TECHNICAL FIELD
[0001] The present disclosure relates to methods and systems of protecting and controlling
renewable energy plants. More particularly, the disclosure relates to methods of protecting
wind power plants during power network faults, and especially recurring power network
faults.
BACKGROUND
[0002] Wind power plants, as well as other renewable energy power plants, are expected to
conform to particular requirements of the power network to which they are connected.
Wind power plants, which typically comprise a plurality of wind turbine generators
and are also known as a wind parks or a wind farms, are each connected to a power
network or 'grid'. At the power network, the power output from each wind power plant
to the network is controlled, under normal operating conditions, by a power plant
control system or controller (PPC). In exceptional operating conditions, such as during
a grid fault, wind turbine generators are protected by low-voltage ride-through (LVRT)
and fault ride-through (FRT) protection schemes implemented by a wind turbine controller.
Both the PPC and wind turbine controller implement operational limits and requirements
as set out by a Transmission System Operator (TSO) or in country-specific grid interconnection
requirements or 'grid codes' to achieve continuity of power supply.
[0003] Establishing continuity of power supply is particularly important to grid operation
and control. A notable challenge to this continuity is presented when a transient
fault occurs, which leads to a voltage dip while the line or equipment on which the
fault occurred is temporarily taken offline by opening circuit breakers around the
fault. Transient faults are often only temporary events, such as flash-overs across
insulators or self-clearing fault on power lines, and the preferred approach on many
power networks is to automatically reclose the tripped breaker after a predefined
time delay to increase availability of power supply. If the fault has not been fully
cleared when the breakers are reclosed, then there may be a second voltage dip, and
the fault becomes a recurring fault. Until the fault clears, there may be any number
of dips. Wind turbine generators are expected to remain connected to the power network
through such temporary faults.
[0004] As mentioned, during external fault scenarios, each wind turbine generator is protected
from voltage deviation beyond its tolerable limits by an LVRT protection scheme. The
protection scheme operates to track a predefined curve during the fault, and is set
to disconnect the turbine for any voltage deviation below the curve. The turbine should
remain connected to the network at all other times. If a ride-through threshold is
reached, the LVRT protection scheme is reset in preparation for future faults.
[0005] However, even though the turbine design and LVRT protection scheme are coordinated
with the requirements of the power network, recurring fault scenarios present a problem
in wind power plant operation. More precisely, operating conventional LVRT protection
schemes may result in unwanted disconnection of the wind turbine generator from the
power network due to the configuration of the LVRT protection scheme not taking account
of recurring faults. Even when LVRT protection schemes are configured to be compliant
with the network requirements relating to recurring faults, a conflict may result
due to other protection systems operating in precedence to the LVRT protection scheme.
This conflict impacts the ability of the LVRT protection scheme, as well as other
protection schemes, to provide sufficient protection to the wind turbine generator,
and so may make the wind turbine generator vulnerable to damage.
[0007] In view of the above mentioned problems there is need for protection of wind turbine
generators that can sufficiently operate during recurring faults and without impacting
the operation of conventional LVRT protection schemes.
SUMMARY OF THE INVENTION
[0008] According to an aspect of the present invention, as defined by claim 1, there is
provided a method for operating a wind turbine generator connected to a power network
to account for recurring voltage faults on the power network caused by automatic reclosure
of at least one circuit breaker following a short-circuit. The method comprises: identifying
a deviation of voltage level of the power network from a normal operational voltage
level of the network; determining that the identified deviation fulfils criteria for
automatic reclosure; and operating the wind turbine generator in a recurring fault
mode if automatic reclosure criteria are fulfilled. In operating the wind turbine
generator in recurring fault mode, the method comprises: monitoring the recovery of
the voltage level from the deviation; categorising the recovery of the voltage as
one of at least a strong recovery or a weak recovery; and implementing a ride-through
protocol according to the category of recovery.
[0009] By implementing a recurring fault mode that is separate to conventional low-voltage
ride-through modes, the method provides a protection protocol that is able to account
for multiple voltage dips based upon characteristics of the recovery. In particular,
by categorising the recovery, the method protects generators throughout recurring
faults, whilst remaining compliant with grid requirements as is mandatory for new
power plants. Furthermore, the above method does not impact upon conventional low-voltage
ride-through modes due to the determination of the deviation fulfilling particular
criteria and only entering the recurring fault mode if the criteria are fulfilled.
Therefore, the method acts as an augmentation to the low-voltage ride-through modes,
requiring minimal or no alteration to existing hardware. Advantageously, therefore,
the method can be implemented readily in both existing and new plants.
[0010] The deviation may comprise a power network fault. Determining that the deviation
fulfils criteria for automatic reclosure may comprise comparing the voltage levels
following the fault with a predetermined reclosure threshold.
[0011] By using a reclosure threshold, it is noted that recurring faults are most likely
to happen where circuit breakers are configured to automatically reclose. Comparing
voltage levels in the described manner ensures that the method is able to smoothly
integrate with existing power networks.
[0012] According to the present invention, categorising the recovery of the voltage may
comprise applying one or more tests to the recovery such that the recovery is categorised
as strong recovery if it passes the, or each, test and is categorised as weak recovery
if it does not pass one or more of the tests.
[0013] Preferably, the method comprises three tests, and the recovery may be categorised
as strong recovery only if it passes each of the three tests.
[0014] The recovery is categorised as weak recovery unless it passes particular tests, thereby
implementing a strict approach to voltage recovery. Where weak recovery is involved,
there may be some danger to generators if the correct protocol is not implemented,
and so the step of categorising the recovery as strong recovery only if it passes
the, or each, test ensures that protection of generators can be prioritised.
[0015] The at least one test may comprise comparing the voltage level with a first voltage
threshold. The test may be passed if the voltage level exceeds the first voltage threshold
in a predetermined first time period. The test may be passed if the voltage level
exceeds the first voltage threshold at the end of a predetermined first time period.
[0016] Beneficially, comparison of voltage level with a threshold within periods of time
indicates the speed and size of the recovery adequately. It is possible that the recovery
of the voltage within the particular time period is a function of the state of the
grid and/or the power plant, and so can be used as a gauge or metric of the recovery.
[0017] The at least one test may comprise comparing the voltage level with a second voltage
threshold. The test may be passed if the voltage level exceeds the second voltage
threshold in a predetermined second time period. The test may be passed if the voltage
level exceeds the second voltage threshold at the end of a predetermined second time
period.
[0018] Implementation of two tiers of voltage thresholds over certain time periods is useful
for computational efficiency, and for speed of implementation of ride-through protocols
should the recovery fail one or more of the tests. The tests may be performed sequentially,
such that failure of a first test results in the categorisation of the recovery as
weak.
[0019] The second voltage threshold may be greater than the first voltage threshold. The
second voltage threshold may be an upper voltage threshold, which is less than an
operational voltage of the generator. The second voltage threshold may be equal to
the predetermined reclosure threshold. The first voltage threshold may be a lower
voltage threshold, and may be user-determined. The first voltage threshold may alternatively
be set by predetermined grid requirements, or may be adaptive based upon monitored
parameters of the plant or grid.
[0020] The first and second time periods may be concurrent and of equal length. Thus, the
comparison of voltage levels against the first and second thresholds may be performed
at the same time.
[0021] The at least one test may comprise comparing the voltage level with a third voltage
threshold and performing a count of the number of times that the voltage level is
equal to the third voltage threshold within a third predetermined time period. The
test may be passed if the count is zero or an even number. The test may be passed
if the voltage level is greater than the third voltage threshold at the end of the
predetermined time period.
[0022] Counting the times that the third threshold is crossed provides an indication of
stability of the voltage levels following the initial recovery. An unstable, and therefore
weak, recovery, may have an odd count, where the voltage level is below the third
threshold at the end of the third time period. This may indicate that the recovery
has decayed below the level that it should be, and advantageously permits protection
of the generators where instability is present.
[0023] The second and third voltage threshold may be the same. The third time period may
follow at least one of the first time period or the second time period. Comparing
the voltage level with a third voltage threshold may be performed after the comparison
of the voltage level with the first or the second threshold. The comparison of the
voltage level with the third voltage threshold may be performed only if the previous
two comparison tests are passed.
[0024] The method may further comprise determining that the voltage deviation fulfils low-voltage
criteria. The method may further comprise entering a low-voltage mode if the low-voltage
criteria are fulfilled, the low-voltage mode being configured to run concurrently
with the recurring fault mode. Running concurrent low-voltage and recurring fault
modes provides an extra layer of protection, and uses the existing protocol to help
protect generators during recurring fault situations.
[0025] If the voltage recovery is categorised as weak recovery, the step of implementing
a ride-through protocol may comprise terminating the recurring-fault mode and operating
the wind turbine generator in low-voltage mode only. The method therefore protects
the generators first and foremost, where a weak recovery exists.
[0026] If the voltage recovery is categorised as strong recovery, the step of implementing
a ride-through protocol may comprise altering the low-voltage mode to account for
a subsequent voltage dip. Alteration of a low-voltage mode may be a particularly useful
feature as it allows for restriction of the low-voltage mode's operation. Disconnection
of the generators from the grid due to the low-voltage mode's operation during recurring
faults can be halted.
[0027] Altering the low-voltage mode may comprise restarting the low-voltage mode before
automatic reclosure to prevent the wind turbine generator from being disconnected
in the event of another voltage deviation.
[0028] Where the voltage recovery is strong, by altering the low-voltage mode in the above
way, the method beneficially identifies that the generator is unlikely to be in danger
in the low-voltage mode and so acts to ensure that disconnection does not occur should
a further voltage deviation happen. This procedure improves the likelihood that generator
is maintained in compliance with grid requirements.
[0029] The method may comprise identifying a further voltage deviation and operating the
wind turbine generator in recurring fault mode in relation to the further voltage
deviation. In this way, the method is useful in protecting generators throughout the
entirety of the recurring fault, not just the first deviations.
[0030] The method may comprise terminating recurring fault mode if the voltage levels return
to normal operational levels.
[0031] According to another aspect of the invention, as defined by claim 14, there is provided
a wind turbine generator may comprise a wind turbine controller configured to carry
out the method described above.
[0032] According to another aspect of the invention, as defined by claim 15, there is provided
a computer program product downloadable from a communication network and/or stored
on a machine readable medium, comprising program code instructions for implementing
the method described above.
BRIEF DESCRIPTION OF THE DRAWINGS
[0033] One or more embodiments of the invention will now be described, by way of example
only, with reference to the accompanying drawings, in which:
Figure 1 is a schematic view of a wind power plant and its connection to a grid;
Figure 2 is a chart showing a typical reclosing sequence during a recurring fault on a power
network;
Figure 3 is a chart showing voltage recovery of a wind turbine generator using conventional
protection methodology;
Figure 4 is a block diagram of a control method according to an embodiment of the invention;
Figure 5 is a flow chart illustrating the control method of Figure 4;
Figure 6a is a chart showing strong voltage recovery of a wind turbine generator;
Figure 6b is a chart showing the resetting of the low-voltage ride-through protocol in response
to the recovery show in Figure 6a;
Figure 7 is a chart showing weak voltage recovery of a wind turbine generator;
Figure 8 is a chart showing an alternative strong voltage recovery of a wind turbine generator;
and
Figure 9 is a chart showing an alternative weak voltage recovery of a wind turbine generator.
DETAILED DESCRIPTION
[0034] Figure 1 illustrates a typical architecture in which a wind power plant (WPP) is
connected to a main transmission grid as part of a wider power network. As will be
understood by the skilled reader, a WPP comprises at least one wind turbine generator
(WTG), and is also known as a wind park or a wind farm. The example shown is representative
only and the skilled reader will appreciate that other specific architectures are
possible, in relation to both wind power plants and power plants for other renewable
energy sources. Thus, the invention also relates to renewable energy power plants
in general, rather than being specific to wind power plants as in the illustrated
embodiment. In addition, the skilled reader will appreciate that methods, systems
and techniques also described below may be applicable to many different configurations
of power network. Moreover, the components of the wind power plant and power network
are conventional and as such would be familiar to the skilled reader.
[0035] Figure 1 shows a power network 10 incorporating a WPP 12. The WPP 12 includes a plurality
of WTGs 14. A single WTG would also be possible. Each of the plurality of WTGs 14
converts wind energy into electrical energy, which is transferred from the WTGs 14
to a main transmission network or main grid 16, as active current, for distribution.
A collector network 17 extends between the WPP 12 and the main grid 16.
[0036] Each of the WTGs 14 is associated with a respective WTG controller 15. In some embodiments,
a set of WTGs may share a single, semi-centralised WTG controller, such that there
are fewer WTG controllers than WTGs. WTG controllers 15 can be considered to be computer
systems capable of operating a WTG 14 in the manner prescribed herein.
[0037] During normal operation of the WPP 12, the WTG controllers 15 operate to implement
active and reactive current requests received from a power plant controller (PPC)
32. During extraordinary conditions, such as during a grid fault, the WTG controllers
15 operate to fulfil predetermined network requirements, as well as acting to protect
the WTGs 14 from any potentially harmful conditions.
[0038] WTGs 14 generate both active current and reactive current, and are operated to support
the voltage level of the main grid 16. The main grid 16 often has specific requirements
for voltage support, especially during deviations of the voltage from conventional
operating conditions, with which the WPP 12 is required to comply. The WPP 12 will
be expected to stay connected to the grid 16 throughout a variety of faults or voltage
deviations, including during recurring faults.
[0039] Recurring faults are faults where the voltage level 'dips', or drops below a certain
threshold value, more than once without returning to normal operational levels. Initially,
a fault may occur where the voltage level decreases rapidly from normal operational
levels. Often, voltage levels recover to close to conventional levels. However, in
some circumstances, recurring faults occur where the voltage levels do not completely
recover to pre-fault levels, and instead a second dip occurs, where the voltage drops
rapidly again after recovering partially. A recurring fault may have any number of
dips before recovery. Recurring faults may also be defined by way of time periods,
such as where a second voltage dip occurs within a predefined time period after the
first fault. Such time periods may be quantifiable using knowledge of the operation
of systems within the grid. By way of example, the predefined time period may be one
second, but this should be understood as not to be limiting.
[0040] More particularly, recurring faults occur when a short-circuit is not cleared in
time to prevent multiple voltage dips occurring on the grid, due to the automatic
operation of protection systems within the power plant or grid. Conventional protection
systems may inadvertently disconnect the WPP 12 from the grid 16 during multiple voltage
dips and recurring faults, and their adaptation to account for multiple dips can lead
to inefficient protection of the WPP 12 during other faults. WPPs 12 having WTGs 14
that are operated according to the method of the present invention are configured
to account for recurring faults by resetting conventional protection systems prior
to the next dip, provided the condition of the grid 16 is good enough to support strong
voltage recovery.
[0041] Returning to Figure 1, each of the WTGs 14 of the WPP 12 is connected to a local
grid (not shown) that links the WTGs 14. The WPP 12 is, in turn, suitably connected
to a collector bus 18 via a feeder line 20. The collector bus 18 may be at an intermediate
voltage level that is suitable for relatively short distance power transmission, for
example in the region of 10 kV to 150 kV, most usually between 110 kV and 150 kV.
The collector bus 18 may also provide a point of common coupling (PCC) for a plurality
of wind power plants, although, only a single WPP 12 is shown here for simplicity.
[0042] The collector bus 18 is connected to a main step-up transformer 22 by a transmission
line 24. The main transformer 22 is in turn connected to the main grid 16 at a Point
of Interconnection (Pol) 26 by another transmission line 28. The Pol 26 is an interface
between the WPP 12 and the main grid 16.
[0043] While the collector bus 18 may be required to span distances up to around 100km,
the main grid 16 may be an international, national, or regional grid such as the National
Grid of Great Britain, for example, and therefore may be required to span distances
of up to around 250km or more. Accordingly, the voltage level of the main grid 16
may be much higher than the voltage level of the collector bus 18 for better transmission
efficiency.
[0044] The connecting lines such as the transmission and feeder lines 20, 24, 28 may each
include a protection system 30 to protect individual components from damage during
or following extreme conditions. For example, it is envisaged that at least an appropriate
circuit breaker will be included in each line.
[0045] Hereinafter, it should be assumed that references to components being connected or
connections between components comprise suitable feeder or transmission lines as described
above unless it is otherwise indicated.
[0046] A Power Plant Controller (PPC) 32 is connected to the power network 10 at a Point
of Measurement (PoM) 34 and is also connected directly to the WPP 12. The role of
the PPC 32 is to act as a command and control interface between the WPP 12 and a grid
operator or transmission system operator (TSO) 36. The TSO 36 is responsible for indicating
the needs and requirements of the main grid 16 to the PPC 32. The PPC 32, in its role
as command and control interface, interprets the power delivery demands requested
of it by the TSO 36 and manages the WTGs 14 in the WPP 12 in order to satisfy those
requirements, whilst taking into account other operative factors such as grid faults
and sudden changes in output or measured grid voltage.
[0047] The PPC 32 is a suitable computer system for carrying out the controls and commands
as described above and so incorporates a processing module 38, a connectivity module
40, a memory module 42 and a sensing module 44.
[0048] In order to monitor and regulate the output of the WPP 12 and to interpret the power
demands correctly, the PPC 32 is connected to the transmission line 28 between the
main transformer 22 and the Pol 26 at the PoM 34. The PPC 32 is equipped to measure
a variety of parameters including a representative power output that will be supplied
to the main grid 16 at the Pol 26 by the WPP 12. As the PoM 34 is not at the Pol 26,
the measured parameters are only representative as losses in the lines between the
PoM 34 and Pol 26, and between the PoM 34 and the PPC 32, may have an effect on the
measurements. Suitable compensation may take place to account for the losses to ensure
that the measurements are accurate.
[0049] In addition, the PPC 32 measures parameters of the power output such as a frequency
and voltage, as well as reactive current exchange between the WPP 12 and the main
grid 16 and the voltage level of the main grid 16. The PPC 32 compares the measured
parameters against specific grid requirements and communicates control commands to
specific components of the WPP 12 accordingly. The WPP 12 is capable of altering its
reactive current output in reaction to commands received from the PPC 32.
[0050] The PPC 32 communicates control commands to the WTG controllers 15, or directly to
the WTGs 14, in a suitable manner. It will be noted that Figure 1 is a schematic view,
so the way in which the control commands are transferred is not depicted explicitly.
However, it will be appreciated that suitable cabling may be provided to interconnect
the PPC 32 and the WTGs 14 or WTG controllers 15. The interconnections may be direct
or 'point to point' connections, or may be part of a local area network (LAN) operated
under a suitable protocol (CAN-bus or Ethernet for example). Also, it should be appreciated
that rather than using cabling, the control commands may be transmitted wirelessly
over a suitable wireless network, for example operating under WiFi
™ or ZigBee
™ standards (IEEE802.11 and 802.15.4 respectively).
[0051] The main grid 16 incorporates, among other components, transmission lines 45 for
transmission of power supplied by the WPP 12 and other connected power plants to end
users (not shown). For safety, the main grid 16 also incorporates protection means,
in the form of a plurality of automatically reclosing circuit breakers 46, at intervals
along each transmission line 45. These line breakers 46, which are also known as 'reclosers'
operate to prevent damage to the system 10 if an event occurs that leads to a sudden
and unexpected voltage change, such as a short circuit. This protection is achieved
by opening the line breakers 46 to isolate the section of the transmission lines 45
where the short circuit has occurred. The line breakers 46 automatically reclose the
isolated line 45 after a predetermined time period has elapsed following the opening
of the line breakers 46 so as to bring the line 45 back online following the fault
as quickly as possible.
[0052] The diagram of Figure 1 should only be taken as a representation of a power network.
Alternative configurations of power network and power plants are known and it is expected
that other known components may be incorporated in addition to or as alternatives
to the components shown and described in Figure 1. Such changes would be within the
capabilities of the skilled person. For example, substations or extra transformers
would be expected to be incorporated in the wind power plant depending upon the number
of turbines included in the plurality of wind turbines.
[0053] As discussed in relation to Figure 1, the main grid 16 incorporates a plurality of
line breakers 46 which operate to isolate sections of the transmission line 45 if
a fault event, for example a short circuit, occurs on that section of the line 45.
Line breakers 46 or other circuit breakers may also be used for performing maintenance
on that line section. Short circuits result in dips in the voltage levels of the grid
16, and these dips are also reflected in the voltage level at the Pol 26 between the
grid 16 and the WPP 14. Once the line breakers 46 have isolated the short circuiting
section of the transmission lines 45 from the rest of the grid 16, the voltage levels
can recover.
[0054] As events that result in short circuits are usually temporary, or only semi-permanent
at the very least, the event may quickly clear itself, allowing the transmission line
45 to be brought back 'online' following the outage by re-closing the line breakers
46 to reconnect the isolated, disconnected section of line 45 to the rest of the grid
16. Line breakers 46 automatically reclose after a predetermined time period has elapsed
following an outage so that the line can be offline for as short a time as possible.
If the event has cleared, then the voltage of the grid 16 can be brought back to ordinary
levels. Typically, the time period is around 1.5 seconds which is specified by a grid
operating system.
[0055] However, if the event has not cleared, then the reclosing of the affected section
of transmission line 45 by the line breakers 46 will simply reconnect the short circuit
to the grid 16, causing another dip in voltage levels. The line breakers 46 then open
again, and attempts to reclose again once the time period has elapsed. This leads
to multiple voltage dips, or what is known as a 'recurring fault', and is seen across
the network.
[0056] For example, a short circuit may be caused by a stray tree branch briefly touching
a transmission line. As the tree moves away from the line, the problem will be removed,
the line will be clear to be brought back online, and so automatic reclosing will
be successful. If the tree branch remains in contact with the transmission line, reclosure
of the affected section of the line by the line breakers will only result in another
voltage dip. Multiple voltage dips will occur until the problem has been resolved,
and the fault has cleared.
[0057] To deal with recurring faults, power network interconnection requirements, or grid
codes, have specific criteria that connected WPPs 12 should meet in order to be compliant.
Non-compliance may lead to penalties being imposed on power plant operators, especially
for operators of existing power plants. Compliance is mandatory for new power plants.
An example of these criteria is shown in the %voltage-time chart of Figure 2, which
illustrates the requirements for generating units, i.e. WTGs 14, during automatic
reclosure of a transmission line 45. The WTG controllers 15 and/or PPC 32 are expected
to operate the WTGs 14 to comply with these criteria during recurring faults.
[0058] In Figure 2, a short circuit event occurs at 0 seconds, which may also be referred
to as 't1'. Prior to this event, the WTG 14 is assumed to be operating in its normal
operational range of between 90 % and 110 % of expected voltage, which may also be
written as between 0.9 and 1.1 per-unit voltage (pu).
[0059] As would be understood by the skilled person, per-unit voltage is an expression of
the voltage with respect to a base value which is used as a reference. Using a per-unit
system allows for normalization of values across transformers and other components
that may change the value by an order of magnitude.
[0060] At 0 seconds, the short circuit occurs, and the voltage level of the grid 16 drops
to 0 %, or 0 pu, voltage. Similarly, the voltage level of the WTGs 14 will also drop.
After 0.16 seconds, or 't2', the line breakers 46 act to isolate the short circuit,
and open, after which each WTG 14 is expected to recover back to its pre-fault voltage
level at its terminal. As will be understood by the skilled person, the terminal of
the WTG is the point of connection of that WTG 14 to its local grid (not shown).
[0061] The line breakers 46 are configured to automatically reclose an affected line 45
once a time period of 1.5 seconds has elapsed after they opened, i.e. 1.5 seconds
after t2. As the fault has not yet self-cleared, a second voltage dip occurs 1.66
seconds after the short circuit first occurred. The line breakers 46 respond to re-isolate
the affected line 45 0.16 seconds later, and re-open.
[0062] In the example of Figure 2, it is assumed that the fault clears after the second
dip, and so when the line breakers 46 act to reclose the line 45 at a time of 1.5
seconds after opening for the second time, at 3.32 seconds, there is not another dip.
Instead, it is expected that the WTG 14 will continue to supply active power, maintaining
the 80 % voltage level at least, before returning to ordinary operation between 90
% and 110 % voltage level 10 seconds later at 11.82 seconds.
[0063] It will be appreciated that the times shown in Figure 2 are used as examples only.
Other values may be used as appropriate. The durations after which openings or reclosures
of the line occur are specific to each main grid 16.
[0064] Figure 3 shows a similar chart to that of Figure 2 overlaid with an example of a
conventional low-voltage ride-through (LVRT) protection scheme curve. The curve dictates
the terminal voltage level above which a WTG 14 should be kept connected to the grid
16 or its local grid (not shown) by the WTG controller 15 or PPC 32. If the voltage
level falls below the curve, the WTG 14 should 'trip' and be disconnected, in order
to protect the WTG 14 from sustained low voltage conditions.
[0065] Initially the LVRT curve tracks the fault and, a short period after the opening of
the line, increases linearly from 0 pu to 0.8 pu over a predefined time period. The
relatively slow and slightly delayed rise of the curve means that the conditions for
disconnection of the WTG 14 typically have to constitute a major fault resulting in
sustained low voltages. Once the terminal voltage has reached a predefined exit threshold,
which is slightly below 0.9 pu in this example, the LVRT curve is no longer required
and so effectively 'resets' in preparation for a subsequent fault.
[0066] Ordinarily, when only a single dip results from a fault, the terminal voltage of
the WTG 14 would be expected to rise above 0.8 pu well before the LVRT curve, meaning
that the WTG 14 stays connected to the grid as required. It would be expected that
the terminal voltage would then rise to the exit threshold value to 'reset' the LVRT
curve.
[0067] In contrast, in multiple dip scenarios, even though the WTG 14 should stay connected
to the grid, the presence of a second or later dip will result in a voltage drop that
is below the LVRT curve, and so disconnection of the WTG 14 will result.
[0068] In some situations, in order to deal with multiple dips, LVRT curve exit thresholds
have been lowered to unusually low levels so that the LVRT curve resets prior to the
second dip. However, this too may result in exposure of the WTG 14 to damage as the
exit threshold should be set close to normal operating condition. Interference with
under-voltage protection schemes is also likely in this situation.
[0069] Therefore, the present invention presents a solution to the problem of how best to
account for multiple voltage dips. The present invention utilises a protection scheme
that is operable in addition to the LVRT protection scheme and that integrates with
the LVRT protection scheme to provide adequate protection for WTGs during recurring
fault scenarios. In particular, the present invention utilises the recovery of voltage
as an input to a control method to satisfactorily predict, in real time and in the
period between dips, whether it will be necessary to reset the LVRT curve in preparation
for a second or subsequent dip, as well as predicting whether resetting the curve
is likely to endanger the WTG.
[0070] A representation of the incorporation of the present invention into an existing WTG
protection scheme 100 is shown in Figure 4. In Figure 4, an input voltage, U
s, is queried by a low-voltage protection scheme 102, an under-voltage protection scheme
104 and an over-voltage protection scheme 106. The low-voltage protection scheme 102,
which incorporates the LVRT curve 108 and a timer 110, now includes a 'recurring fault
ride-through' (RFRT) reset protection module 115, operating according to a RFRT reset
method 200, in communication with the timer 110. Any of the low-voltage, under-voltage,
or over-voltage protection systems 102, 104, 106 may output a trip signal, based upon
the input voltage, U
S.
[0071] It can be seen, therefore, that the present invention does not interrupt the operation
of any of the protection schemes 102, 104, 106 but instead supplements the LVRT protection
102 by providing a new, extra level of scrutiny to the terminal voltage, U
s, seen by the WTG 14. Note that the under-voltage protection scheme 104 and the overvoltage
protection scheme 106 are not the focus of the inventive concept described herein,
but are included in this discussion in overview for context and completeness. Similarly,
the override modules 120, AGO trigger 122, and switch 124 for selecting low-voltage,
under-voltage, or AGO are provided for context only.
[0072] Therefore, it will be appreciated that the RFRT reset protection module 115 provides
functionality that is in addition to and complements existing protection functionality
that may be provided in a WTG or power plant controller.
[0073] The RFRT reset method 200, according to which the module 115 and low-voltage protection
system 102 operate, is implemented within a WTG 14 or PPC 32 as a mode of operation,
which may be referred to as RFRT mode, or more simply, 'recurring fault mode'. Recurring
fault mode is entered if a voltage deviation or excursion from normal operational
voltage levels of the main grid 16 is identified, and if it is determined that the
deviation fulfils criteria for automatic reclosure of a transmission line 45 to occur.
If a deviation fulfilling the criteria is determined, the mode is entered and the
recovery of voltage is monitored, categorised into a category according to predetermined
measures, and the correct response is implemented. The correct response is in the
form of a ride-through protocol.
[0074] In other words, the mode and method 200 is implemented to operate a WTG 14 to account
for recurring faults caused by automatic reclosure, and the recurring fault mode serves
the purpose of balancing a compromise between allowing for a recurring fault and protecting
WTGs from inadequate grid conditions. If, having identified a deviation of voltage
levels and determined that recurring faults are possible, the grid condition is sufficient
to ensure safety of the WTG, then recurring faults are catered for. However, the safety
of the WTG takes precedence over accounting for recurring faults, so unstable grid
conditions are countered with the established LVRT protection scheme.
[0075] For sufficient protection, the voltage level attained following the dip, the speed
at which that voltage level was attained, and the stability of the voltage level at
the terminal should all be considered before a ride-through protocol is decided upon.
These 'tests' may form the basis for the categorisation.
[0076] The recurring fault mode is preferably carried out for each individual WTG at respective
WTG controllers, although it is possible that the method may also be performed by
the PPC, by an intermediate controller, or by a remote controller.
[0077] An example of a method that can be used to categorise the recovery of voltage levels
following a fault as described above is shown in Figure 5. The method 200 of Figure
5 categorises voltage recovery into one of two categories: 'weak recovery' or 'strong
recovery'. Weak voltage recovery indicates that the recovery of the voltage is insufficient
and potentially volatile, and that such instability may cause damage to the WTG 14.
During weak recovery, therefore, the WTG 14 is controlled according to the conventional
LVRT protection scheme. Strong recovery indicates that the recovery of the voltage
is stable and sufficient to permit resetting of the LVRT protection scheme to account
for recurring faults.
[0078] The method 200 of Figure 5 is begun if it is identified that a deviation of voltage
level from normal operational voltages has occurred, and this step may also form the
initial step of the method, despite not being shown here. Once the method 200 has
been begun, it is determined 202 whether the deviation fulfils the criteria for automatic
reclosure by comparing the level to which the voltage has dipped, U
retained, at time t1, to a lower voltage threshold, LVT. The LVT is a predetermined level
set by operators of the main grid 16, and is the level that voltage must dip below
for automatic reclosure to be implemented. The LVT may also by altered by the grid
operator based on the condition of the grid. Any changes to this value will be communicated
to the PPC 32 and the WTG controllers 15 by the TSO 36.
[0079] If, in this step 202, it is determined that the LVT is not crossed by the voltage
level, then ordinary LVRT procedures are followed 204. The threshold for LVRT protection
schemes to be implemented is assumed to be higher than the LVT.
[0080] If it is determined by this step 202 that U
retained is less than LVT, the recurring fault ride-through (RFRT) sequence, or recurring
fault mode, is implemented 206, and the WTG 14 is operated according to it. The recurring
fault mode and LVRT protection schemes operate in tandem, and the recurring fault
mode can be considered to augment the LVRT protection scheme. The recurring fault
mode may be terminated at any point based upon the method 200.
[0081] Having activated 206 the recurring fault mode, the first test, also first analysis
208, of the recovery is performed 208 between time t2 and time t3. Time t2 is the
point at which the affected transmission line 45 is isolated by opening the line breakers
46, and so will be a known variable for the WTG controllers 15. Time t2 is typically
calculated relative to time t1 and is set by the grid operator according to grid conditions.
Time t3 is also a fixed time period and is set relative to t1. Time t3 is determined
for the WTG 14, WPP 12 or grid 16 as required, and is variable such that it can be
altered based on the conditions of the system 10 and requirements of the operator
as will be discussed later.
[0082] Returning to the first analysis 208 of the method 200, the recovery voltage, U
recovery, is compared with the LVT to identify whether the voltage level has returned above
this threshold following the dip within the time period between t2 and t3. U
recovery is the actual measured voltage level that is achieved following the removal of the
first dip, after t2. If the recovery voltage is above the low voltage threshold at
any point between t2 and t3, then the second analysis 210 is performed. If, for the
entire time between t2 and t3, the voltage does not achieve a level above LVT, then
the voltage recovery is categorised 212 as weak, the recurring fault mode is terminated,
and the conventional LVRT scheme is followed 204.
[0083] The second test, also second analysis 210, is performed upon identification that
the recovery voltage was above the low voltage threshold within the time period between
t2 and t3, i.e. between the opening of the line on which the fault is identified and
the time period set by the system for the purpose of categorisation of the recovery.
The second analysis 210 identifies when the recovery voltage first crosses an upper
voltage threshold (UVT). The UVT is a predetermined threshold that is greater than
the LVT but lower than the exit threshold for the LVRT scheme. The UVT can be set
according to grid conditions or according to the WPP operation or interconnection.
The UVT may be specified by the TSO 36 or by the WPP operator.
[0084] The time measured from t2 to the first crossing of the UVT is labelled t
recovery*. If t
recovery* is less than t3-t2, then the third analysis or test 214 is performed. If t
recovery* is greater than t3-t2, then the voltage recovery is categorised 212 as weak, the
recurring fault mode is terminated, and the conventional LVRT scheme is followed 204.
Therefore, this second analysis 210 deals with the speed of the recovery.
[0085] If the first two analyses 208, 210 have identified that the voltage recovery is not
weak, then the third analysis 214 is performed. The third analysis 214 identifies
the stability of the voltage recovery at the UVT. By considering the oscillatory movement
of the voltage level about the UVT, the stability of the recovery can be monitored
and determined prior to the reclosure of the line by the line breakers 46.
[0086] The third analysis 214 comprises counting 216 the crossings of the UVT by the recovery
voltage in the time period between time t3 and time t4. Put another way, this means
that every time U
recovery= UVT, the count increases, provided those crossings are between t3 and t4. Time t4
is a time calculated to be fractionally before the reclosure of the line 45 by the
line breakers 46. As the time of the reclosure is known relative to t2 and t1, t4
can be set to be just before this reclosure.
[0087] As prior to the third analysis 214 the voltage level has exceeded UVT, a subsequent
crossing will bring the voltage level below the UVT. Similarly, all odd number of
crossings according to the count of the third analysis 214 at this step will be a
dip in the voltage, while even numbered crossings will indicate the voltage level
rising about the UVT. Therefore the third analysis 214 also comprises the step 218
of identifying if the count is an even integer. If the count is not even, then the
voltage level will be below the UVT prior to the next voltage dip, and the voltage
recovery is categorised 212 as weak. If the count is 0 or even, then the voltage recovery
is above the UVT immediately before the next dip, and the voltage recovery can be
categorised 220 as strong recovery. As the voltage recovery is strong, then recurring
faults can be accommodated, and so the LVRT curve is reset 222 at t4 so that the next
dip does not disconnect the WTG.
[0088] Thus, more generally, the recurring fault mode may be considered to carry out monitoring
of the recovery, categorisation of the recovery into a category such as strong recovery
or weak recovery, and implementing an operation of the WTG 15 according to ride-through
protocol. It should be noted that although only strong and weak recovery are discussed
here, it may be useful to incorporate more categories to permit different actions
to be taken based upon the conditions of the system.
[0089] Examples of different recoveries are shown in Figures 6 to 9. Figures 6 and 8 show
different scenarios in which voltage recoveries might be categorised as strong, while
Figures 7 and 9 show scenarios in which voltage recoveries might be categorised as
weak.
[0090] In each of Figures 6 to 9, a fault occurs at t1, and the voltage deviation from operating
voltage is sufficient to fulfil the criteria set out in the first step 202 of the
method 200 of Figure 5. That is to say, that in each of Figures 6 to 9, the recurring
fault mode is activated 206 and followed according to the steps of Figure 5.
[0091] Furthermore, in each of Figures 6a to 9, it is assumed that the line breakers 46
are opened at t2 and result in a voltage recovery as the short circuit is isolated.
It is also assumed that reclosure happens very shortly after t4. Finally, these Figures
are only concerned with the recovery following the first dip, and so the recovery
of the second dip is shown as being the ideal case, in which the voltage level returns
to a level above UVT instantaneously and remains at this level for a while before
returning to pre-fault levels after a set time period. It will be appreciated that
multiple dips may occur if the fault is not cleared following the second dip, and
so the method 200 of Figure 5 may be repeated as many times as necessary.
[0092] Focussing initially on Figure 6a, with reference to Figure 5, the voltage deviation
occurs at t1, recurring fault mode is activated 206, and the line breakers 46 are
opened at t2 as discussed above. A voltage recovery is shown between t2 and t3. The
voltage recovery crosses the LVT, and so passes the first test 208 of Figure 5. UVT
is also crossed by the voltage recovery, and this is crossed before t3, meaning that
the second test 210 of the recurring fault mode of Figure 5 is passed. Finally, the
same voltage level is maintained above UVT until t4, and so the count for recovery
voltage being UVT is 0.
[0093] The final test 214 is therefore passed, and the recovery can be categorised 220 as
strong. In this case, the LVRT curve is reset 222 at t4, although this is not shown
in Figure 6a. The WTG 14 will stay connected through the second dip.
[0094] Figure 6b shows the effect of resetting the LVRT curve. In Figure 6b, the voltage
levels of Figure 6a are shown by the dashed line, while the LVRT curve is shown in
the solid line. It can be seen that at or between t4 and the second dip, the LVRT
curve is reset to its lowest point, and the count before the slow ramp up of the LVRT
curve is restarted.
[0095] Also shown in Figure 6a, and in Figure 7, is a shaded area between t2 and t3. This
shaded area indicates the region through which an initial recovery should pass in
order to be considered strong. If the recovery does not lie in this region, the recovery
is automatically considered weak, regardless of the later recovery.
[0096] In Figure 7, the voltage deviation occurs at t1, and the line breakers 46 are opened
at t2. The recovery reaches the LVT, and so the first test 210 is passed. However,
UVT is reached after t3, so the recovery time is greater than t3-t2. The second test
212 is not passed, and the recovery is categorised 212 as weak. It can be seen that
the weak initial recovery falls outside the shaded area. Therefore, the LVRT curve
is not reset prior to the second dip in this scenario, and the second dip will result
in the LVRT curve tripping and disconnection of the WTG 14.
[0097] Figure 8 shows a strong recovery, where oscillations occur following the initial
recovery above UVT. It can be seen that the recovery of the voltage level between
t2 and t3 passes the first and second tests 208, 210 of the recurring fault mode,
and that between t3 and t4, the voltage level is equal to UVT at two times, once when
descending below UVT and once when returning above UVT. Therefore, as the count of
UVT = U
recovery is 2, the recovery is categorised 220 as strong. The LVRT is reset 222 at t4, prior
to the second dip. The WTG 14 will stay connected through the second dip.
[0098] Finally, Figure 9 shows an initial strong recovery, which subsequently turns weak
between t3 and t4. As can be seen, the initial recovery falls within the shaded portion
of the grid, and passes the first two tests 208, 210 of the recurring fault mode.
However, the count of UVT = U
recovery is 3, as the voltage level oscillates between t3 and t4 and falls below UVT at t4.
Therefore, the recovery is categorised 212 as weak, and the LVRT curve is not reset.
Instead, the conventional LVRT protection scheme is followed 204 and the second dip
will result in the LVRT curve tripping and disconnection of the WTG 14.
[0099] Based upon requirements of the operator, t3 may be altered to implement more or less
stringent requirements for strong recovery to be assigned. For example, if a grid
is considered to be a strong grid, the recovery should be fast and stable and so t3
may be reduced. Time t3 may also be set according to grid conditions or may be predetermined
during installation of the WPP 12 to account for the interconnection between the WPP
12 and the main grid 16.
[0100] Furthermore, while t3 is fixed relative to t1, an additional time, t2a, may be included
in some embodiments. Time t2a designates the point at which the recovery initially
crosses the UVT. If this additional time is used, then the third analysis step is
performed between t2a and t4, instead of t3 and t4. This may be particularly useful
in very volatile grid conditions, where the voltage may dip below UVT again before
t3.
[0101] Many modifications may be made to the above examples without departing from the scope
of the present invention as defined in the accompanying claims.
1. Verfahren zum Betreiben einer Windkraftanlage (14), die mit einem Leistungsnetzwerk
(16) verbunden ist, um wiederkehrende Spannungsfehler auf dem Leistungsnetzwerk zu
berücksichtigen, die durch automatische Wiedereinschaltung mindestens eines Leistungsschalters
(46) nach einem Kurzschluss verursacht werden, wobei das Verfahren
das Erkennen einer Abweichung des Spannungspegels des Leistungsnetzwerkes von einem
normalen Betriebsspannungspegel des Netzwerkes;
das Bestimmen, dass die erkannte Abweichung die Kriterien für die automatische Wiedereinschaltung
erfüllt; und
das Betreiben der Windkraftanlage in einem wiederkehrenden Fehlermodus umfasst, wenn
die Kriterien für eine automatische Wiedereinschaltung erfüllt sind, wobei das Verfahren
beim Betreiben der Windkraftanlage im wiederkehrenden Fehlermodus Folgendes umfasst:
Überwachen der Wiederherstellung des Spannungspegels von der Abweichung;
Kategorisieren der Wiederherstellung der Spannung als zumindest starke oder schwache
Wiederherstellung; und
Durchführen eines Ride-Through-Protokolls je nach Kategorie der Wiederherstellung,
wobei das Verfahren dadurch gekennzeichnet ist, dass die Kategorisierung der Wiederherstellung der Spannung die Anwendung eines oder mehrerer
Tests auf die Wiederherstellung umfasst, so dass die Wiederherstellung als starke
Wiederherstellung kategorisiert wird, wenn sie den oder jeden Test besteht, und als
schwache Wiederherstellung kategorisiert wird, wenn sie einen oder mehrere der Tests
nicht besteht.
2. Verfahren nach Anspruch 1, wobei die Abweichung einen Leistungsnetzwerkfehler umfasst
und die Feststellung, dass die Abweichung die Kriterien für eine automatische Wiedereinschaltung
erfüllt, den Vergleich der auf den Fehler folgenden Spannungspegel mit einem vorgegebenen
Wiedereinschaltungsschwellenwert umfasst.
3. Verfahren nach einem der vorstehenden Ansprüche, wobei der mindestens eine Test den
Vergleich des Spannungspegels mit einem ersten Spannungsschwellenwert umfasst, und
wobei der Test bestanden wird, wenn der Spannungspegel den ersten Spannungsschwellenwert
in einer vorbestimmten ersten Zeitspanne überschreitet.
4. Verfahren nach Anspruch 3, wobei der mindestens eine Test das Vergleichen des Spannungspegels
mit einem zweiten Spannungsschwellenwert umfasst, und wobei der Test bestanden wird,
wenn der Spannungspegel den zweiten Spannungsschwellenwert in einer vorbestimmten
zweiten Zeitspanne überschreitet.
5. Verfahren nach Anspruch 4, wobei der zweite Spannungsschwellenwert größer ist als
der erste Spannungsschwellenwert.
6. Verfahren nach Anspruch 4 oder Anspruch 5, wobei die erste und die zweite Zeitspanne
gleichzeitig ablaufen und gleich lang sind.
7. Verfahren nach einem der vorstehenden Ansprüche, wobei der mindestens eine Test das
Vergleichen des Spannungspegels mit einem dritten Spannungsschwellenwert und das Durchführen
einer Zählung der Anzahl von Malen, bei denen der Spannungspegel gleich dem dritten
Spannungsschwellenwert innerhalb einer dritten vorbestimmten Zeitspanne ist, umfasst,
und wobei der Test bestanden ist, wenn die Zählung Null oder eine gerade Zahl ist.
8. Verfahren nach Anspruch 7 in Abhängigkeit von Anspruch 4, wobei der zweite und der
dritte Spannungsschwellenwert gleich sind.
9. Verfahren nach Anspruch 7 oder Anspruch 8, wenn es von Anspruch 4 abhängt, wobei die
dritte Zeitspanne auf die erste Zeitspanne und/oder die zweite Zeitspanne folgt.
10. Verfahren nach einem der vorstehenden Ansprüche, umfassend:
Bestimmen, dass die Spannungsabweichung die Kriterien für eine Niederspannung erfüllt;
und
Eintreten in einen Niederspannungsmodus, wenn die Kriterien für eine Niederspannung
erfüllt sind, wobei der Niederspannungsmodus so konfiguriert ist, dass er gleichzeitig
mit dem wiederkehrenden Fehlermodus läuft, wobei:
wenn die Spannungswiederherstellung als schwache Wiederherstellung kategorisiert wird,
der Schritt der Implementierung eines Ride-Through-Protokolls das Beenden des wiederkehrenden
Fehlermodus und den Betrieb der Windkraftanlage nur im Niederspannungsmodus umfasst.
11. Verfahren nach einem der vorstehenden Ansprüche, umfassend:
Bestimmen, dass die Abweichung die Kriterien für eine Niederspannung erfüllt;
Eintreten in einen Niederspannungsmodus, wenn die Kriterien für eine Niederspannung
erfüllt sind, wobei der Niederspannungsmodus so konfiguriert ist, dass er gleichzeitig
mit dem wiederkehrenden Fehlermodus läuft, und wobei:
wenn die Spannungswiederherstellung als starke Wiederherstellung kategorisiert wird,
der Schritt der Implementierung eines Ride-Through-Protokolls das Ändern des Niederspannungsmodus
umfasst, um einen nachfolgenden Spannungseinbruch zu berücksichtigen.
12. Verfahren nach einem der vorstehenden Ansprüche, umfassend das Erkennen einer weiteren
Spannungsabweichung, und Betreiben der Windkraftanlage im wiederkehrenden Fehlermodus
in Abhängigkeit von der weiteren Spannungsabweichung.
13. Verfahren nach einem der vorstehenden Ansprüche, umfassend die Beendigung des wiederkehrenden
Fehlermodus, wenn die Spannungspegel auf normale Betriebspegel zurückkehren.
14. Windkraftanlage (14) umfassend eine Windkraftanlagensteuerung (15), wobei die Steuerung
Mittel zur Durchführung des Verfahrens nach einem der vorstehenden Ansprüche umfasst.
15. Computerprogrammprodukt, das von einem Kommunikationsnetzwerk heruntergeladen werden
kann und/oder auf einem maschinenlesbaren Medium gespeichert ist und Programmcodeanweisungen
zur Durchführung eines Verfahrens nach einem der Ansprüche 1 bis 13 umfasst.
1. Procédé pour faire fonctionner une éolienne (14) connectée à un réseau de puissance
(16) pour tenir compte des défauts de tension récurrents sur le réseau de puissance
provoqués par la refermeture automatique d'au moins un disjoncteur (46) à la suite
d'un court-circuit, le procédé comprenant les étapes consistant à
identifier un écart du niveau de tension du réseau de puissance par rapport à un niveau
de tension opérationnel normal du réseau ;
déterminer que l'écart identifié remplit les critères pour une refermeture automatique
; et
faire fonctionner l'éolienne dans un mode de défaut récurrent si les critères de refermeture
automatique sont remplis, dans lequel, lors du fonctionnement de l'éolienne dans le
mode de défaut récurrent, le procédé comprend les étapes suivantes :
surveiller la récupération du niveau de tension à partir de l'écart ;
classer la récupération de la tension comme étant au moins une récupération forte
ou une récupération faible ; et
mettre en œuvre un protocole de passage en fonction de la catégorie de récupération,
le procédé caractérisé en ce que la catégorisation de la récupération de la tension comprend l'application d'un ou
plusieurs tests à la récupération de sorte que la récupération est catégorisée comme
récupération forte si elle passe le ou chaque test et est catégorisée comme récupération
faible si elle ne passe pas un ou plusieurs des tests.
2. Procédé selon la revendication 1, dans lequel l'écart comprend un défaut du réseau
de puissance, et la détermination que l'écart remplit les critères pour une refermeture
automatique comprend la comparaison des niveaux de tension à la suite du défaut avec
un seuil de refermeture prédéterminé.
3. Procédé selon une quelconque revendication précédente, dans lequel le au moins un
test comprend la comparaison du niveau de tension avec un premier seuil de tension,
et dans lequel le test est réussi si le niveau de tension dépasse le premier seuil
de tension dans une première durée prédéterminée.
4. Procédé selon la revendication 3, dans lequel le au moins un test comprend la comparaison
du niveau de tension avec un deuxième seuil de tension, et dans lequel le test est
réussi si le niveau de tension dépasse le deuxième seuil de tension dans une deuxième
durée prédéterminée.
5. Procédé selon la revendication 4, dans lequel le deuxième seuil de tension est supérieur
au premier seuil de tension.
6. Procédé selon la revendication 4 ou la revendication 5, dans lequel les première et
deuxième durées sont concomitantes et de même longueur.
7. Procédé selon une quelconque revendication précédente, dans lequel le au moins un
test comprend la comparaison du niveau de tension avec un troisième seuil de tension
et la réalisation d'un comptage du nombre de fois où le niveau de tension est égal
au troisième seuil de tension au sein d'une troisième durée prédéterminée, et dans
lequel le test est réussi si le comptage est zéro ou un nombre pair.
8. Procédé selon la revendication 7 lorsqu'il dépend de la revendication 4, dans lequel
les deuxième et troisième seuils de tension sont identiques.
9. Procédé selon la revendication 7 ou la revendication 8 lorsqu'il dépend de la revendication
4, dans lequel la troisième durée suit au moins une de la première durée ou de la
deuxième durée.
10. Procédé selon une quelconque revendication précédente comprenant :
la détermination du fait que l'écart de tension remplit les critères de basse tension
; et
l'entrée dans un mode basse tension si les critères de basse tension sont remplis,
le mode basse tension étant configuré pour fonctionner en concomitance avec le mode
de défaut récurrent, dans lequel :
si la récupération de tension est catégorisée comme étant une récupération faible,
l'étape de mise en œuvre d'un protocole de passage comprend la fin du mode de défaut
récurrent et le fonctionnement de l'éolienne dans le mode basse tension uniquement.
11. Procédé selon une quelconque revendication précédente comprenant :
la détermination du fait que l'écart remplit les critères de basse tension ;
l'entrée dans un mode basse tension si les critères de basse tension sont remplis,
le mode basse tension étant configuré pour fonctionner en concomitance avec le mode
de défaut récurrent, et dans lequel :
si la récupération de tension est catégorisée comme une récupération forte, l'étape
de mise en œuvre d'un protocole de passage comprend la modification du mode basse
tension pour tenir compte d'une chute de tension ultérieure.
12. Procédé selon une quelconque revendication précédente comprenant l'identification
d'un autre écart de tension et le fonctionnement de l'éolienne dans le mode de défaut
récurrent en relation avec l'autre écart de tension.
13. Procédé selon une quelconque revendication précédente comprenant la fin du mode de
défaut récurrent si les niveaux de tension reviennent à des niveaux opérationnels
normaux.
14. Éolienne (14) comprenant un dispositif de commande d'éolienne (15), le dispositif
de commande comprenant des moyens destinés à mettre en œuvre le procédé selon une
quelconque revendication précédente.
15. Produit programme d'ordinateur téléchargeable depuis un réseau de communication et/ou
stocké sur un support lisible par machine, comprenant des instructions de code de
programme pour mettre en œuvre un procédé selon l'une quelconque des revendications
1 à 13.