[0001] The present invention relates to a hydraulic system, in particular a hydraulic system
used on working machines.
[0002] A typical working machine may include a hydraulic system having a hydraulic pump
and one or more hydraulically operated services (such as actuators) coupled to the
hydraulic pump. One or more control valves are used to control the supply of hydraulic
fluid from the hydraulic pump to the or each actuator. Thus, an operator may use a
control interface to control operation of the one or more control valves to cause
actuation of one or more of the actuators.
[0003] The actuators may be coupled to parts of the working machine. For example, the actuation
of an actuator may cause movement of a working arm of the working machine.
[0004] Known load sensing hydraulic systems aim to keep a constant flow for a given position
of a control valve, in particular for a given position of a spool of a directional
control spool valve. This is done by maintaining a constant pressure difference known
as (valve) margin pressure, across the orifice made by the spool.
[0005] The associated pump has a control valve that automatically keeps the pump pressure
and flow at a level needed to fulfil the system load and flow needs. When none of
the hydraulic circuits are being used the pump will be operating at a "stand by" pressure,
typically be somewhere the range 20-30 bar. When a hydraulic service is being used
a signal representative of the pressure demanded at the service is sent to the pump
control valve which then controls the pump to operate at the required pump pressure
and flow. The pump outlet pressure will typically be somewhere in the range 20-30
bar above the pressure at the service and the difference between the pump supply pressure
and the service pressure is called the pump margin pressure. In known load sensing
systems the pump margin pressure and the valve margin pressures are usually identical
(ignoring any line losses).
[0006] On a variable displacement hydraulic pump the margin pressure is set by a load sense
controller bias spring. On a fixed displacement hydraulic pump the margin pressure
is set by a bypass regulator valve bias spring. It is not possible to adjust the spring
pressure of the load sense controller bias spring or the bypass regulator valve bias
spring whilst the machine is in operation i.e. whilst the machine is being used and
as such the spring pressure is fixed whilst the machine is being used
[0007] Typically a service will react more quickly with a higher valve margin pressure than
with a lower valve margin pressure. A higher margin pressure can be advantageous in
some circumstances, for example when a loading shovel is being used to load loose
material, such as earth. However, under other circumstances a higher margin pressure
can be disadvantageous. For example, where an operator needs to carefully control
the position of a service. With a higher margin pressure the service can react too
quickly to operator inputs making precise control of the service difficult. Additionally,
higher margin pressures for low flow requirements represent an unnecessary energy
loss. An example where careful control of a service is required would be operative
of a loading shovel during a grading operation (i.e. an operation where a ground surface
is levelled off or graded by taking a thin skim off the ground). In such prior art
systems the margin pressure has to be set at a compromise.
[0008] Other prior art has attempted to vary the margin pressure at the pump, and so affect
the valve margin pressure to offer additional levels of flow control, but they suffer
from a lack of range (i.e. they start at the pre-set level and allow only a gradual
reduction in margin pressure, towards zero, by offsetting the spring load by electrical
solenoid or hydraulic pilot pressure means.
[0009] Operation of the hydraulic pump consumes fuel (the hydraulic pump is typically coupled
to an engine of the working machine which drives the hydraulic pump). Therefore, there
is a desire to operate the hydraulic pump and valves as efficiently as possible.
[0010] There is also a desire to provide hydraulic fluid quickly with minimal transmission
losses when it is required to avoid any significant lag between, for example, an operator
using a control interface to cause actuation of an actuator and the actuator actuating
as a result.
[0011] The distribution of hydraulic fluid between a plurality of control valves and associated
actuators is difficult as, for example, the termination of the operation of one actuator
can have a significant impact on the pressure of the hydraulic fluid in the hydraulic
system and, hence, the operation of the other actuators. There is a desire to reduce
the unwanted impact of changes in the demand for hydraulic fluid on the operation
of actuators of a hydraulic system.
[0012] An object of the present invention is to overcome one or more problems associated
with the prior art.
[0013] Thus, according to one aspect of the present invention there is provided a method
of operating a hydraulic system including providing
a hydraulic pump having a pump outlet,
a main orifice having a main orifice inlet in fluid communication with the pump outlet
and a main orifice outlet for supplying pressurised fluid to a service,
a flow orifice having a flow orifice inlet for sensing a pressure representative of
a pressure at the pump outlet and a flow orifice outlet,
an amplification orifice having an amplification orifice inlet in fluid communication
with the flow orifice outlet and an amplification orifice outlet for sensing a pressure
representative of a pressure at a service,
means for generating an output signal representative of a fluid pressure between the
flow orifice outlet and the amplification orifice inlet,
and a pump controller for controlling the hydraulic pump in response to the output
signal,
the flow orifice defining a flow orifice cross section area and
the amplification orifice defining an amplification orifice cross section area,
the flow orifice cross section area and the amplification orifice cross section area
defining a ratio,
in which the main orifice is variable and the ratio is variable,
the method further comprising the steps of operating the system in a first mode so
as to define a first mode ratio regime and operating the system in a second mode so
as to define a second mode ratio regime,
so that the first mode ratio regime is different to the second mode ratio regime.
[0014] The method may include operating the system in the first mode when the first mode
ratio regime is to have a fixed ratio.
[0015] The method may include the first mode ratio regime which fixes the ratio at greater
than 1 or less than 1 or equal to 1.
[0016] The method may include operating the system in the first mode when the first mode
ratio regime is to have a variable ratio.
[0017] The method may include the variable ratio including a ratio of greater than 1 and/or
including a ratio of less than 1 and/or including a ratio equal to 1.
[0018] The method may include the variable ratio excluding a ratio of greater than 1 or
wherein the variable ratio excluding a ratio of less than 1.
[0019] The method may include operating the system in the second mode when the second mode
ratio regime is to have a fixed ratio.
[0020] The method may include the second mode ratio being greater than 1 or less than 1,
or equal to 1.
[0021] The method may include operating the system in the second mode when the second mode
ratio regime is to have a variable ratio.
[0022] The method may include having a variable ratio which includes a ratio of greater
than 1 and/or includes a ratio of less than 1 and/or includes a ratio equal to 1.
[0023] The method may include having a variable ratio which excludes a ratio of greater
than 1 or wherein the variable ratio excludes a ratio of less than 1.
[0024] The method may further comprise the steps of operating the system in a third mode
so as to define a third mode ratio regime so that the ratio is controlled differently
in the first mode and the second mode and the third mode wherein when operating the
system in the third mode the third mode ratio regime is to have a fixed ratio.
[0025] The method may include the third mode ratio being greater than 1 or less than 1,
or equal to 1.
[0026] The method may further comprise the steps of operating the system in a third mode
so as to define a third mode ratio regime so that the ratio is controlled differently
in the first mode and the second mode and the third mode wherein when operating the
system in the third mode the third mode ratio regime is to have a variable ratio.
[0027] The method may include the variable ratio including a ratio of greater than 1 and/or
including a ratio of less than 1 and/or including a ratio equal to 1.
[0028] The method may include the variable ratio excluding a ratio of greater than 1 or
wherein the variable ratio excludes a ratio of less than 1.
[0029] The method may include the amplification orifice outlet is in fluid communication
with a service.
[0030] The method may include the flow orifice being variable.
[0031] The method may include the amplification orifice being variable.
[0032] The method may include the flow orifice being fixed.
[0033] The method may include the amplification orifice being fixed.
[0034] The method may include the main orifice being variable only between a first position
and a second position.
[0035] The method may include the flow orifice being variable only between a first position
and a second position.
[0036] The method may include the amplification orifice being variable only between a first
position and a second position.
[0037] The method may include the first position being a closed position.
[0038] The method may include the main orifice being variable between a first position,
a second position and a third position.
[0039] The method may include the flow orifice being variable between a first position,
a second position and a third position.
[0040] The method may include the amplification orifice being variable between a first position,
a second position and a third position.
[0041] The method may include the first position being a closed position.
[0042] The method may include the main orifice being continuously variable.
[0043] The method may include the flow orifice being continuously variable.
[0044] The method may include the amplification orifice being continuously variable.
[0045] The method may include the hydraulic pump being a variable displacement hydraulic
pump having a pump margin pressure and the controller is configured to vary a margin
pressure of the main orifice relative to the pump margin pressure in response to the
output signal.
[0046] The method may include the hydraulic pump is a fixed displacement hydraulic pump,
having a pump margin pressure defined by a bypass regulator valve and the controller
is configured to vary a margin pressure of the main orifice relative to the pump margin
pressure in response to the output signal.
[0047] The method may include the controller being configured to increase the margin pressure
of the main orifice relative to the pump margin pressure in response to the output
signal.
[0048] According to a further aspect of the present invention there is provided a hydraulic
system including
a hydraulic pump having a pump outlet,
a main orifice having a main orifice inlet in fluid communication with the pump outlet
and a main orifice outlet for supplying pressurised fluid to a service,
a flow orifice having a flow orifice inlet for sensing a pressure representative of
a pressure at the pump outlet and a flow orifice outlet,
an amplification orifice having an amplification orifice inlet in fluid communication
with the flow orifice outlet and an amplification orifice outlet for sensing a pressure
representative of a pressure at a service,
means for generating an output signal representative of a fluid pressure between the
flow orifice outlet and the amplification orifice inlet,
and a pump controller for controlling the hydraulic pump in response to the output
signal,
the flow orifice defining a flow orifice cross section area and
the amplification orifice defining an amplification orifice cross section area,
the flow orifice cross section area and the amplification orifice cross section area
defining a ratio,
in which the main orifice is variable and the ratio is variable,
the main orifice defining a main orifice margin pressure, the system being configured
to vary the main orifice margin pressure by varying the ratio.
[0049] The hydraulic system may include the pump defining a pump margin pressure and the
system being configured to vary the main orifice margin pressure relative to the pump
margin pressure.
[0050] The hydraulic system may include the main orifice margin pressure being greater than
the pump margin pressure.
[0051] Aspects of embodiments of the present invention as described, by way of example,
with reference to the accompanying drawings, in which:
Figure 1 shows a working machine incorporating a hydraulic system according to the
present invention;
Figure 2 shows an embodiment of a hydraulic system according to the present invention,
Figure 3 shows a hydraulic system according to the present invention, and
Figure 4 shows a hydraulic system according to the present invention.
[0052] With reference to figure 1, there is shown a working machine 10.
[0053] The working machine 10 may be a machine as generally depicted in figure 1; however,
it will be appreciated that embodiments of the present invention may be used in relation
to other types of working machine and the machine depicted in figure 1 is merely shown
by way of example.
[0054] The working machine 10 includes a main body 12 which may include a cab 14 mounted
thereon. The main body 12 of the machine carries an engine 16. The main body 12 may
include a ground engaging arrangement 18. The ground engaging arrangement may comprise,
for example, a plurality of wheels mounted on a plurality of axles and/or may comprise
one or more endless tracks. The ground engaging arrangement 18 is coupled to the engine
16 which is configured to drive the ground engaging arrangement 18 with respect to
a ground surface to cause movement of the main body across the ground surface.
[0055] The working machine 10 may include one or more working arms 20 on which may be mounted
respective working tools or implements 22. The working machine may include two working
arms 20, for example, as depicted in figure 1. The or each working arm 20 may comprise
a plurality of arm sections coupled to each other - for example, with the distal end
of one arm section coupled in a pivotable configuration to a proximal end of another
arm section. The or each working arm 20, or a part thereof, may be configured for
movement with respect to the main body 12 of the working machine 10. A working arm
20 may comprise a boom coupled to a dipper arm.
[0056] Movement of the or each working arm, or part thereof, may be driven by a respective
service such as an actuator 24 which may be a hydraulic actuator 24.
[0057] Other services may be provided to drive movement of other components of the working
machine 10.
[0058] A hydraulic system 30 (see figure 2) is provided to control and drive a hydraulic
service of the working machine such as one or more of the or each actuator 24 of the
working machine 10.
[0059] Hydraulic system 30 includes a hydraulic pump 32 driven by the engine and having
a pump outlet 60 and a pump inlet 65 in fluid communication with a source of hydraulic
fluid 34 in the form of a tank. The hydraulic pump supplies pressurised fluid to a
hydraulic service (in this case an actuator 24) primarily via main orifice 43 as described
below.
[0060] The hydraulic system has a main fluid path 61 and a secondary fluid path 62. The
main fluid path is in fluid communication with the pump outlet 60 and includes a main
orifice 43. The secondary fluid path 62 is in parallel with the main orifice 43. The
secondary fluid path includes a flow (or pilot) orifice 44 and an amplification orifice
45 in series with the flow orifice. Means 63 is capable of generating an output signal
representative of the fluid pressure in the secondary fluid path 62 between the flow
orifice 44 and the amplification orifice 45 in this case means 63 is a port connected
to pressure sensing line 66. A pump controller 64 is capable of controlling the pump
flow in response to the output signal. The main orifice 43 is variable and at least
one of the flow orifice 44 and amplification orifice 45 is a variable orifice.
[0061] Pump 32 may be a variable displacement pump or it may be a fixed displacement pump.
[0062] When the pump 32 is a variable displacement pump the pump controller 64 may act to
vary the pump flow. For example where pump 32 is a variable displacement swash plate
pump then the pump controller 64 may act to vary the angle of the swash plate, thereby
varying the pump flow.
[0063] Where the pump 32 is a fixed displacement pump the fixed displacement pump may include
a bypass valve through which excess fluid flow can pass on route to a reservoir (or
tank) of hydraulic fluid (such as source of hydraulic fluid 34). The pump controller
64 may vary the relief pressure of the bypass valve, thereby varying the amount of
excess fluid flow that passes to tank.
[0064] As mentioned above the main orifice 43 is a variable orifice, which may be variable
between just two orifice areas, or it may be variable between two or more discreet
orifice areas, or it may be continuously variable over a range of orifice areas. The
smallest orifice area of the main orifice may be zero (i.e. the main orifice may be
closable) or the smallest orifice area may be a non zero area (i.e. the main orifice
may not be closable). The main orifice 43 may be varied manually or electrically,
or via a pilot pressure.
[0065] The flow orifice (or pilot orifice) 44 may be a fixed orifice or may be a variable
orifice. When the flow orifice 44 is a variable orifice, it may be variable between
just two orifice areas, or it may be variable between two or more discreet orifice
areas, or it may be continuously variable over a range of orifice areas. When the
flow orifice 44 is a variable orifice the smallest orifice area may be zero (i.e.
the flow orifice may be closable) or the smallest orifice area may be a non zero area
(i.e. the flow orifice may not be closable). Where flow orifice 44 is variable it
may be varied manually, or electrically, or via a pilot pressure.
[0066] The amplification orifice 45 may be a fixed orifice or may be a variable orifice.
When the amplification orifice 45 is a variable orifice, it may be variable between
just two orifice areas, or it may be variable between two or more discreet orifice
areas, or it may be continuously variable over a range of orifice areas. When the
amplification orifice 45 is a variable orifice the smallest orifice area may be a
non zero area (i.e. the amplification orifice may not be closable). Where amplification
orifice 45 is variable it may be varied manually, or electrically, or via a pilot
pressure.
[0067] Where two or more of main orifice 43, flow orifice 44 and amplification orifice 45
are variable, they may be varied together or they may be varied independently.
[0068] The means 63 for generating an output signal representative of the fluid pressure
in the secondary fluid path between the flow orifice and amplification orifice may
be a tapping generating a pilot pressure signal or may be a pressure sensor that generates
an electrical signal.
[0069] Table 1 below shows three options with regard to the main orifice, flow orifice and
amplification orifice being either variable or fixed.
Table 1
Options |
Main Orifice |
Flow Orifice (pilot orifice) |
Amplification Orifice |
1 |
V |
V |
V |
2 |
V |
F |
V |
3 |
V |
V |
F |
[0070] Consideration of figure 2 shows that:-
hydraulic lines 50, 61A and 62A will all be at the same hydraulic pressure namely
the pump outlet pressure,
hydraulic lines 61B, 62C and 51 will all be at the same hydraulic pressure namely
the service pressure, or load sense pressure, i.e. the pressure sensed at the load
(or service).
[0071] When the service is being operated the pump will be pumping hydraulic fluid along
line 50, and line 61A, through the main orifice 43 along line 61B and line 51 to the
service 24. Because there will be a pressure drop across the main orifice as the hydraulic
fluid passes through the orifice then the pump outlet pressure will be higher than
the service pressure, the difference between the pump outlet pressure and service
pressure being the margin pressure.
[0072] The pressure in the line 62B between the flow orifice will be less than the pump
outlet pressure but will be greater than the service pressure.
[0073] The actual value will depend upon the relative cross sectional areas of the flow
and amplification orifices.
[0074] Thus if the flow orifice cross section area is larger than the amplification orifice
cross section area then the pressure in line 62B will be nearer the pump outlet pressure
than the service pressure.
[0075] Conversely if the cross section area of the flow orifice is smaller than the cross
section area of the amplification orifice then the pressure in line 62B will be nearer
the service pressure than the pump outlet pressure.
[0076] Thus by varying the ratio of the cross section area of the flow orifice and amplification
orifice the pressure in the line 62B (the intermediate pressure) between the flow
orifice and amp orifice can be varied and will be less than the pump outlet pressure
but more than the service pressure. This intermediate pressure can then be communicated
to the pump via line 66 so that the pump swash setting is controlled to match the
flow demands.
[0077] The present invention allows the system to be operated in a first mode and in a second
mode such that the ratio is controlled differently in the first mode and the second
mode.
[0078] As mentioned above, in prior art load sensing systems, the pump margin pressure and
valve margin pressure are usually identical (ignoring any line losses). The present
invention allows the valve (or orifice) margin pressure to be varied relative to the
pump margin pressure. This is done by varying the flow orifice area to amplification
orifice area ratio. Thus the valve margin pressure equals the pump margin pressure
plus (the area ratio squared times the pump margin pressure), in other words:
or 
[0079] Thus the first mode of operation defines a first mode ratio regime and the second
mode defines a second mode ratio regime which is different from the first mode ratio
regime.
[0080] In one embodiment in one mode the cross section area of the flow orifice may be 3
mm
2 and the cross section area of the amplification orifice may be set to 4 mm
2, giving a ratio of 3:4 i.e. 0.75. This ratio remains constant, setting a fixed valve
margin pressure (in this case equivalent to the pump margin x (1 + 0.75
2), different to the pump margin pressure proportional to the ratio. When operating
the machine in this mode with orifice 43 varying from zero to some max value flow
control of the service is established. In this mode the valve orifice 43 will have
a relatively low margin pressure of about 1.56 times the pump margin pressure across
it and hence this mode is suitable for precision work, such as grading. In this mode
the ratio regime is to have a fixed ratio i.e. when operating in this mode the ratio
does not change, i.e. the ratio remains constant.
[0081] In another mode, the cross section area of the flow orifice may be 3 mm
2 and the cross section area of the amplification orifice may be set to 1 mm
2, giving a ratio of 3:1 i.e. 3. This ratio remains constant when operating the machine
in this mode. In this mode the valve orifice 43 will have a relatively high margin
pressure (about 10 times the pump margin) across it and hence this mode is suitable
for fast work such as loading. In this mode the ratio regime is to have a fixed ratio
i.e. when operating in this mode the ratio does not change, i.e. the ratio remains
constant.
[0082] In another mode, the cross section area of the flow orifice may be 3 mm
2 and the cross section area of the amplification orifice may vary between 4 mm
2 at a relatively low displacement of an associated spool and 1.5 mm
2 at a relatively high displacement of an associated spool. Under these circumstances
the ratio will vary between 3:4, i.e. 0.75 at relatively low displacements and 3:1,
i.e. 3 at relatively high displacements. Under these circumstances, the valve orifice
43 will have a relatively low margin (of about 1.56 times the pump margin pressure
across it) at low spool displacement and will have a relatively high margin (of about
10 times the pump margin across it) at high spool displacement and hence this mode
is suitable for precision work such as grading at low spool displacement and is suitable
for fast work, such as loading at high spool displacement spool. The spool may typically
be a control spool for controlling the service (such as an actuator). In this mode
the ratio regime is to have a variable ratio i.e. when operating in this mode the
ratio changes i.e. the ratio does not remain constant.
[0083] In the above example it will be appreciated for all three modes of operation the
flow orifice cross section area is 3 mm
2, i.e. the flow orifice cross section area is fixed. By controlling the amplification
orifice in three different ways (set at 4 mm
2, set at 1 mm
2, variable between 1 mm
2 and 4 mm
2) then it is possible to control the ratio in three different ways (the ratio fixed
at 0.75, the ratio fixed at 3, the ratio variable between 0.75 and 3) i.e. it is possible
to have three different ratio regimes by being able to control the ratio in three
different ways (i.e. by having three different ratio regimes) then the pressure at
the means 63 and in hydraulic lines 66 can be controlled in three different ways allowing
the valve margin pressure across orifice 43 to be controlled in three different ways.
[0084] In the example above the main orifice is variable, the amplification orifice is variable
and the flow orifice is fixed and this equates to option 2 in table 1 above. In an
alternative embodiment the amplification orifice could be fixed and the flow orifice
could be variable as in option 3 in table 1 above. In one mode the cross section area
of the flow orifice may remain constant during operation in this mode. In a different
mode of operation the cross section area of the flow orifice may remain constant at
a different cross section area. In an alternative mode the cross section area of the
flow orifice may vary dependant upon a characteristic of machine (for example dependent
upon the position of associated spool). By controlling the cross section area of the
flow orifice in different ways allows control of the ratio of cross section area of
the flow orifice and amplification orifice in different ways and this in turn allows
the valve margin pressure across orifice 43 to be controlled in different ways.
[0085] In option 1 in table 1 above, both the flow orifice and the amplification orifice
are variable. Under these circumstances in one embodiment in one mode, the cross section
area of the flow orifice may be set to 2 mm
2 and the cross section area of the amplification orifice may be set to 4 mm
2 giving a ratio of 2:4 or 0.5. This ratio remains constant when operating the machine
in this mode. In this mode the valve will have a relatively low pressure margin and
hence this may be suitable for precision work, such as grading.
[0086] In another mode the cross section area of the flow orifice may be set to 4 mm
2 and the cross section area of the amplification orifice may be set to 2 mm
2 giving a ratio of 4:2 i.e. 2. This ratio remains constant when operating the machine
in this mode. In this mode the valve will have a relatively high margin and hence
this mode is suitable for fast work such as loading.
[0087] In another mode the cross section area of either the amplification orifice or the
flow orifice or both orifices may vary depending upon a characteristic of the machine,
for example depending upon the position of an associated spool. In one mode the cross
section area of the amplification orifice may vary whilst cross section area of the
flow orifice remains constant. In another mode the cross section area of the flow
orifice may be variable whilst the cross section area of the amplification orifice
remains constant. In another mode the cross section area of the amplification orifice
may vary and the cross section area of the flow orifice may vary. As will be appreciated,
by arranging for the cross section area of the flow orifice to be variable and the
cross section area of the amplification orifice to be variable allows the system to
be operated in a first mode and in a second mode such that the ratio is controlled
differently in the first mode and the second mode.
[0088] With reference to figure 3 there is shown a further hydraulic system 230 according
to the present invention with components that fulfil the same function as hydraulic
system 30 being labelled 200 greater. Pump 232 is a fixed displacement pump. A bypass
regulator 270 allows excess fluid flow to pass to tank and is controlled via a port
263 between the flow orifice 244 and amplification orifice 245 and pressure sensing
line 266. The flow orifice and amplification orifice are in series with the amplification
orifice being downstream of the flow orifice.
[0089] In this case there are two main orifices 243A and 243B. The main orifice 243A is
defined by orifice 243A1 and orifice 243A2 of control valve 271. Orifice 243B is defined
by orifice 243B1 and 243B2 contained within control valve 272.
[0090] Load sensing copy valve 277 is provided. Copy valves are known per se and act to
replicate the pressure either side of the valve. Thus, the pressure at C is replicated
by the copy valve such that the pressure at C' is the same as the pressure at C.
[0091] Control valve 271 controls service 273 and control valve 272 controls service 274.
A compensator 275 is associated with control valve 271 and a compensator 276 is associated
with control valve 272. Compensators per se are known and act to reduce pressure being
supplied to the associated service under certain conditions. Thus, for the purpose
of explanation, it is assumed that service 273 requires a higher pressure than service
274. Accordingly, the spool of compensator 275 will be positioned as shown in figure
3 and when the control valve 271 is operated, then hydraulic fluid will pass through
the control valve 271, through the compensator 275 (without any significant loss in
pressure) through control valve 271 to service 273.
[0092] However, because, in this example, service 274 operates at a lower pressure, the
spool of compensator 276 will be positioned towards the left when viewing figure 3
i.e. the spool will move to the middle position shown and may move nearly to the fully
closed position (the right hand box symbol) since the pressure at D in the hydraulic
circuit will be less than the pressure at A and therefore the pressure at C' will
cause the spool of the compensator to move left when viewing figure 3. This will result
in fluid flowing through compensator 276 dropping the pressure between A and D.
[0093] Hydraulic system 330 includes a known drain regulator 280 which is arranged to drain
trapped pressure when no service spool is actuated thus allowing pump pressure to
fall back to a low standby value.
[0094] Relief valves 281 and 282 are provided to protect service 274. Relief valves 283
and 284 are provided to protect service 273. Relief valve 285 acts to limit the pressure
in line 266 but can be temporarily overridden by a "boost" valve 286, which, when
actuated by the operator results in a pressure drop across the valve thereby enabling
the pressure in line 266 to increase above the relief valve pressure setting of relief
valve 285. This "boost" valve is used in circumstances where extra system pressure
is temporarily required, for example, during a digging operation.
[0095] Consideration of figure 3 shows the following:-
[0096] The main orifice 243A and 243B are in fluid communication with the pump outlet. Each
main orifice 243A and 243B supplies pressurised fluid to its associated service 273
and 274. The flow orifice 244 has a flow orifice inlet which senses a pressure representative
of the pressure of the pump outlet, i.e. in this case it senses the pressure of the
pump outlet. The flow orifice has an outlet. The amplification orifice 245 has an
inlet in fluid communication with the flow orifice outlet. The amplification orifice
outlet senses a pressure, C' representative of a pressure C at a service (in the above
example, the pressure at service 273). Means in the form of port 263 generate an output
signal representative of the fluid pressure between the flow orifice outlet and the
amplification orifice inlet. A pump controller (in this case bypass regulator 270)
controls the hydraulic pump in response to the output signal. The flow orifice defines
a flow orifice cross section area in this case a fixed cross section area. The amplification
orifice defines an amplification orifice cross section area, in this case a variable
cross section area. The flow orifice cross section area and the amplification cross
section area define a ratio. The main orifice 243A, 243B is variable. The ratio is
variable (by virtue of varying the amplification orifice 245). The hydraulic system
30 can be operated in a first mode and in a second mode such that the ratio is controlled
differently in the first mode and the second mode. The ratio is controlled differently
by virtue of controlling the cross section area of the amplification orifice differently
in the first and second modes. In one mode, the amplification orifice can be controlled
by maintaining the amplification orifice cross section area at a specified value.
In the second mode of operation the amplification orifice may be maintained at a specified
value different from the value when operating in first mode. In another mode of operation
the cross section area of the amplification orifice may be variable.
[0097] In further embodiments in addition to the amplification orifice being variable the
flow orifice may be variable.
[0098] In further embodiments the amplification orifice may be fixed and the flow orifice
may be variable.
[0099] When the flow orifice is variable it may operate in a first mode where the cross
section area of flow orifice is fixed. The system may operate in a second mode where
the cross section area of the flow orifice is fixed at a different value to when operating
the first mode. The system may operate in a mode where the cross section area of the
flow orifice is variable.
[0100] The bypass regulator 270 includes a spring 290 which sets a basic pump pressure margin.
In the present invention this basic setting may be relatively low, for example 4 bar.
The pressure in line 266 acts to assist spring 290 thereby increasing the pump pressure
i.e. the pump pressure will always be 4 bar higher than the pressure in line 266.
Because the ratio of cross section areas between the flow orifice and amplification
orifice can be varied depending upon which mode of operation this system is being
operated under, then the pressure in line 266 varies depending upon the mode of operation
in which the system is operating and hence the valve orifice 243A1 and 243B1 margin
pressure can be varied depending upon the mode of operation in which the system is
being operated.
[0101] With reference to figure 4 there is shown a further hydraulic system 330 with components
that fulfil the same function as hydraulic system 230 being labelled 100 greater.
[0102] The only difference between hydraulic system 230 and hydraulic system 330 is that
hydraulic system 330 includes a variable pump with associated hydraulic circuitry
whereas hydraulic system 230 has a fixed pump with associated hydraulic circuitry.
Thus, pump 332 is a variable displacement pump. In this case pump 332 has a swash
plate 394, the angle of which is controlled by swash plate controller 395. The basic
pump margin pressure is set by spring 390 and the spring pressure of spring 390 will
be supplemented by the pressure in line 366 to increase the pump pressure as required.
The hydraulic system 330 can operate in the first mode where the ratio of the cross
section area of the flow orifice and amplification orifice is controlled in a first
manner and can operate in a second mode where the ratio of the flow control orifice
cross section area and amplification orifice cross section area is controlled in a
second manner.
[0103] In further embodiments in addition to the amplification orifice being variable the
flow orifice may be variable.
[0104] In further embodiments the amplification orifice may be fixed and the flow orifice
may be variable.
[0105] When the flow orifice is variable it may operate in a first mode where the cross
section area of flow orifice is fixed. The system may operate in a second mode where
the cross section area of the flow orifice is fixed at a different value to when operating
the first mode. The system may operate in a mode where the cross section area of the
flow orifice is variable.
[0106] As mentioned above, the outlet from the amplification orifice 45 senses the pressure
representative of a pressure at service 24. In this case the outlet of amplification
orifice 45 senses the pressure by being in fluid communication with the service.
[0107] These can be contrasted with the outlet from amplification orifice 245 and 345, which,
whilst also sensing a pressure representative of a pressure at a service (in the example
the pressure representative of pressure at the respective service 273, 373), the outlet
from the amplification orifice 245 and 345 is not in fluid communication with respective
service 273, 373.
[0108] As described above one ratio regime is to keep the ratio (or ratio value) fixed.
In the example above the ratio value was 0.75 and this ratio value remained constant
when operating the system in this mode. As described above, another, different ratio
regime is to keep the ratio (or ratio value) fixed at a different value, in the example
case the ratio value was 3 and this ratio value remained constant when operating the
system in this mode. Thus, it is possible to have two different ratio regimes even
though the value of the ratio does not change when operating under each of the regimes.
The regimes are different because the value of the ratio when operating under each
regime is different.
[0109] As described above, one ratio regime is to vary the ratio (or vary the ratio value).
The example above the ratio value was varied between 0.86 and 2. As will be appreciated,
another, different ratio regime would be to vary the ratio differently, for example
the ratio could vary between 0.5 and 2 to provide a different ratio regime, the ratio
could vary between 0.68 and 3 to provide a different ratio regime. Where the ratio
regime has a variable ratio value, the ratio value may vary dependent upon a first
machine characteristic in a first ratio regime and may vary dependent upon a second
machine characteristic in a second ratio regime.
[0110] Clearly if one ratio regime has a fixed ratio and another ratio regime has a variable
ratio, then these two ratio regimes will necessarily be different regimes.
1. A method of operating a hydraulic system including providing
a hydraulic pump having a pump outlet,
a main orifice having a main orifice inlet in fluid communication with the pump outlet
and a main orifice outlet for supplying pressurised fluid to a service,
a flow orifice having a flow orifice inlet for sensing a pressure representative of
a pressure at the pump outlet and a flow orifice outlet,
an amplification orifice having an amplification orifice inlet in fluid communication
with the flow orifice outlet and an amplification orifice outlet for sensing a pressure
representative of a pressure at a service,
means for generating an output signal representative of a fluid pressure between the
flow orifice outlet and the amplification orifice inlet,
and a pump controller for controlling the hydraulic pump in response to the output
signal,
the flow orifice defining a flow orifice cross section area and
the amplification orifice defining an amplification orifice cross section area,
the flow orifice cross section area and the amplification orifice cross section area
defining a ratio,
in which the main orifice is variable and the ratio is variable,
the method further comprising the steps of operating the system in a first mode so
as to define a first mode ratio regime and operating the system in a second mode so
as to define a second mode ratio regime,
so that the first mode ratio regime is different to the second mode ratio regime.
2. A method as defined in claim 1 wherein when operating the system in the first mode
the first mode ratio regime is to have a fixed ratio, preferably wherein the first
mode ratio regime fixes the ratio at greater than 1 or less than 1 or equal to 1.
3. A method as defined in claim 1 wherein when operating the system in the first mode
the first mode ratio regime is to have a variable ratio, preferably wherein the variable
ratio includes a ratio of greater than 1 and/or includes a ratio of less than 1 and/or
includes a ratio equal to 1 and/or preferably wherein the variable ratio excludes
a ratio of greater than 1 or wherein the variable ratio excludes a ratio of less than
1.
4. A method as defined in claim 1 wherein when operating the system in the second mode
the second mode ratio regime is to have a fixed ratio, preferably wherein the second
mode ratio is greater than 1 or less than 1, or equal to 1.
5. A method as defined in claim 1 wherein when operating the system in the second mode
the second mode ratio regime is to have a variable ratio, preferably wherein the variable
ratio includes a ratio of greater than 1 and/or includes a ratio of less than 1 and/or
includes a ratio equal to 1 and/or preferably wherein the variable ratio excludes
a ratio of greater than 1 or wherein the variable ratio excludes the ratio of less
than 1.
6. A method as defined in claim 1, the method further comprising the steps of operating
the system in a third mode so as to define a third mode ratio regime so that the ratio
is controlled differently in the first mode and the second mode and the third mode
wherein when operating the system in the third mode the third mode ratio regime is
to have a fixed ratio, preferably wherein the third mode ratio is greater than 1 or
less than 1, or equal to 1.
7. A method as defined in claim 1, the method further comprising the steps of operating
the system in a third mode so as to define a third mode ratio regime so that the ratio
is controlled differently in the first mode and the second mode and the third mode
wherein when operating the system in the third mode the third mode ratio regime is
to have a variable ratio, preferably wherein the variable ratio includes a ratio of
greater than 1 and/or includes a ratio of less than 1 and/or includes a ratio equal
to 1 and/or preferably wherein the variable ratio excludes a ratio of greater than
1 or wherein the variable ratio excludes a ratio of less than 1.
8. A method as defined in any preceding claim wherein the amplification orifice outlet
is in fluid communication with a service.
9. A method as defined in any preceding claim in which the flow orifice is variable,
preferably in which the amplification orifice is variable.
10. A method as defined in any of claims 1 to 8 in which the flow orifice is fixed and/or
in which the amplification orifice is fixed.
11. A method as defined in any proceeding claim wherein the hydraulic pump is a variable
displacement hydraulic pump having a pump margin pressure and the controller is configured
to vary a margin pressure of the main orifice relative to the pump margin pressure
in response to the output signal.
12. A method as defined in any one of claims 1 to 10 in which the hydraulic pump is a
fixed displacement hydraulic pump, having a pump margin pressure defined by a bypass
regulator valve and the controller is configured to vary a margin pressure of the
main orifice relative to the pump margin pressure in response to the output signal.
13. A method as defined in claim 11 or 12 wherein the controller is configured to increase
the margin pressure of the main orifice relative to the pump margin pressure in response
to the output signal.
14. A hydraulic system including
a hydraulic pump having a pump outlet,
a main orifice having a main orifice inlet in fluid communication with the pump outlet
and a main orifice outlet for supplying pressurised fluid to a service,
a flow orifice having a flow orifice inlet for sensing a pressure representative of
a pressure at the pump outlet and a flow orifice outlet,
an amplification orifice having an amplification orifice inlet in fluid communication
with the flow orifice outlet and an amplification orifice outlet for sensing a pressure
representative of a pressure at a service,
means for generating an output signal representative of a fluid pressure between the
flow orifice outlet and the amplification orifice inlet,
and a pump controller for controlling the hydraulic pump in response to the output
signal,
the flow orifice defining a flow orifice cross section area and
the amplification orifice defining an amplification orifice cross section area,
the flow orifice cross section area and the amplification orifice cross section area
defining a ratio,
in which the main orifice is variable and the ratio is variable,
the main orifice defining a main orifice margin pressure, the system being configured
to vary the main orifice margin pressure by varying the ratio.
15. A hydraulic system as defined in claim 14 wherein the pump defines a pump margin pressure
and the system is configured to vary the main orifice margin pressure relative to
the pump margin pressure, preferably wherein the main orifice margin pressure is greater
than the pump margin pressure.