisance
alarms from activity such as cooking and also from dust build-up in the optical chamber.
The user presses the test/hush button and the device is de-sensitised for 10 minutes.
If the smoke clears the device will not go back into alarm and the "problem" is solved.
However, if the device goes back into alarm, pressing the test/hush button (within
4 minutes) will again de-sensitise the device for 10 minutes, but now towards the
end of this second ten minutes, the device will "quickly" compensate for the contamination
in the chamber within a few minutes. In standby this normally takes hours, to ensure
it does not inadvertently compensate for a slowly developing fire.
[0045] If the smoke alarm does not go back into alarm, the dust compensation algorithm has
now fixed the problem and the issue is resolved.
[0046] However, if the device goes back into alarm for the third time (i.e. the device has
now been seeing an alarm condition for over (10 + 10 =) 20 minutes, the user presses
the hush/test button (within 4 minutes of it going back into alarm) for a third time.
Now the smoke alarm silences the horn for 8 hours, (provided the chamber continues
to sense an alarm condition). If the alarm condition clears (e.g. due to the chamber
being cleaned) for at least 5 minutes continuously (to ensure the alarm is not being
caused by "intermittent" contamination such as a fibre wafting in and out of the sensitive
part of the chamber) then the smoke alarm goes back to normal standby. During the
8 hours the device will give two short beeps (10 millisec long) about 0.5 seconds
apart every 10 minutes to gently remind the user that the device is not operational
and should be replaced. This also allows it to comply with the standard EN14604 alarm
silence facility clause that states "continuous operation of the alarm silence control
shall not lead to the smoke alarm being de-sensitised for more than 15 minutes without
an audible warning being given".
[0047] After the 8 hours the device will go back into its alarm and now pressing the test/hush
button (within 4 minutes) will silence it as in 3 above for a further 24 hours (with
2 beeps every 10 minutes). If the smoke chamber contamination is cleaned the device
will reset to normal sensitivity.
[0048] There has rightly been a great reluctance to allowing users to "permanently" disable
a smoke alarm. However the above does not allow the user to disable the horn, and
keep it disabled, unless the following stringent conditions are fulfilled:
- until it has been in alarm over 20 minutes
- the hush button has to be pressed three times, at 10 minute intervals
- the device will return to normal sensitivity if the "permanent" alarm condition clears
- there is an audible and visual warning of two beeps every 10 minutes to inform the
user the device is not capable of sensing smoke.
[0049] If a device has been in alarm for over 20 minutes and there is no smoke, the user
is going to silence it one way or the other (e.g. by pulling it off the ceiling and
possibly damaging both the ceiling and the device) - as by this stage the smoke alarm
is just giving a useless and very noisy nuisance alarm.
[0050] When a device is contaminated and in continuous alarm, it is essentially of no further
use to the resident as a smoke alarm. It is reasonable therefore to give the user
8 hour respite from the horn sounding by just pressing the button, in a defined sequence,
to prevent inadvertent use.
[0051] In a further embodiment the hush could be enabled by remotely using a hardwired switch
or by using a radiolink switch.
[0052] Some standards allow radio transmitting devices to automatically silence the horns
once the alarm has been given for at least 30 minutes. This is to preserve battery
life and is based on the premise that users will have taken appropriate action (e.g.
by evacuating the premises or by extinguishing the fire) well before the 30 minutes
of alarm has elapsed.
Simple Maintenance Diagnostic Tests
[0053] In recent times more and more smoke alarms are being tested/inspected and monitored
at least yearly by trained personnel (for example this is becoming mandatory in some
countries). At present many inspectors simply wipe the smoke alarm with a damp cloth,
to remove any external dust or cobwebs and press the test button. This tells the inspector
that the device is working at present, but does not give any indication of imminent
or intermittent problems such as build-up of contamination, of the battery nearing
depletion or of poor location.
[0054] A further problem is that if a device (in say a property with 10 alarms) is giving
beeps just once a minute it can be very tedious and time-consuming to locate it, and
indeed some inspectors in a hurry might replace all the devices rather than spend
the time to identify the problem device. Some manufacturers have test apparatus for
field engineers for testing devices after they have been removed from the ceiling.
This is effective but costly as the devices have to be removed from the ceiling and
special unique apparatus for each type of alarm is required.
[0055] The controller U1 is programmed to give the inspector, using simple indicators already
in the alarm, comprehensive data to allow them to quickly identify defective devices
and also devices that are likely to become defective prior to the next inspection
period (normally inspections are done annually). The main defects which need to be
identified are a partially contaminated device, devices where the battery voltage
is close to the low battery trip point and badly sited alarms giving nuisance alarms
due to being too close to a kitchen or bathroom.
[0056] Referring to Fig. 6 the inspector presses the test button and the information in
the trouble shooting diagnostics section giving the state of the alarm. This also
checks if the device is going to give low battery beeps or chamber beeps within about
12 to 18 months.
Indicators and their Uses
[0057] The device of the invention in various embodiments has a comprehensive set of indicators
(sounder, red LED and yellow LED) to help the user gain the maximum benefit from the
alarms with no, or minimal nuisance effects (such as horn beeps or LED flashes). These
are explained below as a set out in the user instructions.
Normal Operation
[0058] In normal operation, the device is silent and there are no LED flashes (which could
be intrusive in a dark bedroom at night). The user should press the test button weekly
to check the sensor, electronics and horn; and also to familiarise the occupants with
the sound of the alarms. The horn will start softly so as to reduce exposure to excessive
noise levels.
If a Fire Occurs
[0059] As soon as the device senses smoke it will go into alarm (along with any interconnected
alarms). The red LED on the devices sensing smoke flashes rapidly (every ½ second)
to indicate if it is the device sensing fire.
If a Nuisance Alarm Occurs
[0060] The user presses the large test button (e.g. with a broom handle) to silence the
device for 10 minutes - the red LED will then flash every 8 seconds for 10 minutes
while the smoke sensitivity is reduced.
If the Battery is Low
[0061] Normally the battery will last over 10 years before it becomes partially depleted.
When electronic self testing indicates that the battery is becoming low the device
will beep and the red LED will flash at the same time (about every 32 seconds) to
warn the user. This indicates that the device must be replaced. If it is not convenient
to replace the device immediately, then the user can press the test button to silence
the low battery beeps and stop the red LED flashing for 12 hours. This can be repeated
as required.
Contaminated Chamber False Alarm
[0062] If the device goes into alarm without any apparent smoke being present, press the
test button to silence the alarm for 10 minutes (as described above). If the device
goes back into alarm it may be contaminated. Pressing the test button again, within
4 minutes of the alarm going back into alarm, will get the device to compensate for
chamber contamination. This will normally resolve the problem.
[0063] If the device goes into alarm for a third time, the device is excessively contaminated
and must be replaced. If it is not convenient to replace it immediately, pressing
the test button within 4 minutes of it going into alarm (for the third time) will
silence the device for 12 hours - however it will give two short beeps (½ second apart)
every 10 minutes to remind the user it has been disabled. If the contamination clears
the device will return to normal operation.
[0064] This does not reduce the user's fire protection, as when a device is in continuous
alarm due to a fault, it is now useless and must be silenced - by taking the device
down or as described here. This procedure has the added benefits that the user is
reminded every 10 minutes by two short beeps that the alarm needs to be replaced and
that if the problem clears the device will return to detecting fire.
[0065] Pressing the test button after the 12 hours are up and the unit has gone back into
alarm, will silence it again for a further 12 hours.
If the Smoke Sensor becomes Defective
[0066] In the unlikely event of the smoke sensing chamber becoming defective, the device
will give a short beep with a yellow LED flash every 32 seconds. The device must then
be replaced. If it is not convenient to replace it immediately, pressing the test
button will silence the beeps and stop the yellow LED flashing for 12 hours. This
can be repeated as required.
How to identify which device has been in alarm (memory)
[0067] Sometimes a device may alarm for a short period (e.g. due to a small puff of cooking
fumes or vapour from a bathroom). While the horn is sounding the red LED will flashing
every ½ seconds. When the horn stops the red LED will give two short flashes (0.5
seconds apart) every 16 seconds for 24 hours. This can be particularly beneficial
in identifying a device that gave a short alarm during the night.
[0068] After the 24 hours has elapsed, a device that has been in alarm can still be identified.
When the test button is pressed, the horn will sound with rapid chirping (instead
of its normal sound). This can be invaluable to a maintenance person troubleshooting
a property some days, or even months later - as it can highlight that a particular
device should be moved further from a kitchen or bathroom or that a particular device
has an intermittent defect. This pressing of the test button also resets the two memory
features.
How to identify which device is giving fault beeps
[0069] If one smoke alarm is giving short beeps every 32 seconds and there are a number
of devices in the house, then the one giving the beeps can be quickly identified by
simply pressing the test button.
[0070] There are two possibilities when the button is pressed:
amber LED flashes every 0.5 seconds and horn sounds:
low battery, replace device,
amber LED flashes every 0.5 seconds but horn does not sound:
chamber defective, replace device.
How to Identify Heavily Contaminated Alarms
[0071] Press the test button and if the device is heavily contaminated the red and amber
LEDs will flash alternatively every half second - the horn will ramp up the sound
in the normal way. (This red / amber / red / amber indication on pressing the button
is also given when the device is likely to false alarm continuously within about 18
months, assuming the contamination continues build-up continues. It also gives this
indication if it already is giving a continuous false alarm but it has been silenced
for 12 hours as described in 5 above).
[0072] How to identify if a device should be replaced:
Check the "replace by date" on the sidewall.
[0073] Press the test button and check the horn ramps up to full sound and the red LED flashes
every 0.5 seconds. If this does not occur, replace the device.
[0074] When the test button is pressed the low battery voltage trip point is increased,
by the expected voltage drop over the following year (typically by 40 mV to 100 mV)
and if the battery voltage is less than this more severe requirement when the test
button is pressed, the horn will sound in the normal way but the yellow light will
flash rapidly to indicate the battery is likely to give low battery beeps within a
year. This allows the inspector to replace the alarm. The user will therefore not
be disturbed by beeps during the following year and also the service company will
not be called out to replace the device.
[0075] The following is a summary of advantages of the invention:
Suppression of contaminated chamber false alarms for 8 hours in a simple way - units
with clean (or cleaned chambers) cannot be de-sensitised for 8 hours.
[0076] Comprehensive diagnostics using just a red LED, a yellow LED, the sounder and the
test button to identify:
- which unit had been in alarm in previous 24 hours and/or since button was pressed,
- a unit giving low battery beeps or going to give low battery beeps in 12/18 months,
- a unit giving faulty chamber beeps, and
- a contaminated chamber unit that is likely to become fully contaminated in 12/18 months.
[0077] Faster response to fire as the smoke chamber sampling rate is increased as the smoke
builds up from every 16 seconds to 1 second - without significantly increasing current
drain on the battery.
[0078] Very high levels of dust compensation (up to 8 times the normal smoke sensitivity)
due to the wide dynamic range of the conditioning circuitry, with a just 2.2 volt
supply.
[0079] Smoke sensitivity constant over full battery voltage range from 3.6 to 2.2 Volts.
[0080] Horn start up pulse (inductive) significantly reduced by inducing the oscillator
to reach the resonant frequency more quickly.
[0081] Smoke sensitivity constant over the full temperature range of -10°C to + 55°C
[0082] It will be appreciated that the invention also provides a simple way of identifying
if a device is significantly contaminated and likely to go into continuous alarm within
12 to 18 months by pressing the test button. It also provides a simple way if identifying
if the device has been silenced for 12 hours due to a contamination nuisance alarm
by pressing the test button. A further advantageous aspect is flashing the LED and
the change in the horn sound on button test to find devices that have been in alarm.
[0083] The invention is not limited to the embodiments described but may be varied in construction
and detail.
1. A smoke alarm device comprising:
an optical smoke sensor including a light emitting diode (IRED) and a photo-detector
(PD) mounted in a chamber,
a circuit with a processor (U1), a user interface, and a sound emitter (HORN), in
which the processor is adapted to cause the light emitter (IRED) to be activated by
a drive circuit, and
wherein the processor (U1) is adapted to enter a de-sensitized mode for at least a
first and
a second period upon receipt of user commands, and the processor is adapted to automatically
perform dust compensation re-calibration in said second or a subsequent de-sensitized
period, wherein the re-calibration is implemented in a duration of less than twenty
minutes, wherein the processor directs emission of an indicator that the device is
de-sensitized while it is in the de-sensitized mode.
2. A smoke alarm device as claimed in claim 1, wherein the processor is adapted to cease
alarming for a period in excess of 4 hours if it performs dust compensation and also
receives a hush instruction from a user.
3. A smoke alarm device as claimed in claims 1 or 2, wherein the circuit includes a current
source for the light emitter to maintain a uniform current through said emitter, wherein
said current source comprises a light emitter control switch transistor (Q3) in series
with the light emitter, a resistor (R25) connected between the light emitter switch
(Q3) and ground, a diode (U3) providing a voltage reference for a base of a light
emitter switch (Q3), and a control switch (QP2) linked with the base of the light
emitter switch (Q3), and means in the processor (U1) for activating the control switch
(QP2).
4. A smoke alarm device as claimed in any preceding claim, wherein the circuit includes
gain components (U2) for providing different gains from the light detector, and the
processor is adapted to choose an appropriate gain, wherein the gain components include
a plurality of inter-connected op-amps, in which a capacitance (C2) across the gain-setting
resistor of an op-amp provides attenuation of high frequency noise (C2) and a capacitance
(C1) in series between two op-amps provides filtering of DC and low frequency noise
caused by ambient light.
5. A smoke alarm device as claimed in claims 3 or 4, wherein the processor is adapted
to dynamically choose a gain value according to temperature-induced variations in
light output of the light emitter.
6. A smoke alarm device as claimed in any of claims 3 to 5, wherein the gain stage components
(U2) include four op-amps arranged to amplify the detector output, in which a full
gain is provided by the four stages and a lower gain is provided by the first three
stages, and in which the processor (U1) is adapted to use the high gain until the
photo-detector output signal is just below the supply and to then switch over to the
low gain to ensure that the lowest signal to be amplified has an output from the high
gain stages which is large enough to give an target signal to noise ratio for both
internally-generated noise and externally-generated noise.
7. A smoke alarm device as claimed in any preceding claim, wherein the circuit is adapted
to compensate for a reduction of light emitter photon output as temperature increases,
in which the circuit comprises a first clock having a low temperature variation but
high power consumption, and a watchdog timer which has a higher temperature variation
but low power consumption, and the processor is adapted to normally use the watchdog
timer and to switch to use of the first clock periodically to measure the period of
the watchdog timer to deduce the temperature from the change in this period.
8. A smoke alarm device as claimed in any preceding claim, wherein the sound emitter
(HORN) includes a piezoelectric membrane, and the processor (U1) is adapted to interrupt
a drive to the sound emitter at start-up, wherein the drive is interrupted for a time
duration of approximately the period of the piezo membrane.
9. A smoke alarm device as claimed in any preceding claim, wherein the processor is adapted
to speed up a light emitter activation rate in response to increased smoke detection.
10. A smoke alarm device as claimed in claim 9, wherein the processor (U1) is adapted
to trigger a next shorter inter-activation duration upon smoke level reaching successively
higher thresholds until an alarm level is reached.
11. A smoke alarm device as claimed in any preceding claim, wherein the processor is adapted
to generate an output for identifying the device from within a group of devices, in
which the processor is adapted to turn on a combination of a sound emitter and two
flashing indicators to indicate a low battery or fault, or a contaminated chamber,
or if the device had been in alarm previously in response to user pressing of a test
button, wherein said time period is in the range of 0.2 seconds to about 0.75 seconds
between flashes.
12. A smoke alarm device as claimed in any preceding claim, wherein the processor (U1)
is adapted to identify if the device is approaching a low battery condition or a dust
contaminated condition, and to generate an output indicating this, in which the processor
is adapted to generate said output if it is projected that the condition will arise
in a time period of 6 to 24 months, preferably 12 to 18 months.
13. A smoke alarm device as claimed in claim 12, wherein said output is generated in response
to user pressing of a test button.
14. A smoke alarm device as claimed in claims 12 or 13, wherein the processor (U1) is
adapted to apply a more stringent battery test to determine if the device is approaching
a low battery condition.
15. A smoke alarm device as claimed in claim 14, wherein said test is performed only during
a user interaction such as a button test, thus helping to avoid a the problem of a
premature indication caused by low temperature.