Technical Field
[0001] The invention relates to the field of fire safety and fire technology. A new method
of fire ventilation function test and a device specifically arranged for carrying
out this method of verification test of the fire ventilation functionality are invented.
Background Art
[0002] Fire safety of large complexes such as manufacturing objects, industrial as well
as non-industrial halls, tunnels of motorway and road corridors, metro and other constructional
objects, is determined most of all theoretically by means of calculation during engineering
design of their construction, based on expert science and technology knowledge. Requirements
for structural design of objects, used materials, and means of fire ignition and propagation
prevention are specified in the project of fire safety of buildings. Means of detection
of possible fire, means of fire ventilation of the object, air-handling, escape routes
etc. are also specified. Device for heat and smoke removal, that is the fire ventilation,
is one of the basic fire safety devices. However, unfortunately the design does not
always take into consideration all real dangers, sometimes the design is not exactly
followed during the object realization, sometimes the prescribed quality or maintenance
of fire ventilation is not observed and in other cases, unexpected situations can
occur that are solved as late as during the construction work. For these reasons,
it is necessary to perform tests to verify functionality of fire ventilation before
commissioning and during operation.
[0003] Currently, tests to verify the functionality of fire ventilation in buildings as
well as in linear constructions are carried out by means of so-called performance
tests. During these tests, projected parameters of fire ventilation, especially the
speed and direction of air flow over the tested area in time, are verified by physical
measurement using anemometers. Besides measuring instruments, this method uses no
special testing equipment.
[0004] As another method of verifying the functionality of the fire ventilation system,
a method is used in which a generator of a real smoke like the true fume during a
fire is placed into the tested area, whereupon the movement and concentration of the
resulting smoke is monitored in the course of operation of the fire ventilation means.
Real smoke is usually obtained by combustion of gasoline and/or diesel fuel, solid
combustible materials, or other combustible materials that are known as usual materials
burning in fires. The advantage of this method is that it allows visualization, i.e.
recording that can be watched with the possibility of monitoring and reviewing the
flow of air masses with smoke fumes, and it also gives the possibility of measuring
the optical density of smoke and thus monitoring of the smoke stratification. Carrying
out of these visualization tests is very important because they allow quite reliable
assessment of potential threats to the lives of persons and give accurate values for
software and hardware modifications of fire ventilation. This method is mainly used
in tunnel constructions, where persons are most endangered by combustion products,
whether it is the case of transversal or longitudinal ventilation. A considerable
disadvantage of this method is generation of high temperature and creation of toxic
combustion products, which limit the possibility of taking measurements and making
required records and endanger the persons present. Carbon dioxide (CO
2), carbon monoxide (CO), and hydrogen cyanide (HCN) are generally known as the worst,
at higher concentrations lethal combustion products and all these substances are formed
also in the case of the mentioned method. Persons performing these tests and any other
persons have limited access and movement in these areas during the tests and must
be equipped with appropriate personal protective equipments such as fire suits, masks,
etc., which are increasing the price of the tests. Huge disadvantage of this method
is that the high temperatures accompanying combustion and/or aggressive combustion
products can cause destruction of building constructions and/or impair surface finishing
and technological equipment of objects, contained markings and signs, air conditioning
units, electronic systems, measuring and control elements, etc., which may represent
damages even in order of hundreds of thousands of Euros. This method uses simple tanks
or tubs filled entirely or partially with combustible matter as a device for generation
of smoke fumes.
[0005] A variant of the method described in the previous paragraph is the method prescribed
by the Austrian guideline RVS 09.02.31 for verifying the functionality of ventilation
in tunnel constructions. Hot smoke is produced by combustion of 5 litres of gasoline
or 20 litres of diesel fuel in a steel container on the area of 1 m
2, the passage of the hot smoke through the tested space is recorded on a video and
simultaneously the optical density of the smoke is measured at different heights.
During operation of contained air-handling equipment, the time of exchange of gases
and polluted air in dependence on the volume exchange of air masses and on the smoke
optical density is monitored and measured, and then evaluated. According to the results
of the test carried out in this way, the parameters of fire ventilation are then set
on the contained air-handling equipment and dispatchers are informed on the expected
behaviour of a real fire. From the point of view of heat output as well as smoke production,
this methodology does not give a true picture of a possible fire, especially because
of the failure to keep the required amount of smoke generated in m
3/s. In fact, 20 m
3/s of smoke is created during a fire of a passenger car, 50 m
3/s of smoke is generated during a fire of a medium-sized car, and 80 to 100 m
3/s of smoke is created during a fire of a truck. In addition to the failure to simulate
the amount of smoke corresponding to the real fire, this test also generates toxic
and aggressive gaseous combustion products that degrade the technological equipment
of the tunnel and constitute the need for repairs and replacements, and also imply
the need to clean the space of the tunnel, which, in addition to high costs, results
in the necessity of long-term shutdown of tunnels and complicates traffic and transportation.
[0006] Another method uses so-called cold smoke. Standard smoke cartridge is used as a source
for the monitored cloud, or only water vapour is used. The product of smoke cartridge
is a mixture of gases. Water vapour is also a gaseous phase only. In both cases, the
resulting cloud is based on just harmless gaseous substances and it is visible. The
advantage of this method is the absence of toxic fumes and the possibility of recording
and observation of movement of the developed cloud. However, it is impossible to achieve
the dynamics of behaviour of a real smoke during a fire in terms of stratification,
or even approximate to it, mainly because of the absence of thermal dynamics of solid
particles, whose presence would make it possible to measure optical density in a way
comparable with the smoke in a real fire. Consequence of this fact is the inability
to fully evaluate correct functioning of fire ventilation.
Disclosure of Invention:
[0007] The above-mentioned disadvantages are eliminated to a considerable extent by the
invention. A new method of fire ventilation function test is invented, according to
which a generator of non-toxic aerosol simulating combustion smoke products is placed
into the tested space and the generator is equipped with a predetermined number of
compositions, these compositions are activated and then propagation of the generated
non-toxic aerosol is monitored, while a video is recorded and measurements of values
necessary for evaluation of functionality of fire ventilation in the given space are
performed, and finally the observed measurements are compared with values of a real
smoke, for instance the smoke produced during combustion of gasoline and diesel fuel,
measured in a test space. Functionality of fire ventilation of the tested space is
evaluated on the basis of observed results and these findings are used for setting
detectors of electric fire signalization, control units of tested air-handling devices
and devices for heat and smoke removal, for retrofitting as the case may be, construction
adjustments, etc.
[0008] Preferably a non-toxic aerosol is generated in the generator and the aerosol formed
at the temperature of 600 to 1300° C consists of a mixture of solid and gaseous phases,
of which the solid phase consists of particles with a particle size of 1 to 5 µm based
on potassium carbonate, potassium hydrogen carbonate and carbon, and the gaseous phase
is a medium based on carbon dioxide, water vapours, nitrous gases, nitrogen and ammonia.
This aerosol has extinguishing effects. It is non-toxic, considering contents of possible
toxic admixtures below the limit values given by standards, and with its stratification,
density, mobility and appearance, it is visually as well as regarding measurable values
comparable with real properties of smoke formed by combustion of gasoline, diesel
fuel, and solid substances of the type of usual materials causing fires such as wood,
paper, plastics etc. High temperature of the aerosol formation allows performing temperature
measurements at the site of the simulated fire. The high temperature is created only
at the site of the generator where it simulates the process of real fire, whereupon
in the course of the aerosol movement across the ventilation systems it has no longer
the destructive value and it does not devastate technological or structural equipment
of the object. Stratification of the aerosol cloud, the way and process of its waft
across the tested space as well as the optical density values correspond to the values
of the real fire smoke.
[0009] Non-toxic aerosol is preferably generated in quantity fully corresponding to the
production of real smoke during fire, i.e. 3 to 100 m
3/s, while the specific generated quantity for individual verification test is determined
in advance within the mentioned range. This is done particularly in dependence on
projected parameters of the fire ventilation for the tested space, for instance at
the level of the highest values permitted by the project or at the level close to
these values.
[0010] Preferably all the values mentioned below are monitored in the course of the test.
These are the speed of the aerosol cloud movement measured by means of monitoring
the flow of air including the contained aerosol, the temperature in the area of the
aerosol generator and in the space, and stratification and dispersal of the aerosol
cloud by means of measurement of optical density of the aerosol. Preferably at the
same time, video is also recorded that indicates the direction and flow of aerosol
particles in dependence on functioning of the fire ventilation and also the time of
exchange of gases and polluted air in dependence on the volume exchange of air masses
and on the aerosol optical density is measured.
[0011] Preferably the aerosol optical density is determined in the tested space during the
test by means of video recording and/or by measurements at different distances from
activation of compositions and in different heights. These measurements at different
distances and at different height levels allow monitoring the movement and dispersal
of the generated aerosol cloud.
[0012] If the tested space is equipped with air-handling equipment, it is purposeful to
put into operation all or, according to the aim of the test, some of the air-handling
equipment of the tested space in the course of the aerosol generation and monitoring
of the aerosol propagation. The method is intended especially for verification whether
the tested space is equipped with sufficient air-handling devices for smoke and heat
removal, and for testing the quality of functionality of these devices in the given
spaces. However, alternatively it is not excluded to use it to test even spaces that
are lacking air-handling devices for the time being, which is eligible for instance
in the case of older constructional objects and in objects with natural ventilation.
[0013] Preferably, the generator of non-toxic aerosol is still before activation of the
contained composition placed on at least one carrier mounted on or behind a vehicle,
and that in such position and so open to the surrounding space that the generated
aerosol can freely propagate to the surrounding space. This propagation has usually
a shape of a cloud that is moving in the tested space and diffuses here or is removed
with the help of the tested air-handling devices and/or natural ventilation. After
the dose of compositions is transported to the site of activation, one-shot or sequential
activation is performed by firing the compositions. Activation can take place statically,
i.e. with leaving the source of aerosol immovable at the site of the composition activation
until diffusion or removal of the aerosol cloud. Preferably, in particular for tests
in tunnels and other long corridors, the vehicle can move inside the tested space,
for instance by driving across the tested space during and/or after activation of
the composition, while a mobile video device such as another vehicle with a video
camera is moving in the area of the edge of the generated aerosol cloud and recording
a video enabling to visualize the course of the test. This variant of carrying out
the method is ideal for testing of railway tunnels or road tunnels.
[0014] The invention solves also design of the device suitable for carrying out the invented
method of the fire ventilation function test according to the invention. The device
includes a generator containing vessels of non-inflammable solid material, e.g. steel,
with inner cavity that are at least partially filled with combustible composition.
The essence of the new solution is that the compositions in the vessels are creating
the source of non-toxic aerosol imitating with its appearance, optical density, stratification,
and the manner of movement authentically the combustion products, i.e. the aerosol
consisting of solid particles with the particle size of 1 to 5 µm and non-toxic gaseous
substances. No cooler is contained; the vessel contains only a firing device in addition
to the composition, and only a free space is in vessels above the composition with
the firing device. To produce sufficient amount of the smoke imitation for the purpose
of the method, these vessels are in the number of 4 to 10 pieces placed in at least
one storage device of non-inflammable solid material such as steel, and here equipped
with a common perforated cover.
[0015] The storage device for the vessels is preferably in a shape of a stand with its upper
part created as a bed for the vessels and under this bed, a base with at least one
inner cavity for necessary electric elements of the firing device is located.
[0016] The bed is preferably equipped with at least one opening and the inner cavity of
the base is through, connected to this opening, while the base is equipped with at
least one element stabilizing its position relative to the support. For example a
support plate with holes and fixing bolts or rivets created at the bottom, or welded
strips of material, an extended and bent wall of the base leg, welded profile, etc.
can be used as the element stabilizing the position of the stand to the support.
[0017] The stand in the number of one or more is preferably placed in a tub of non-inflammable
solid material such as steel, where this tub contains at least a bottom and all-circumferential
rim, while the stand is firmly, immovably fixed to the bottom of this tub. The tub
creates bearing basis for the stands occupied or only some of them occupied with the
vessels, it allows transport of compositions to the site of use and transport during
use, as the case may be, and it can serve for possible supplementary flammable charge
such as ethanol in case the client requires increasing of the fire effect. Part of
the rim on one side can be extended and used for fixing the tub with stands and compositions
to the site of use, for instance to the carrier, as shown hereinafter in the example
of embodiment.
[0018] The tub preferably contains one to twenty stands, while at least some of the contained
stands have full bed filled with the vessels. The perforated cover mentioned above
in the first paragraph of the device description can be in a configuration with dimensions
for covering all contained stands together or for covering of each one of contained
stands separately or as the case may be for covering groups of stands. The stands
are preferably covered with the perforated cover separately one by one, which saves
material in the case of incomplete occupation of the tub with the stands and facilitates
manipulations connected with mounting of individual elements of the device into the
whole unit.
[0019] Preferably to allow carrying out the method in tunnels in particular, the tub is
placed on a bearing structure of a movable device, for instance of a vehicle, freely
open to the surrounding space at least in the area of the cover. Thus the tub with
stands and compositions can be preferably fixed for instance on a trailer behind a
car or on a special carrier directly on the car. In contrast to existing methods,
the device created and arranged in this way can be operated without any danger by
a driver present in the tested space.
[0020] The composition preferably consists of a material from which in case of firing the
composition the non-toxic aerosol is generated, solid particles of which contain a
mixture of potassium carbonate, potassium hydrogen carbonate and carbon, and the gaseous
phase of which contains a mixture of carbon dioxide, water vapours, nitrous gases,
nitrogen, and ammonia. This material is known already and available on the market,
but it is manufactured and used up to now for completely different purpose, i.e. as
an extinguishing mixture.
[0021] The designed technical solution according to the invention has the advantages in
that it simulates the real smoke that is produced during a fire, but it is non-toxic
and does not cause destruction or damage to the instrumentation and other equipment
in the object due to high heat. Simulation of the real smoke from combustion of substances
that are frequently the usual cause of the fire, i.e. gasoline, diesel fuel, paper,
wood, solid fuels, plastics, etc. is perfect especially regarding the optical features.
The aerosol cloud is generated that has the appearance for human eye and even for
detecting device identical to the smoke during a fire, and that has also identical
stratification with respect to the particle density, cloud shape, the way of movement
of the cloud as well as the way and speed of diffusion. The said values can be visualised
by means of video recording, with the possibility of subsequent and repeated reviewing
and with the possibility to measure the values such as optical density in various
places and heights etc. The figures of toxic admixtures present are below the toxicity
levels stated by the standards, and thus this aerosol can be considered to be non-toxic.
Because of the fact that the aerosol cloud is non-toxic and it is even dispersed in
the tested space and removed from the tested space by air-handling system during the
test, it is possible to perform firing of the composition on a static or moving vehicle
with a driver without the risk of persons' health hazard and it is possible to perform
in an ideal way a video recording during the test, for instance from a vehicle moving
behind the vehicle with the composition. With the help of the invented method and
device, it is possible to perform high quality and safe testing of functionality of
fire ventilation without the need of subsequent replacing of these devices or other
equipment of the tested area, and also without the need for demanding cleaning of
these devices and tested space, i.e. without the necessity of high costs and of long-term
shutdown of the tested space. The method and device according to the invention allow
finding in an optimal way the values to which the particular fire ventilation has
to be set. It further allows making dispatchers familiar with a real fire, i.e. with
probable direction of the fire propagation according to the place of origin and with
its course. From the point of view of toxicity of substances, the concentration of
toxic admixtures ranges in values in order of 100 to 600 times lower than the prescribed
permissible exposure limits. It is possible to generate imitation of smoke according
to the required output, in exactly preset value within the interval of 3 to 100 m
3/s. Activation of the aerosol formation can be performed manually or remotely using
electric pulse. The method and the device are suitable for utilisation for any tested
spaces, in particular road and railroad tunnels, large structural complexes, industrial
and other halls, technological workshops, etc.
Review of Figures on Drawings
[0022] The invention is illustrated using drawings, where Fig. 1 shows perspective view
of an example of the device for the fire ventilation function test according to the
invention, Fig. 2 shows top plan view into the individual vessel with the composition,
Fig. 3 shows front view of the vessel when section is drawn along the line A-A indicated
on the previous figure, Fig. 4 shows perspective view of individual stand, Fig. 5
shows front view of vertical longitudinal section drawn across the stand filled with
the vessels, through the centre of the vessels, Fig. 6 shows perspective view of the
tub filled with empty stands, Fig. 7 shows perspective view of the individual tub,
Fig. 8 shows illustration of function of the invented device and of carrying out the
method during the fire ventilation function test in a room equipped with air-handling
device with a fan, Fig. 9 shows illustration of function of the invented device and
of carrying out the method during the fire ventilation function test in a room with
natural ventilation by means of an air shaft, Fig. 10A, B, C shows illustration of
function of the invented device and three demonstrative variants of carrying out the
method during the fire ventilation function test in a tunnel using static compositions,
and Fig. 11A, B, C shows illustration of function of the invented device and three
demonstrative variants of carrying out the method during the fire ventilation function
test in a tunnel using mobile compositions.
Example of Embodiment of Invention
[0023] Example of the best embodiment of the invention is the device for carrying out the
method of the fire ventilation function test with illustrations of its use and process
during carrying out the method according to Figs. 1 to 11.
[0024] The core of the device for carrying out the method of the fire ventilation function
test is the generator shown on Fig. 1. The generator contains the source of non-toxic
aerosol simulating smoke fumes created during a fire, which creates the charge in
vessels
1 of non-inflammable solid material. In this example of embodiment, vessels
1 of practical cylindrical shape has been chosen, which are made of steel and thus
are having sufficient strength and mechanical durability. The inner cavity of the
vessels
1 is only partially filed with the charge, this charge is as the aerosol source the
flammable composition
2. Besides the composition
2, each vessel
1 placed in the generator contains only the firing device
3 with necessary electric accessories allowing firing, including electric conductors
4 in the case of wire firing. Only a free space is inside the vessels
1 above the composition
2 with the firing device
3, no cooler is contained, presence of which is considered to be essential in case
of existing devices. Arrangement of
1 is clearly visible on Figs. 2 and 3. As shown on Fig.1, the vessels
1 are in the number of 4 to 10 pieces placed in storage devices in the shape of stands
made of non-inflammable solid material. In this example of embodiment, preferred chosen
number of vessels
1 is six pieces per each stand, which is within the abovementioned range. The stands
for this example of embodiment has been made of steel, however, also other suitable
material can be used that ensures sufficient strength and mechanical durability for
the stands.
[0025] Arrangement of stands and their occupation is clearly visible on Figs. 4 and 5. The
upper part is created by the bed
5 for placing the vessels
1, and it has a shape of a box with a cut-out in the centre. Under this bed
5, the base
6 is located and in this case it is arranged as a leg, but it can have also different
suitable shape in other case. The base
6 is hollow; its inner cavity has dimensions and shape allowing placing of necessary
accompanying electric elements and the firing device, electric conductors
4 in particular. The cut-out in the centre of the bed
5 is arranged as an admission opening
7 into the cavity of the base
6, which is through and connected to the opening
7. The base
6 is equipped with at least one element stabilizing its position to the support, in
this case it is a support plate
8 created at the bottom. Each stand is equipped with a bolt-on perforated cover
9 covering the vessels
1 and preventing their unwanted loosening during transport to the site of use and during
the aerosol generation and preventing also unwanted premature damage to the firing
device
3 and possibly contained conductors
4. Perforation of the cover
9 creates openings for escape of generated aerosol from vessels
1 into space and for creation of the aerosol cloud. The vessels
1 can be placed in the bed
5 of the stand together with the boxes
10, in which they are supplied, or possibly such boxes
10 filled with vessels
1 containing the composition
2 can be prepared in advance separately and their presence facilitates manipulation
during counting charges, filling of stands, and also clean-up of used vessels
1 and a trash left over later after completion of tests.
[0026] The stands in the number of one to twenty are placed in a tub
11 of non-inflammable sufficiently strong material. In this example of embodiment, the
tub
11 is made of steel. The tub
11 has a bottom
12, to which all contained stands are firmly and immovably fixed using common means
of connection such as screws, bolts, rivets, or welding joints. A peripheral rim
13 projecting upwards is created around the bottom
12 of the tub
11 to prevent falling out of possibly broken off pieces of material and allowing placing
of supplementary charge such as ethanol etc. on the client's request to increase the
fire effect for instance. If the wire firing device
3 is used, the tub
11 can have created openings
7 for electric conductors
4, where these openings
7 are arranged so that they are linked adequately to the cavities of bases
6 and openings
7 of beds
5 of the stands. Even several tubs
11 with stands can be used for one test, according to calculated necessary dose of compositions
2. As far as the number of vessels
1 in individual stands is concerned, it is of course significantly more economic to
fill preferentially full beds
5 with the vessels
1, with possible gathering of calculated remaining number of vessels
1 gathered into one stand, with a higher number of unused stands, rather than evenly
but incompletely occupy unnecessarily high number of stands and to provide them with
perforated covers
9.
[0027] The tub
11 can be in the number of one or more fixed on a bearing structure
14 of a movable device, for instance on a vehicle, and that in such position and place
on the vehicle selected so that at least the area of each contained cover
9 shall remain freely open to the surrounding space for all the time of the test, which
is necessary to prevent occurrence of any barrier to creation of cloud from the generated
aerosol. The optimal placement is using a special bearing structure
14 custom made for this purpose and mounted at the rear side of a car, however any other
suitable carrying means can be possibly chosen such as roof baggage rack on the vehicle,
trailer, bowl etc. Angular circumferential shape of the tub
11 and other elements mentioned above is not a requirement.
[0028] The composition
2 consists of a material generating in case of firing a non-toxic aerosol, solid particles
of which contain a mixture of potassium carbonate (K
2CO
3), potassium hydrogen carbonate (KHCO
3) and carbon (C), and the gaseous phase of which contains a mixture of carbon dioxide
(CO
2) water vapours (H
2O), nitrous gases (NO
x), nitrogen (N
2), and ammonia (NH
4). For instance mixture of the following composition suits well as this material:
Substance |
% by weight in the mixture |
Potassium perchlorate (KClO4) |
20 to 26 |
Potassium nitrate (KNO3) |
50 to 60 |
Binding component, epoxy resin |
19 to 23 |
Binding component, hardener |
0.8 to 1.2 |
[0029] The abovementioned quantities and types of substances imply materials available on
the market, i.e. of technical purity of approximately 99%, so that besides the listed
substances, also a small amount of admixtures can be contained. Aerosol generated
by firing this mixture can be characterised as unhealthy up to harmful, however this
harmfulness does not reach such a degree that it could be considered as toxic.
[0030] The device is designed for the new method of the fire ventilation function test according
to the invention. Example performance of tests according to this method is described
hereinafter. Function of the device and carrying out of the method are shown on Figs.
8 to 11.
[0031] Preparation for performance of the method includes at least examination of the project
documentation of the tested space, ascertainment of the type, number, and location
of air-handling devices and devices for smoke and heat removal, and of other devices
in the tested space, finding of elements of natural ventilation, determination of
shape, dimensions, and materials in the tested premises and identification of projected
parameters of the fire ventilation. Further on, this preparation includes distribution
of corresponding sensors and gauges in the tested space, including possible video
cameras
15 unless they were already installed sooner. The device according to the invention
equipped with calculated necessary number of vessels
1 with composition
2 is prepared in advance. The generator of non-toxic aerosol simulating combustion
smoke products is placed into the tested space, its compositions
2 are activated and then propagation of the generated aerosol is monitored, while a
video is recorded and measurements of values necessary for evaluation of functionality
of fire ventilation in the given space are performed, and finally the observed measurements
are compared with values of a real smoke, for instance the smoke formed during combustion
of gasoline and diesel fuel, measured in a test space. On the basis of the found results,
evaluation of functionality of the fire ventilation of the tested space is performed.
Modern scientific and technical equipment including data control and evaluation systems
are used as far as possible for measurements and evaluation.
[0032] When fired, the non-toxic aerosol is generated in the generator at the temperature
of 600 to 1300° C, while the specific temperature values from the given range depend
in particular on the quantity of material in the compositions
2, on the specific composition of the compositions
2, on the presence and quantity of oxidizers and, as the case may be, on the presence
of supplementary ignited media increasing temperature such as ethanol poured in the
tub
5. The aerosol generated from the compositions
2 forms an aerosol cloud consisting of a mixture of solid and gaseous phases, of which
the solid phase consists of particles with a particle size of 1 to 5 µm based on potassium
carbonate, potassium hydrogen carbonate and carbon, and the gaseous phase is created
by a mixture of substances in a gaseous state containing carbon dioxide, water vapours,
nitrous gases, nitrogen, and ammonia and/or compounds of these substances. Dose of
compositions
2 is calculated so that the non-toxic aerosol is generated in quantity of 3 to 100
m
3/s, while the specific generated quantity of aerosol for individual verification test
is determined within the given range in advance depending on the client's request,
as far as possible in dependence on projected parameters of the fire ventilation for
the tested space, for instance at the level identical or close to the upper threshold
of the highest values permitted by the project. In the course of the test, the flow
speed of the air containing aerosol, the temperature in the area of the aerosol generator
and in the space, optical density of the aerosol, and possibly other measurable values
in the tested space and, as the case may be, also at inputs and outputs of air-handling
devices are monitored. Significant contribution of the invention is among others the
possibility to record video indicating the direction and flow of the aerosol particles
in dependence on functioning of the fire ventilation right in the area of the edge
of the aerosol cloud. Also the time of exchange of gases and polluted air in dependence
on the volume exchange of air masses and on the aerosol optical density is measured.
Because the aerosol cloud has properties with respect to optical density, movement,
and diffusion comparable with the real smoke from a fire, also the aerosol optical
density at different height levels is determined in the tested space during the test
by means of video recording and/or by measurements at different heights. The video
recorded then allows for visualisation of the course of the test utilisable for evaluation
of the test results as well as for demonstrative purposes such as exhibition at training
courses, for practical instruction exercise of fire-fighters etc.
[0033] If air-handling devices are contained in the tested space, they are preferably operating
in the course of the aerosol generation and monitoring of the aerosol propagation.
The method is solved completely for purposes of tests of ventilation of tunnels and
other corridors in the following way for tunnels, halls, and similar tested spaces
of large dimensions, the generator of non-toxic aerosol is still before activation
of the contained compositions
2 placed on at least one carrier mounted on or behind a vehicle, and that in such position
and so open to the surrounding space that the generated aerosol can freely propagate
to the surrounding space. The vehicle with the composition
2 is transported to the site of activation of compositions
2 and then, during activation and/or after activation of compositions
2 by their firing, the vehicle moves in the tested space. Visible aerosol cloud is
generated from activated compositions
2, which propagates in the tested space in a way similar to a smoke from a real fire
during combustion of gasoline, diesel fuel, etc. The area of the edge of the aerosol
cloud is monitored for all the time of the test, i.e. at least for the time of movement
of the cloud in the tested space. This monitoring can be ensured by a mobile video
device such as a video camera
15 located on a separate vehicle, by means of which a video recording enabling to visualize
the course of the test is continuously recorded.
[0034] The abovementioned method according to the invention and functioning of the device
according to the invention designed for this method is clearly illustrated on Figures
8 and 9 in the case of statically placed generator, from which Fig. 8 demonstrates
generation and propagation of the aerosol cloud in a room ventilated with the air-handling
device with a pipe system and Fig. 9 in a room only with natural ventilation by means
of an air shaft. The line on these figures marks so called safe line h, which is the
height limit showing the height in a direction from the room floor, up to which breathing
is still safe for persons in the area during fire in the case of utilisation or operation
of the present means of fire ventilation. Here, arrows indicate natural inflow of
air through structural holes.
[0035] Fig. 10 shows carrying out of the fire ventilation function test in a tunnel using
the generator placed on the bearing structure
14 mounted on a vehicle that is standing during performance of the test. In the case
A, the vehicle with the generator is standing in the central part of the tested tunnel;
in the case B, it is standing in the area at the beginning of the tunnel; in the case
C, it is standing in the area at the end of the tunnel. In all cases A, B, C, two
additional vehicles are used for monitoring, each with the video camera
15, which are standing near the edge of the aerosol cloud and are driving further back
and forth depending on how the aerosol cloud propagates at the beginning and finally
wanes through ventilation. The invention enables persons to operate these vehicles
as well as the video camera
15 without the risk to the persons' life and health hazard. At that, none of the vehicles
in the tunnel area are exposed to danger of fire too.
[0036] Fig. 11 shows carrying out of the fire ventilation function test in a tunnel using
the generators placed on the bearing structures
14 mounted on vehicles that are moving during performance of the test. In the case A,
the compositions
2 of the generators are activated in the area of the central part of the tested tunnel,
after which the vehicles drive away spreading the aerosol cloud towards the end of
the tunnel. In the case B, the compositions
2 of the generators are activated already in the area of the beginning of the tested
tunnel, after which the vehicles drive away spreading the aerosol cloud towards the
end of the tunnel. In the case C, the compositions
2 of the generators are activated in the area of the end of the tested tunnel, after
which the vehicles drive away spreading the aerosol cloud towards the beginning of
the tunnel. In all cases A, B, C, one or two additional vehicles with the video camera
15 can be used for monitoring and shooting of video-recording, in a way similar to the
case described with Fig. 10.
[0037] The abovementioned variants of the solution according to the invention are demonstrating,
and not limiting. Therefore still various other combinations of the embodiment of
the device as well as of the method within the frame of conditions according to the
invention are possible.
1. Method of the fire ventilation function test, characterized by that a generator of non-toxic aerosol simulating combustion smoke products is placed into
the tested space while the generator is equipped with a predetermined number of compositions
(2), these compositions (2) are activated and then propagation of the generated aerosol
is monitored, while a video is recorded and measurements of values necessary for evaluation
of functionality of the fire ventilation in the given space are performed, and finally
the taken measurements are compared with values of a real smoke, for instance the
smoke produced during combustion of gasoline and diesel fuel, measured in a test space
and the functionality of the fire ventilation of the tested space is evaluated on
the basis of the observed results.
2. Method of the fire ventilation function test according to claim 1 characterized by that the non-toxic aerosol is generated in the generator at the temperature of 600 to
1300° C consisting of a mixture of solid and gaseous phases, of which the solid phase
consists of particles with a particle size of 1 to 5 µm based on potassium carbonate,
potassium hydrogen carbonate, and carbon, and the gaseous phase is a medium based
on carbon dioxide, water vapours, nitrous gases, nitrogen and ammonia.
3. Method of the fire ventilation function test according to claims 1 and 2 characterized by that the non-toxic aerosol is generated in quantity of 3 to 100 m3/s, while the particular generated quantity for individual verification test is determined
within the given range in advance depending on the projected parameters of the fire
ventilation for the tested space, for instance at the level of the highest values
permitted by the project.
4. Method of the fire ventilation function test according to claims 1 to 3 characterized by that in the course of the test, the flow speed of the air including the contained aerosol,
the temperature in the area of the aerosol generator and in the space, and optical
density of the aerosol are monitored, video is recorded of the direction and flow
of aerosol particles in dependence on functioning of the fire ventilation, and the
time of exchange of gases and polluted air in dependence on the volume exchange of
air masses and on the aerosol optical density is measured.
5. Method of the fire ventilation function test according to claims 1 to 4 characterized by that the aerosol optical density at different height levels is determined in the tested
space during the test by means of video recording and/or by measurements in different
heights.
6. Method of the fire ventilation function test according to claims 1 to 5 characterized by that the air-handling devices of the tested space are in operation in the course of the
aerosol generation and monitoring of the aerosol propagation in the tested space.
7. Method of the fire ventilation function test according to claims 1 to 6 characterized by that at least one generator of non-toxic aerosol is still before activation of the contained
composition (2) placed on a carrier mounted on or behind a vehicle, and this in such
position and so open to the surrounding space that the generated aerosol can freely
propagate to the surrounding space, after which the vehicle together with the composition
(2) is transported to the site of activation of the composition (2) and then, during
activation and/or after activation of the composition (2), the vehicle moves within
the tested space, for instance by driving across the tested space, and during this
time, the generated aerosol cloud simulating smoke propagates in the tested space,
while a mobile video device such as a video camera (15) located on another vehicle
is moving in the area of the edge of this cloud for all the time of the test and is
continuously recording a video record enabling to visualize the course of the test.
8. Device for carrying out the method of the fire ventilation function test according
to any of the claims 1 to 7 including the generator containing vessels (1) of non-inflammable
solid material, for instance steel, with inner cavity, that are at least partially
filled with combustible composition (2), characterized by that the compositions (2) in the vessels (1) constitute the source of non-toxic aerosol
imitating the combustion products, i.e. the aerosol consisting of solid particles
with the particle size of 1 to 5 µm and non-toxic gaseous substances, while the vessel
(1) contains only a firing device (3) in addition to the composition (2), and only
a free space is in vessels (1) above the composition with the firing device (3), and
while these vessels (1) are in the number of 4 to 10 pieces placed in at least one
storage device made of non-inflammable solid material such as steel, and are equipped
here with a common perforated cover (9).
9. Device for carrying out the method of the fire ventilation function test according
to claim 8 characterized by that the storage device for the vessels (1) is in a shape of a stand, the upper part of
which is created by a bed (5) for the vessels (1), and under this bed (5) a base (6)
with at least one inner cavity for necessary electric elements of the firing device
(3), for instance for conductors (4), is located.
10. Device for carrying out the method of the fire ventilation function test according
to claim 9 characterized by that the bed (5) is equipped with at least one opening (7) and the inner cavity of the
base (6) is through, connected to this opening (7), while the base (6) is equipped
with at least one element stabilizing its position relative to the support, for example
a support plate (8) created at the bottom.
11. Device for carrying out the method of the fire ventilation function test according
to claims 9 and 10 characterized by that the stand in the number of at least one is placed in a tub (11) made of non-inflammable
solid material such as steel, where this tub (11) contains at least a bottom (12)
and all-circumferential rim (13), while the stand is firmly, immovably fixed to the
bottom (12) of this tub (11).
12. Device for carrying out the method of the fire ventilation function test according
to claim 11 characterized by that the tub (11) contains one to twenty stands, while at least some of the contained
stands have the bed (5) fully filled with the vessels (1) covered with the perforated
cover (9).
13. Device for carrying out the method of the fire ventilation function test according
to claim 12 characterized by that the tub (11) is placed on a bearing structure (14) of a movable device, for instance
of a vehicle, freely open to the surrounding space at least in the area of the cover
(9).
14. Device for carrying out the method of the fire ventilation function test according
to any of the claims 8 to 13 characterized by that the composition (2) consists of a material generating in case of firing the composition
(2) the non-toxic aerosol, solid particles of which contain a mixture of potassium
carbonate, potassium hydrogen carbonate and carbon, and the gaseous phase of which
contains a mixture of carbon dioxide, water vapours, nitrous gases, nitrogen, and
ammonia.