BACKGROUND OF THE INVENTION
Field Of The Invention
[0001] This invention relates to electrical induction apparatus, e.g. electric power transformers,
specifically to the dielectric liquid coolants contained therein and especially to
those coolants consisting of or containing as a constituent, polychlorinated biphenyl,
PCB. More particularly, the present invention relates to methods for converting PCB-containing
electrical induction apparatus, e.g. transformers, into substantially PCB-free transformers
in order to qualify said transformers as "non-PCB transformers" under U.S. government
regulations.
Prior Art
[0002] Because of their fire resistance, chemical and thermal stability, and good dielectric
properties, PCB's have been found to be excellent transformer coolants. US-A-2,582,200
discloses the use of PCB's alone or in admixture with compatible viscosity modifiers,
e.g., trichlorobenzene, and such trichlorobenzene-PCB mixtures have been termed generically
"askarels". These askarels may also contain minor quantities of additives such as
ethyl silicate, epoxy compounds and other materials used as scavengers for halogen
decomposition products which may result from potential electric arcing. ASTM D-2283-75
describes several types of askarels and delineates their physical and chemical specifications.
[0003] However, PCB's have been cited in the U.S. Toxic Substances Control Act of 1976 as
an environmental and physiological hazard, and because of their high chemical stability
they are non- biodegradable. Hence, they will persist in the en- vironmentand are
even subject to biological magnification (accumulation in higher orders of life through
the food chain). Accordingly, in the U.S., transformers are no longer made with PCB
or askarel fluids. While older units containing PCB may still be used under some circumstances,
it is necessary to provide special precautions such as containment dikes and maintain
regular inspections. Transformers containing PCB's are at a fur- therdisadvantage
since maintenance requiring the core to be detanked is prohibited, and the transformer
owner remains responsible for all environmental contamination, including clean-up
costs, due to leakage, tank rupture, or other spillage of PCB's, or due to toxic by-product
emissions resulting from fires. To replace a PCB-containing transformer, it is necessary
to (1 ) removethetrans- former from service, (2) drain the PCB and flush the unit
in a prescribed manner, (3) remove the unit and replace with a new transformer, and
(4) transport the old transformer to an approved landfill for burial (or to a solid
waste incinerator). Even then, the owner who contracts to have it buried still owns
the transformer and is still responsible (liable) for any future pollution problems
caused by it. Liquid wastes generated during replacement must be incinerated at special
approved sites. Thus replacement of a PCB transformer can be expensive, but more importantly,
since most pure PCB or askarel transformers are indoors, in building basements or
in special enclosed vaults with limited access, it may not be physically feasible
to remove or install a transformer, nor would it be desirable from an asset management
perspective.
[0004] A desired approach to the problem would be to replace the PCB oil with an innocuous,
compatible fluid. A number of fluid types have been used in new transformers as reported
in Robert A. Westin, "Assessment of the Use of Selected Replacement Fluids for PCB's
in Electrical Equipment", EPA, NTIS, PB-296377, March 1,1979; J. Reason and W. Bloomquist,
"PCB Replacements: Where the Transformer Industry Stands Now", Power, October, 1979,
p. 64-65; Harry R. Sheppard, "PCB Replacement in Transformers", Proc. of the Am. Power
Conf., 1977, pp. 1062-68; Chem. Week, 130, 3, 24 (1/20/82); A. Kaufman, Chem. Week,
180 9, 5 (3/3/82) ; CMR Chem. Bus., October 20, 1980, p. 26; Chem. Eng., July 18,
1977, p. 57; Belgian Patent 893,389; Europ. Plastic News, June, 1978, p. 56. Among
these are silicone oils, e.g., polydimethylsiloxaneoils, modified hydrocarbons (for
high flash points, e.g. RTEmp, a proprietary fluid of RTE Corp.), synthetic hydrocarbons
(poly-alpha-olefins), high viscosity esters (e.g. dioctyl phthalate and PAO-13-C,
a proprietary fluid of Uniroyal Corp.), and phosphate esters. A number of halogenated
alkyl and aryl compounds have been used. Among them are the liquid trichloro- and
tetrachlorobenzenes and toluenes and proprietary mixtures thereof (e.g. liquid mixtures
of tetrachlorodiarylmethane with trichlorotoluene isomers). Liquid mixtures of the
trichloro- and tetrachlorobenzene isomers are particularly suitable because of their
low flammabilities (e.g., high fire points) and similar physical and chemical properties
to askarels being removed. Other proposed fluids are tetrachloroethylene (e.g. Diamond
Shamrock's Perclene TG) and polyols and other esters.
[0005] Of all the non-PCB fluids, silicone oils have been the most widely accepted. Their
chemical, physical, and electrical properties are excellent. They have high fire points
(>300°C), and no known toxic or environmental problems. These oils are trimethylsilyl
end-blocked poly(dimethyl- siloxanes) :

wherein n is of a value sufficient to provide the desired viscosity, e.g., viscosity
at 25° C of about 50 centistokes. Commercial silicone oils suitable for use are available
from Union Carbide (L-305), and others. In addition US-A-4,146,491, GB-A-1,540,138
and G B-A-1,589,433 disclose mixtures of silicone oils with a variety of additives
to improve electrical performance in capacitors, transformers and similar electrical
equipment, and disclose polysiloxanes with alkyl and aryl groups other than methyl.
[0006] Replacement of PCB-containing askarels in older transformers with silicone oils or
one of the other substitute fluids would seem to be a simple matter, but it is not.
A typical transformer contains a great deal of cellulosic insulating material to prevent
electrical coils, etc., from improper contact and electrical arcing. This material
is naturally soaked with askarel, and may contain from 3 to 12% of the total fluid
volume of the transformer. This absorbed askarel will not drain out, nor can it be
flushed out by any known means, however efficient. Once the original bulk askarel
is replaced with a fresh non-PCB fluid, the slow process of diffusion permits the
old absorbed askarel to gradually leach out, and the PCB content of the new fluid
will rise. Thus, the new coolant becomes contaminated.
[0007] For purposes of classification of transformers, the U.S. government regulations have
designated those fluids with greater than 500 ppm PCB as "PCB transformers", those
with 50-500 ppm PCB as "PCB contaminated transformers", and those with less than 50
ppm PCB as "non-PCB transformers". While major expenses may be entailed with the first
two classifications in the event of a spill or the necessity of disposal, the last
category is free of U.S. government regulation. To achieve the last classification,
the PCB concentration must remain below 50 ppm for at least 90 days, with the transformer
in service and sufficiently energized that temperatures of 50° C or higher are realized.
This requires a 90-day averaged rate of elution of about 0.56 ppm/day. It is anticipated
that most, if not all, states of the U.S. will adopt regulations which may be the
same as, or stricter, than U.S. government regulations. More lenient regulations may
be possible elsewhere.
[0008] There are a number of commercial retrofill procedures on the market including those
described in "The RetroSil PCB Removal System", Promotional literature of Dow Corning
Corp., #10-205-82 (1982), and trade literature of Positive Technologies, Inc. on the
Zero/PC/Forty process. These utilize clean-out procedures of as high efficiency as
possible during which the electrical apparatus is not in operation. Most include a
series of flushes with liquids such as fuel oil, ethylene glycol, or a number of chlorinated
aliphatic or aromatic compounds. Trichloroethylene is a favorite flush fluid. Some
processes, such as the Positive Technologies, Inc. Zero/PC/Forty process use a fluorocarbon
vapor scrub alternating with the liquid flushes. When the initial clean-out procedure
is complete, the transformer is filled with silicone fluid. As effective as these
elaborate flushing procedures might have been expected to be, they cannot remove PCB
adsorbed into the interstices of the cellulosic material. Consequently, the PCB content
of the silicone coolant gradually rises as the residual PCB leaches out while the
transformer is in use. Therefore, if one wishes to reach a PCB-free state ("non-PCB"
as defined by U.S. government regulation), it is necessary to either periodically
change-out, or continually clean up, the silicone fluid until a leach rate of less
than 50 ppm for 90 days is reached.
[0009] Periodic change-out is very expensive, and because both the silicone and PCB are
essentially non-volatile, distillation cannot be used to separate them is not practicable
and other methods of separation are expensive or ineffective. Dow Corning in its RetroSil
process uses a continual carbon filtration to clean up the fluid ("The RetroSil PCB
Removal System", Promotional literature of Dow Corning Corp., #10-205-82 (1982); Jacqueline
Cox, "Silicone Transformer Fluid from Dow Reduces PCB Levels to EPA Standards", Paper
Trade Journal, Sept. 30, 1982; T. O'Neil and J.J. Kelly, "Silicone Retrofill of Askarel
Transformers", Proc. Elec./Electron. Insul. Conf., 13, 167-170 (1977); W.C. Page and
T. Michaud, "Development of Methods to Retrofil Transformers with Silicone Transformer
Liquid", Proc. Elec./Electron. Insul. Conf., 13, 159-166 (1977). Westinghouse in US-A-4,124,834
has patented a transformer with a filtration process for removing PCB from the coolant,
while RTE in European Patent 0023111 has described the use of chlorinated polymers
as an adsorbing media. However, the filters used in these processes are very expensive
and the removal of PCB is very ineffective, due both to lack of selectivity and the
very low concentrations of PCB being filtered. In lieu of filtration, procedures have
been proposed involving decantation (US-A-4,299,704) which is impractical due to solubility
limitations, and only good at high concentrations; extraction with polyglycols (F.J.
laconianni, A.J. Saggiomo and S.W. Osborn, "PCB Removal from Transformer Oil", EPRI
PCB Seminar, Dallas, Texas, December 3, 1981) or with supercritical CO
2 (Richard P. de Filippi, "C0
2 as a Solvent: Application to Fats, Oils and Other Materials", Chem. and Ind., June
19, 1982, pp. 390-94), and chemical destruction of the PCB's with sodium (British
Patent 2,063,908). None of these schemes have been found to be economically or commercially
practical for askarel transformers. However, the filtration scheme could be a reasonably
effective, though expensive, procedure if it were not for the fact that the leach
rate is so slow that it could take many years to reduce the residual PCB to a point
where the final leach is reduced to an acceptable value (Gilbert Addis and Bentsu
Ro, "Equilibrium Study of PCB's Between Transformer Oil and Transformer Solid Materials",
EPRI PCB Seminar, December 3, 1981).
[0010] The problem and its cause are discussed in L.A. Morgan and R.C. Ostoff, "Problems
Associated with the Retrofilling of Askarel Transformers", IEEE Power Eng. Soc., Winter
Meeting, N.Y., N.Y., Jan. 30 - Feb. 4, 1977, pap. A77, p. 120-9. The solubility of
a typical silicone oil in PCB is practically nil (<0.5%) at temperatures up to and
over 100° C, while the solubility of PCB in the silicone ranges from only 10% at 25°
C to 12% at 100° C. While this limited solubility does not restrict the bulk silicone
from dissolving the available free PCB, it does restrict the ability of the PCB to
diffuse from the pores or interstices of the cellulosic matter.
[0011] Within any given pore filled with PCB, diffusion of PCB out must be accompanied by
diffusion of silicone in. At some point within the pore there must exist an interface
between the PCB and the silicone, across which neither material can very rapidly diffuse.
Because the PCB is more soluble in the silicone than the reverse, the PCB will slowly
diffuse into the silicone while the interface advances gradually into the pore. The
limited solubility restricts the rate of diffusion and while this mechanism can eventually
clean the pore of PCB, it is orders of magnitude slower than if the two fluids were
miscible. The high viscosity of the silicone (and many other coolants) is also an
inhibiting factor. The result is a long drawn-out leach period of perhaps several
years, during which the silicone must be continually filtered or periodically replaced
to remove PCB's from it. Thus, the slow leaching of PCB's out of the solid insulation
by the silicone is worse than no leaching at all since the dangers of a spill of PCB-containing
materials will persist over a period of years. Experimental studies by Morgan and
Osthoff showed, for example, that effective PCB diffusivities into a typical silicone
oil were only 1/10 of those into a 10 centistoke hydrocarbon oil. Although one might
prefer, then, to retrofill with such a hydrocarbon oil, if it were not for the fire
hazard of hydrocarbons, there still also is the problem of separating the PCB from
the contaminated hydrocarbon oil which is high boiling like the PCB and like the silicone
oil.
[0012] The present invention is based on the fact that there are suitable cooling fluids
which are more suitable than silicone oil for operation over a limited time while
leach is being accomplished. They are reasonably volatile for distillation from PCB,
readily miscible therewith, and of relatively low viscosity for rapid diffusion into
the pores of the insulation. The other constituents of askarel, i.e. trichlorobenzene
and tetrachlorobenzene, are found to be ideal fluids for this purpose. They can be
used as temporary or interim, leaching, cooling fluids where fire may be a potential
hazard, while light hydrocarbons could be used if fire is not a hazard.
[0013] No prior art has been found to disclose the concept of producing a substantially
PCB-free transformer by removing, flushing and eluting askarels from transformers
containing same with an interim dielectric liquid or the steps of filling the transformer
tank with an interim dielectric cooling liquid that is miscible with the PCB contained
by the transformer tank, capable of penetrating said electrical insulation and capable
of being separated from the PCB or the step of electrically operating the transformer
while eluting PCB with an interim dielectric liquid and continuing the electrical
operation for a period sufficient to elute the PCB impregnated in the solid insulation
into the interim dielectric cooling liquid, draining the PCB-laden interim coolant,
repeating the cycle of filling with fresh interim coolant, electrically operating
and draining a sufficient number of times until the elution rate of PCB drops below
the rate of 50 ppm, based on the weight of the permanent coolant to be used, after
90 days electrical operation, whereafter the coolant then is drained from the transformer
and thereafter separated from the PCB contained by it thus permitting filling of the
tank with a PCB-free permanent dielectric cooling liquid which remains substantially
PCB-free during subsequent electrical operation.
SUMMARY OF THE INVENTION
[0014] The present invention is based upon the use of a suitable temporary or interim cooling
liquid as a substitute for PCB-containing coolants in electrical induction apparatus,
e.g. transformers, having a vessel (e.g. tank) containing the coolant and an electrical
winding and porous solid cellulosic electrical insulation immersed in and impregnated
with PCB while electrically operating the transformer for a sufficient period of time
to elute the PCB from the solid electrical insulation contained in the transformer.
During the period of operation, the interim dielectric cooling liquid is changed to
speed up the elution process, the preferred goal being to elute so much of the leachable
PCB that the transformer can be operated for 90 days and not exceed 50 ppm PCB content
in the permanent coolant intended for the transformer. After the amount of leachable
PCB in the transformer has been reduced to this desired degree, the interim dielectric
cooling liquid is removed from the tank and the tank is then filled with a PCB-free
permanent dielectric cooling liquid compatible with the transformer. The following
describes a procedure according to this invention by which a PCB-containing fluid
in a transformer is replaced with a permanent PCB-free liquid coolant:
(1) The transformer is shut down (de-energized) and the PCB-containing fluid drained
and disposed of in accordance with environmentally acceptable procedures. The transformer
may be flushed with a flushing fluid, e.g., trichlorobenzene or trichloroethylene,
liquid or vapor, to remove "free" PCB fluid.
(2) The transformer is filled with a temporary or interim cooling fluid, such as trichlorobenzene,
TCB, or a mixture thereof with tetrachlorobenzene, which is miscible with or dissolves
PCB and is capable of penetrating into the pores of the electrical insulation and
which is also capable of being readily separated from the PCB, and electrical operation
is restored.
(3) The fluid temperature is monitored, and if the electrical loading of the transformer
does not provide sufficient fluid temperature to provide the desired rate of PCB elution,
thermal lagging or even external heating can be provided. Circulation of the fluid
through an external loop and pump for the purpose of heating same, or for augmenting
the internal circulation, may also be provided.
(4) The rate of PCB elution into the interim cooling fluid can be determined by periodic
sampling and analysis. The accumulated PCB is periodically removed by removing the
interim cooling fluid containing the PCB and distillation of the interim cooling fluid,
e.g., trichlorobenzene (TCB) from the PCB. This may be done by shutting down, de-energizing,
thetransformer, draining the old fluid for distillation, and replacing with fresh
interim cooling fluid, e.g., TCB. Alternatively, the transformer may be left operational
while fresh interim cooling fluid, e.g., TCB, is added and old TCB removed via a slip
stream or circulation loop.
(5) The PCB-contaminated TCB fluid is distilled to provide an essentially PCB-free
TCB distillate, and a bottom product of PCB contaminated with TCB. The PCB may be
disposed of according to approved U.S. government procedures, e.g., by incineration.
(6) When the elution rate of PCB reaches the desired level, preferably less than 50
ppm PCB based on the weight of the intended permanent coolantfor a period of 90 days
(e.g., an elution rate of 5/9 ppm per day), the permanent retrofill may be accomplished.
The transformer is shut down (deenergized), drained, and filled with the silicone
oil or other permanent cooling fluid compatible with the transformer. It is then returned
to service.
(7) In order to meet U.S. government regula- tionsfor "non-PCB" transformers, analysis
should show a PCB content of less than 50 ppm PCB (based on the weight of the intended
permanent coolant) after a period of 90 days, after which the transformer is reclassified
as PCB free (i.e. "non-PCB").
[0015] With respect to the flushing step, while efficient draining and flushing techniques
should be used, these do not in themselves constitute the invention, but are a part
of all heretofore known retrofill procedures. They are a prelude to the most efficient
embodiment of the invention itself, but their value heretofore has been overrated,
in that it is the slow leach rate, not the efficiency of flush which has been found
to limit the rate of PCB removal. A wide variety of solvents may be used in the flushing
step, including hydrocarbons such as gasoline, kerosene, mineral oil or mineral spirits,
toluene, turpentine, or xylene, a wide range of chlorinated aliphatic or aromatic
hydrocarbons, alcohols, esters, ketones, and so forth. However, from a materials handling
standpoint and PCB separation logistics, it is practical to avoid using any more chemical
types than necessary, so that the use of the intended temporary leach fluid, e.g.,
TCB or mixtures thereof with tetrachlorobenzene, as the initial flush is most practical.
[0016] Fluids other than normally liquid trichlorobenzene, TCB, or a mixture thereof with
tetrachlorobenzene, can be used. The preferred interim fluid has the following characteristics:
(a) it is compatible with PCB (i.e. preferably dissolving at least 50% of its weight
of PCB, more preferably, at least 90% of its weight of PCB and, most preferably, being
miscible in all proportions with PCB); (b) it is of low enough molecular weight to
have good molecular mobility to be able to enter the pores or interstices of the solid
insulating material and it promotes rapid mutual diffusion, preferably, having a viscosity
at 25° C of 10 mm
2/s or less and, more preferably, 3 mm
2/s or less; (c) it can be easily separated, e.g. distilled, preferably, having a boiling
point of 275° C or less and, more preferably, 260° C or less, from PCB; (d) it is
presently considered environmental innocuous; and (e) it is compatible with typical
transformer internals. While TCB, or mixtures with tetrachlorobenzene, is preferred,
a number of alternatives, as above- mentioned can be used. These would include modified
and synthetic hydrocarbons, and a variety of halogenated aromatic and aliphatic compounds.
There are also a variety of liquid trichlorobenzene isomer mixtures. The preferred
TCB fluid would be a mixture of these isomers with or without tetrachlorobenzene isomers.
The advantage lies in the fact that such a mixture has a lower freezing point than
do the individual isomers, thus reducing the chance of it solidifying within the transformers
in very cold climates. Further, the mixtures are often the normal result of manufacture
and hence can cost less than the separated and purified individual isomers.
[0017] Because the preferred objective here is to leach out the PCB at the fastest practical
rate, the preferred embodiment involves operating the transformer to obtain the fastest
possible diffusion rates as specified in step (3) above. When used at its full rated
loading, a transformer should automatically provide enough heat for this purpose.
However, since many transformers are operated below their rated loading, and below
the rated safe temperature, sufficiently elevated temperatures (e.g. at least 50°
C) might not be achieved without thermal lagging or external heating. While this thermal
control represents a preferred embodiment of this invention, it is optional and not
an essential requirement, there being many transformers for which such lagging or
heating may be impractical. Leaching at lower temperatures, even ambient, is workable
but will take longer.
[0018] Fluid circulation as specified in step (3) is optional but is an advantageous embodiment
in that such circulation will prevent the buid-up of concentration gradients which
can act to retard diffusion. Since elution is a slow process, the circulation rate
need not be very rapid. Violent circulation, of course, is to be avoided in order
to avoid damage to the internal structure of the transformer. It is recognized that
many transformers may not, by their construction or placement, be readily modified
to utilize a circulation loop, and such circulation is not considered a necessary
aspect, but only one embodiment of this invention to increase elution rates. In most
transformers, natural thermal gradients alone will induce sufficient circulation especially
in those cases where a relatively low viscosity, mobile coolant, such as TCB, is used.
[0019] As the PCB content in the TCB or other interim coolant in the transformer builds
up, it can eventually reach a point where diffusion no longer serves to leach PCB
from the cellulosic pores or interstices of the insulation within the transformer
tank. A reduction in elution rate as determined by sample analysis is a clue that
this may be occurring. If it is determined that this is occurring, it may become necessary
as specified in step (4) to replace the PCB-laden interim dielectric cooling fluid
with fresh PCB-free fluid. This is most easily accomplished by shutting down the transformer,
draining out the contaminated leach fluid (interim dielectric coolant), and replacing
it with fresh fluid. As a practical matter, instead of monitoring the elution rate
to determine when diffusion no longer serves to effectively leach PCB from the pores
or interstices of the electrical insulation, it is more practical to schedule the
transformer for regular coolant changes. If a non-PCB transformer is desired, coolant
changes are made after selected periods of electrical operation, until the coolant
fails to elute 50 ppm of PCB per 90 days operation. Periods of electrical operation
between coolant changes can be selected to be 20 days to 1 year (or more, if the transformer
owner's needs prevent shutting down the transformer except at rare specified times,
e.g., special holiday periods, such that there may be more than one year between shutdowns
and possibly shutdowns can take place only every other year), preferably 30 to 120
days and most preferably 45 to 90 days.
[0020] The contaminated leach fluid may then be distilled off and condensed for re-use to
leave a PCB bottom product which is incinerated or otherwise disposed of pursuant
to U.S. government regulations. While a complete change of interim coolant is preferred,
it is possible that the inconvenience of additional shutdowns predicates a different
procedure, i.e., that of simultaneously introducing new fresh fluid and removing the
old contaminated fluid while the transformer remains in operation. It is less efficient
because the fresh fluid mixes with the old in the transformer, and fluid of reduced
PCB concentration is actually removed. Thus to eliminate all the PCB, more leach fluid
will have to be removed than for the preferred procedure. This penalty can be reduced
if one takes pains to avoid excessive mixing. For example, new chilled TCB or other
interim dielectric cooling fluid can be introduced into the bottom of the transformer,
while old, warm, PCB-laden interim dielectric cooling fluid is removed from the top.
The density difference will retard mixing. Regardless of the method used, the process
will require repetition until the desired PCB level, e.g., less than 50 ppm in silicone
oil coolant can be maintained for at least 90 days.
[0021] While distillation is the preferred method for separating TCB or other interim dielectric
coolant and PCB, other methods may be feasible, especially if fluid other than TCB
is chosen as the temporaryfluid. The PCB can be removed from the PCB-laden silicone
oil that may result from step (7) by contacting it (e.g. on-site while step (7) is
being carried out or off-site after PCB-laden silicone oil has been removed) with
activated charcoal, zeolites or other adsorbants capable of adsorbing the PCB from
the silicone oil. Any other method for removing PCB from the spent silicone oil can
be employed.
[0022] There is some concern that TCB itself, or other chlorinated interim dielectric coolant,
such as TTCB and the halogenated solvents, may eventually become suspect as a health
hazard, and that thetransformer, though free of PCB, will be contaminated with TCB
or other potentially objectionable interim fluid. The further advantage of the procedure
of this invention is that such contamination can be easily rectified if necessary,
since the interim TCB or other fluid is more volatile than the silicone or heavy hydrocarbon
fluids, or other relatively high viscosity permanent coolant used in the transformer
and can be distilled therefrom.
[0023] Accordingly, the chlorinated portion of the coolant can be replaced and the old batch
sent to a still for easy purification. Two orthreesuch changes over a period of several
months will give a substantially halogen free system, if one is desired.
[0024] Other preferred coolants of a permanent nature that can be used in place of the final
fill of silicone oil include dioctylphthalate, modified hydrocarbon oils, e.g. RTEmp
of RTE Corp., polyalphaolefins, e.g. PAO-13-C of Uniroyal, synthetic ester fluids,
and any other compatible permanent fluid. It is also preferred that the permanent
dielectric fluid be characterized by a high boiling point compared to said interim
dielectric solvent so that the interim dielectric solvent can be separated from the
permanent fluid if the need arises and also to avoid releasing permanent fluid due
to volatilization in the event the transformer tank is ruptured.
[0025] While the following have been suggested, and in some cases used, as permanent dielectric
fluids, they are less preferred than the relatively high viscosity, high boiling permanent
dielectric fluids: te- trachlorodiaryt methane with or without trichlorotoluene isomers,
freon, halogenated hydrocarbons, tetrachloroethylene, the trichlorobenzene isomers
and the tetrachlorobenzene isomers. The trichlorobenzene isomers, the tetrachlorobenzene
isomers, and mixtures thereof have high flammability ratings and other physical propertiessim-
ilar to askarel and therefore are preferred amongst the less preferred permanent fluids.
[0026] The following examples are presented. In the examples, the following abbreviations
have been used.
TCB trichlorobenzene
TTCB tetrachlorobenzene
TCB mix 30-35 wt. % tetrachlorobenzene, TTCB, in trichlorobenzene, TCB (containing
an effective amount of a chlorine scavenging epoxide-based inhibitor)
PCB polychlorinated biphenyls
ppm parts of PCB or TCB mix per million of coolant based on weight
Askarel Askarel Type A, 60 wt. % Aroclor 1260, 40 wt. % TCB
Aroclor 1260 polychlorinated biphenyl containing 60 wt. % chlorine
L-305 A silicone oil within the scope of formula A above, having a viscosity of 50
mm2/s at 25° C
[0027] A "cycle" is the period of time between changes in the coolant. A "part" of a cycle
is a portion of a cycle where the leach rate into the coolant is markedly different
from the rate in the earlier or later portion of the cycle.
Examples 1, 2, A Band C
[0028] Each of the four transformers identified in Table I were drained, rinsed and filled
with the coolant designated for Cycle 1 in each case in Table I.
[0029] In each case of Examples A and 1, the coolant in the transformer prior to draining
and rinsing was mineral oil (Exxon Univolt inhibited oil, transformer grade) containing
the initial PCB concentration shown in Table I. Transformer #459 and #461 of Examples
A and 1 at one time had been askarel-filled transformers that had been previously
switched to mineral oil and respectively contained 9,150 and 7,800 ppm PCB. Transformer
#459 of Example A was drained, spray rinsed with mineral oil and then filled with
fresh mineral oil. Transformer #461 of Example was drained, spray rinsed with TCB
mix and then filled with fresh TCB mix. The transformers were operated at about 80°
C for the time periods listed in Table I. In Example 1, the transformer was drained
of TCB mix and refilled with TCB mix 2 more times to provide two complete cycles and
one ongoing cycle.
[0030] In Examples 2, B and C, each respective transformer was a member of a bank of three
identical Westinghouse transformers having a rated capacity of 333 KVA each. Each
of these transformers contained about 719 I (190 gallons) of type A askarel that was
a coolant having a 60/40 wt. ratio of Aroclor 1260 (PCB) and trichlorobenzene. These
3 transformers were all tied into the same three- phase bank and were all operated
at the same capacity and otherwise encountered the same conditions except as hereinafter
designated. The normal service of the transformers of Examples 2, B and C was far
below their rating and the annual average operating temperature was around 40° C except
as otherwise designated. Transformer #669 (Example 2) and transformer #667 (Example
C) were drained of askarel, spray rinsed twice with TCB mix and subsequently refilled
with TCB mix. Transformer #668 (Example B) was drained, spray rinsed twice with silicone
oil (L-305) and subsequently refilled with silicone oil, L-305. All transformers were
reenergized and liquid samples were taken periodically to check the PCB content.
[0031] All 5 transformers were operated and PCB concentrations were determined at the end
of the various day intervals indicated in Table I and the daily rate of ppm of PCB
increase in the coolant was calculated and converted to a silicone oil coolant basis
(if not already on such basis) as designated in Table I.
[0032] In Example 2, transformer #669 was operated for 96 days then drained, spray rinsed
with TCB mix and refilled with TCB mix and operation was continued in Cycle 2 and
the same sequence was repeated for Cycles 3 and 4 for the transformer. In Example
2, at the end of Cycle 4 in the case of transformer #669, the transformer was drained
and spray rinsed with TCB mix and thereafter filled with TCB mix and it continued
to be electrically operated. The day intervals, PCB concentrations at the end of the
day intervals and overall rate of elution and converted rate of elution in terms of
ppm per day are given in Table I in respect to each cycle.
[0033] In Example B, transformer #668 was initially drained of askarel, spray rinsed twice
with L-305 and filled with fresh L-305. At the end of the 390th day the transformer
was again drained, spray rinsed with L-305 and subsequently filled with fresh L-305
and continued to operate in Cycle 2. The day intervals, PCB concentration at the end
of the day intervals, and the overall rates of elution in ppm per day are correspondingly
listed in Table I.
[0034] Transformer #667 (Example C) was initially drained of askarel, spray rinsed twice
with TCB mix and filled with TCB mix. At the end of the 96th day, it was drained,
spray rinsed and filled with fresh TCB mix. Subsequent cycles are as indicated in
Table I.

[0035] For Example A, transformer # 459, the leach rate had been reduced to an average PCB
leach rate of 0.36 ppm/day in the second part of the first cycle. This was below the
0.55 ppm/day or 50 parts per million in 90 days required for reclassification as non-PCB.
Accordingly, at day 220, the mineral oil was drained and replaced with the permanent
L-305 silicone coolant. As can be seen from Table I the total PCB removed during Cycle
1 was equivalent to 475 ppm in the volume of coolant held by that transformer. This
is less than the 1220 ppm removed during the same interval of time by TCB mix in #461,
a similar size and type of transformer, and indicates that the mineral oil had not
been as effective a leachant as TCB mix.
[0036] In contrast, transformer #461 was leached with TCB mix. At day 68 the TCB solvent
was drained and reintroduced into the same transformer. At day 165 the TCB mix was
drained and replaced with fresh TCB mix. While the overall rate for Cycle 3 was 1.64
ppm per day, the rate decreased during the cycle and as of day 245 the PCB elution
rate was reduced to 0.05 ppm per day which was well below the target rate of 0.55
ppm PCB per day. Accordingly, the fluid can at this point be replaced with a permanent
silicone coolant.
[0037] Transformer #669 (Example 2) was originally filled with askarel. Hence, it had much
more PCB in the insulation than #461 (Example 1) to be leached. Therefore, it required
many more cycles and a considerably longer period of time to leach to an acceptable
level. When the rate of leach falls below the target rate of 50 ppm in 90 days then
the TCB mix can be replaced by silicone. The rate figures in the last column of Table
I show a continual decrease with time, and the target rate should be reached around
day 600. It should be pointed out that transformers #667, #668 and #669 were expected
to be among the most difficult to leach. They are spiral wound transformers in which
the paper insulation, and hence diffusional path length, can be several inches in
depth. In contrast, many transformers are of the "pancake" design in which path lengths
will be less than an inch.
[0038] Examples B and C, transformers #668 and #667, are comparative examples because in
Example B the initial coolant used was silicone oil, and in Example C, the change
over to silicone oil was made before the elution reached 0.55 ppm PCB per day.
[0039] Transformers #667 and #669 were filled initially with askarel which was replaced
with TCB mix, while transformer #668 was filled initially with askarel which was replaced
with L-305 silicone oil. Figure 1 compares PCB analyses for the first cycle of these
three transformers. The data have been converted to the total actual grams of PCB
removed. While about 60,000 to 70,000 grams of PCB were quickly removed (within thefirst
28 days), subsequent removal was much slower, and the rates are indicated by the straight
lines drawn through the points. It is presumed that the major quantity of PCB held
up in the looser insulation is easily extracted regardless of solvent, but that it
is the PCB held up in the tighter wound paper and pressboard insulation which is limiting
to the process, and in this case the effectiveness of the eluants differs. Figure
1 shows this difference. While the data points are somewhat scattered due to the difficulties
of precise PCB analysis, it appears that the silicone takes 400 days to remove the
same quantity which the TCB mix can remove in 60 days. A comparison of the slopes
of the lines shows the TCB mix to be about 8.5 to 9.0 times as effective a leachant
as L-305. The key point in this invention is that the ratio of effectiveness is so
high. Thus, a process which might take 5 to 10 years with silicone alone could be
carried out in a much shorter time with an interim coolant such as TCB mix.
[0040] Figure 2 illustrates the effect of the transformer temperature on the rate of PCB
elution. Both 0667 and #669 were at about 40°C during the first cycle. They were changed
out to fresh TCB mix after 96 days. Because winter was approaching and the transformers
were not utilized to that capacity required to keep their temperatures high, it was
anticipated that low temperatures might interfere with the leaching. Accordingly,
0 667 was artificially heated by applying heat to the cooling fins. Transformer #669
was left unheated for comparison. The temperature of #667 averaged about 55°C, while
that of
#669 averaged about 23°C. Again, the data points are quite scattered, but it is clear
that the warmer transformer eluted PCB faster than the colder one by a factor of 1.6.
This factor may not be linear, and, consequently, the rate gain may not be as dramatic
for higher temperatures. Further leaching was carried out at 85°C when possible, and
thus most leaching listed in Table I was done at this higher temperature.
[0041] By way of further example the following illustrative cases of Example 3-5 are presented.
While they do not represent results from actual transformers, they are based upon
the performance to be expected from the process of this invention under the conditions
outlined below for each example as applied to transformers from which it is relatively
easier to elute PCB by the process of this invention than those transformers used
in Examples 1, 2, A, B and C.
[0042] In each of Examples 3-5 there is used a transformer of 757 (200 gallon) fluid volume
capacity, the internals of which hold up to 6 gallons in the cellulosic materials,
i.e., the paper insulating the coils, and which contains 757 I (200 gallons), more
or less, of an askarel of 50% PCB (500,000 ppm), except for Example 4 wherein the
transformer contains 757 I (200 gallons), more or less, of mineral oil containing
10,000 ppm PCB.
[0043] Figures 3 through 5 are plots of concentration of PCB in ppm in interim dielectric
fluid (TCB) in the transformer plotted on a vertical logarithmic scale versus days
elapsed (or soak time) and graphically illustrate the anticipated results sought to
be obtained by this invention.
Example 3:
[0044] In Example 3, the transformer is first deenergized. Then it is drained of its askarel,
the latter being ultimately disposed of in an approved manner. The transformer is
flushed out with a small quantity (e.g. 95 I (25 gallons) ) of trichlorobenzene, so
as to reduce the residual askarel in the free fluid system to 0.5% of its initial
value. The system is then logically inspected for leaky bushings or other physical
problems which may require repair at this time.
[0045] Then the transformer is filled with 200 gallons of trichlorobenzene, TCB (or, alternatively,
a trichlorobenzene-tetrachlorobenzene mixture), is sealed up, and, after appropriate
testing, is reenergized. Because the flush is not totally thorough, the initial PCB
level in the newfluid in thetransformer is anticipated at 2500 ppm, i.e. 0.5% of the
initial PCB levels. It is assumed that the PCB held up in the cellulosic materials
leaches out at a rate varying from 0.001 to 0.01 % per day. While these values may
appear arbitrary, they are probably attainable in easy-to-leach transformers, and
higher or lower rates will only affect the length of time required to accomplish the
total leach, not the basic procedure. The uppermost curve plotted on the graph marked
Fig. 3 shows the concentration (on a logarithmic scale) of PCB that can be expected
to be found in the transformer fluid as a function of time. In actual commercial applications
of the process one would not need to determine all these concentrations. However,
one would want to sample the old fluid being replaced and determine its PCB concentration.
This is shown by the open circles in Fig. 3. While the exact length of the leaching
periods is arbitrary, experience with a given type of transformer will indicate the
most practical period lengths in terms of overall process time and total number of
fluid replacements. In this example, 60 day leach periods are used.
[0046] At the end of 60 days, the transformer is once more deenergized, the fluid is drained,
and a sample taken for analysis. The system may be reflushed with about 95 1 (25 gallons)
of TCB, and the flush fluid, along with the bulk fluid, is taken to a site where the
TCB may be recovered by distillation (and the residual PCB properly disposed of by
EPA approved methods).
[0047] The transformer is refilled with TCB, and this time the initial expected PCB concentration
(due to residual prior fluid) is about 83 ppm. Again the anticipated PCB concentration
follows along the second highest curve in Fig. 3 for the next 60 days (to 120 days),
whereupon the TCB in the transformer is changed as before, with one exception. Since
the drained TCB fluid has a concentration of PCB less than the initial value for the
first fill, the drained fluid need not be sent to the still for separation, but instead
can be used as the initial fill for a second PCB transformer to be converted to an
non-PCB condition. This saves valuable distillation time and energy, as well as transportation
or handling costs.
[0048] The refill process is repeated one more time. Table ll gives a list of the anticipated
analytical results which are represented by the circles on the graph of Fig. 3. It
is clear from the data of Table II and Fig. 3 thatthe fourth refill will not rise
above 50 ppm PCB content, the U.S. government cut-off value for the designation of
non-PCB transformers. Therefore, at the end of 180 days, the transformer is refilled
with its permanent fluid, a silicone oil, e.g., L-305. The PCB value expected to be
reached after another 60 days (240 days) is only 16 ppm, and afterthe prescribed U.S.
government 90 day period (270 days) it is anticipated to be at still only 18 ppm.
Thus, the transformer may be reclassified as a non-PCB transformer.

Example 4:
[0049] In Example 4, 60 day leach periods are used but flushing out of the transformers
is eliminated. It is assumed that 98% of the fluid can be adequately drained, leaving
2% in the transformer. In this case the initial concentrations will be 2% of the previously
drained fluids instead of the 0.5% of Example 3. The procedure of Example 3 is repeated
in this example.
[0050] The results to be expected for Example 4 are given in Table III and are shown in
the graph of Fig. 4. Note that the objective is still obtained and the system can
be refilled with silicone or other permanent oil at 180 days. The lack of highly efficient
flushing is expected to lead to slightly higher PCB contents in the final fluid, but
this does not substantially change the achievement of the goal of a non-PCB transformer.

Example 5:
[0051] The shapes of the concentration curves in Figs. 3 and 4 might lead one to believe
that the fluid changes should be made more often, e.g., every 30 days instead of 60
days. Example 5 is identical to Example 4, except that30 day leach periods are used.
The expected analytical results are given in Table IV and the plots are shown in Fig.
5. The trend is obvious from the graphs of Fig. 5. The initial refill shows a reduction
almost as good as that for Example 4, but subsequently the reductions start to curve
off. The sixth refill can be made with the permanent fluid, and sometime has been
saved, about 30 days, at the expense of the two extra refills with TCB. This example
illustrates the availability of a trade-off of time vs. number of refills, and the
choice depends upon which is valued the most highly for the specific case at hand.

[0052] The present invention is not limited to use in transformers but can be used in the
case of any electrical induction apparatus using a dielectric coolant liquid including
electromagnets, liquid cooled electric motors, and capacitors, e.g., ballasts employed
in fluorescent lights.
1. A method for replacing a coolant containing PCB in an electrical induction apparatus
having a tank containing said coolant, an electrical winding and porous solid cellulosic
electrical insulation immersed in said PCB-containing coolant with a substantially
PCB-free high boiling dielectric permanent coolant to convert said electrical apparatus
into one in which the rate of elution of PCB into said coolant is below the maximum
allowable rate of elution into the coolant of an electrical apparatus rated as non-PCB,
said solid porous electrical insulation being impregnated with said PCB-containing
coolant, said method comprising the steps of:
(a) draining said PCB-containing coolant from said tank to remove a major portion
of said PCB-containing coolant contained by it;
(b) filling said tank with an interim dielectric cooling liquid that is miscible with
said PCB, is sufficiently low in viscosity to circulate within said tank and penetrate
the interstices of said porous solid electrical insulation, and is capable of being
readily separated from said PCB;
(c) electrically operating said electrical induction apparatus and continuing said
electrical operation for a period sufficient to elute PCB contained in said PCB-containing
coolant impregnated in said porous solid insulation therefrom into said interim dielectric
cooling liquid;
(d) thereafter draining said interim dielectric cooling liquid containing said eluted
PCB from said tank;
(e) repeating the cycle of steps (b), (c) and (d) when the rate of elution of PCB
into said interim dielectric cooling liquid exceeds 0.55 ppm of PCB per day based
on the weight of said permanent dielectric coolant; and
(f) filling said tank with a substantially PCB-free permanent coolant selected from
the group consisting of high boiling, high viscosity, silicone oils, synthetic ester
fluids, poly-alpha-olefin oils and hydrocarbon oils so as to reclassify said electrical
apparatus to non-PCB status.
2. Method as claimed in claim 1 wherein the interim dielectric cooling liquid is trichlorobenzene,
tetrachlorobenzene or mixtures of same and the permanent coolant is a dielectric silicone
oil coolant.
3. Method as claimed in claim 1 or 2 wherein each step (c) is continued for 20 days
to 1 year or 30 to 120 days or 45 to 90 days.
4. Method as claimed in claims 1 to 3 wherein, when carrying out step (d) of the previous
cycle and step (b) of the next succeeding cycle, the interim cooling liquid is drained
from the top of the tank while fresh chilled interim dielectric cooling liquid is
fed into the bottom of the tank and while electrical operation of the apparatus is
continued.
5. Method as claimed in claims 1 to 4, wherein the steps (d) and (f) are carried out
by feeding the PCB-free permanent coolant into the bottom of the tank while removing
the interim dielectric cooling liquid in the tank from the top of said tank, and while
electrical operation of the apparatus is continued.
6. Method as claimed in claims 1 to 5, wherein the tank is provided with heat insulation
in order to raise the temperature of the interim dielectric cooling liquid contained
by it during each step (c) while electrically operating said electrical induction
apparatus.
7. Method as claimed in claims 1 to 6, wherein the interim dielectric cooling liquid
in the tank is heated during step (c) while electrically operating the electric induction
apparatus.
8. Method as claimed in claims 1 to 6 wherein during step (c) the interim dielectric
cooling liquid is removed from said tank, heated and returned to said tank while maintaining
sufficient interim dielectric fluid in said tank and electrically operating said electrical
induction apparatus.
9. Method as claimed in claims 1 to 8 wherein the interim dielectric liquid is more
volatile than the PCB and is separated from the contained PCB by distilling off the
interim dielectric cooling liquid.
10. Method as claimed in claims 1 to 8 wherein the interim dielectric cooling liquid
containing PCB eluted from the solid insulation is drawn off from the tank as a slip
stream while electrically operating the electrical induction apparatus adding fresh
interim dielectric cooling liquid substantially equivalent to the amount of PCB-containing
interim dielectric fluid drawn off in the slip stream.
11. Method as claimed in claims 1 to 10 wherein the tank is flushed with a solvent
for the PCB following step (a) and before step (b).
12. Method as claimed in claim 11 wherein the flushing solvent is the same liquid
as the interim dielectric cooling liquid used in step (b).
13. Method as claimed in claim 11 wherein the flushing solvent and the interim dielectric
cooling liquid is trichlorobenzene.
14. Method as claimed in claims 1 to 12 wherein the interim dielectric cooling liquid
is 1,2,4-trichlorobenzene or a mixture of trichlorobenzene and tetrachlorobenzene.
15. Method as claimed in claims 1 to 14 wherein the permanent coolant employed to
fill the tank is a silicone oil.
16. Method as claimed in claim 15 wherein the permanent coolant used in step (f) is
a silicone oil having the following formula:

wherein n is a number of such value providing a viscosity of about 50 mm
2/s at 25° C.
1. Verfahren zum Austausch eines PCB enthaltenden Kühlmittels in elektrischen Induktionsanlagen
mit einem dieses Kühlmittel enthaltenden Behälter einer elektrischen Wicklung und
einer porösen celluloseartigen elektrischen Isolierung, welche in das PCB-haltige
Kühlmittel eingetaucht ist, gegen ein im wesentlichen PCB-freies, hochsiedendes, dielektrisches
Kühlmittel, um diese elektrische Anlage in eine solche zu überführen, in welcher die
Entfernung von PCB in dem Kühlmittel unterhalb des maximal zulässigen Wertes des Kühlmittels
einer als PCB-freien elektrischen Anlage eingestuften liegt, wobei die poröse elektrische
Isolierung mit dem PCB-haltigen Kühlmittel imprägniert ist,
dadurch gekennzeichnet, dass man
a) das PCB-haltige Kühlmittel aus dem Behälter ablässt, um den Hauptteil des PCB-haltigen
Kühlmittels zu entfernen,
b) in den Behälter ein dielektrisches Kühl-Zwischenmedium einfüllt, welches mit PCB
mischbar ist und welches eine ausreichend niedere Viskosität besitzt, um in dem Behälter
zu fliessen und in die Zwischenräume der porösen elektrischen Isolierung einzudringen
und sich leicht von PCB trennen lässt,
c) man die elektrische Induktionsanlage in Betrieb nimmt und ausreichend lang betreibt,
um PCB aus dem PCB-haltigen Kühlmittel, welches sich in der porösen Isolation befindet,
herauszuwaschen und in dem dielektrischen kühlenden Zwischenmedium aufzunehmen,
d) woraufhin das dielektrische kühlende Zwischenmedium, welches das aus dem Behälter
ausgewaschene PCB enthält, abgelassen und
e) die Verfahrensstufen b), c) und d) wiederholt werden, wenn dasAusmass der PCB-Aufnah
- me in das dielektrische kühlende Zwischenmedium 0,55 ppm PCB pro Tag, bezogen auf
das Gewicht des permanenten dielektrischen Kühlmittels, übersteigt und schliesslich
f) der Behälter mit einem im wesentlichen PCB-freien permanenten Kühlmittel in Form
von hochsiedenden, hochviskosen Siliconölen, synthetischen flüssigen Estern, Poly-a-olefinölen
und/oder Kohlenwasserstoffölen gefüllt wird, um die elektrische Anlage als PCB-frei
klassifizieren zu können.
2. Verfahren nach Anspruch 1, worin das dielektrische kühlende Zwischenmedium Trichlorbenzol,
Tetrachlorbenzol oder deren Gemische und das permanente Kühlmedium ein dielektrisches
Siliconöl ist.
3. Verfahren nach Anspruch 1 oder 2, wobei die Verfahrensstufe c) 20 Tage bis 1 Jahr
oder 30 bis 120 Tage oder 45 bis 90 Tage dauert.
4. Verfahren nach einem der Ansprüche 1 bis 3, wobei - wenn die Verfahrensstufe d)
des vorhergehenden Zyklus und die Verfahrensstufe b) des nachfolgenden Zyklus durchgeführt
werden, das Zwischenmedium oben aus dem Behälter abgelassen und frisches gekühltes
dielektrisches Zwischenmedium in den Boden des Behälters eingeführt wird, während
die Anlage in Betrieb ist.
5. Verfahren nach einem der Ansprüche 1 bis 4, worin die Verfahrensstufen d) und f)
ausgeführt werden, indem das PCB-freie permanente Kühlmittel in den Boden des Behälters
eingeleitet wird, während oben das dielektrische Zwischenmedium entfernt wird und
die Anlage in Betrieb ist.
6. Verfahren nach einem der Ansprüche 1 bis 5, worin der Behälter mit einer Wärmeisolation
ausgestattet ist, um die Temperatur des dielektrischen Zwischenmediums während jeder
Verfahrensstufe c) zu erhöhen, während die Anlage in Betrieb ist.
7. Verfahren nach einem der Ansprüche 1 bis 6, worin das dielektrische Zwischenmedium
in dem Behälter während der Verfahrensstufe c) erwärmt wird bei Betrieb der Anlage.
8. Verfahren nach einem der Ansprüche 1 bis 6, worin während der Verfahrensstufe c)
das dielektrische Zwischenmedium aus dem Behälter abgelassen, erwärmt und wieder in
den Behälter rückgeleitet wird, während in dem Behälter ausreichend dielektrisches
Zwischenmedium aufrechterhalten und die Anlage in Betrieb gehalten wird.
9. Verfahren nach einem der Ansprüche 1 bis 8, worin das dielektrische Zwischenmedium
flüchtiger ist als PCB und von dem darin enthaltenen PCB durch Abdestillieren des
dielektrischen Zwischenmediums getrennt wird.
10. Verfahren nach einem der Ansprüche 1 bis 8, worin das dielektrische Zwischenmedium
enthaltend aus der Isolation ausgewaschenes PCB aus dem Behälter als Zweigstrom abgeführt
wird während des Betriebs und frisches dielektrisches Zwischenmedium in einer Menge
im wesentlichen äquivalent zu dem abgezogenen Strom an PCBhaltigem dielektrischem
Zwischenmedium eingespeist wird.
11. Verfahren nach einem der Ansprüche 1 bis 10, worin der Behälter mit einem Lösungsmittel
für PCB nach der Verfahrensstufe a) und vor der Verfahrensstufe b) ausgespült wird.
12. Verfahren nach Anspruch 11, worin das zum Ausspülen verwendete Lösungsmittel die
gleiche Flüssigkeit ist wie das dielektrische Zwischenmedium der Verfahrensstufe b).
13. Verfahren nach Anspruch 11, worin das zum Ausspülen verwendete Lösungsmittel und
das dielektrische Zwischenmedium Trichlorbenzol sind.
14. Verfahren nach einem der Ansprüche 1 bis 12, worin das dielektrische Zwischenmedium
1,2,4-Trichlorbenzol oder ein Gemisch von diesem mit Tetrachlorbenzol ist.
15. Verfahren nach einem der Ansprüche 1 bis 14, worin das permanente Kühlmittel zum
Füllen des Behälters ein Siliconöl ist.
16. Verfahren nach Anspruch 15, worin das permanente Kühlmittel der Verfahrensstufe
f) ein Siliconöl der Formel

ist, worin n einen solchen Wert hat, dass die Viskosität bei 25° C etwa 20 mm
2/s beträgt.
1. Procédé pour remplacer un fluide de refroidissement contenant des PCB dans un appareil
à induction électrique comportant une cuve contenant ledit fluide de refroidissement,
un enroulement électrique et un isolant électrique cellulosique, solide, poreux immergé
dans ledit fluide de refroidissement contenant des PCB, par un fluide de refroidissement
permanent diélectrique, à haut point d'ébullition, pratiquement sans PCB, pour convertir
ledit appareil électrique en un appareil dans lequel la vitesse d'élution des PCB
dans ledit fluide de refroidissement est inférieure à la vitesse maximale admissible
d'élution dans le fluide de refroidissement d'un appareil électrique classé comme
non-PCB, ledit isolant électrique poreux solide étant imprégné dudit fluide de refroidissement
contenant des PCB, ledit procédé comprenant les étapes qui consistent:
(a) à vider ladite cuve dudit fluide de refroidissement contenant des PCB afin de
retirer de cette cuve une partie majeure dudit fluide de refroidissement contenant
des PCB;
(b) à remplir ladite cuve d'un liquide de refroidissement diélectrique intermédiaire
qui est miscible auxdits PCB, est d'une viscosité suffisamment basse pour circuler
à l'intérieur de la cuve et pour pénétrer dans les interstices dudit isolant électrique,
solide, poreux, et est capable d'être aisément séparé desdits PCB;
(c) à faire fonctionner électriquement ledit appareil à induction électrique et à
poursuivre ledit fonctionnement électrique pendant une période suffisante pour, par
élution, faire passer dudit isolant solide poreux dans ledit liquide de refroidissement
diélectrique intermédiaire, les PCB contenus dans ledit fluide de refroidissement
contenant des PCB, imprégné dans ledit isolant solide poreux;
(d) à vider ensuite de ladite cuve ledit liquide de refroidissement diélectrique intermédiaire
contenant lesdits PCB élués;
(e) à répéter le cycle des étapes (b), (c) et (d) lorsque la vitesse d'élution des
PCB dans ledit liquide de refroidissement diélectrique intermédiaire dépasse 0,50
ppm de PCB par jour sur la base du poids dudit fluide de refroidissement diélectrique
permanent; et
(f) à remplir ladite cuve d'un fluide de refroidissement permanent, sensiblement sans
PCB, choisi dans le groupe constitué d'huiles siliconées à haut point d'ébullition
et haute viscosité, de fluides à base d'esters synthétiques, des huiles poly-alpha-
oléfiniques et des huiles hydrocarbonées afin de reclasser dans un état non- PCB ledit
appareil électrique.
2. Procédé selon la revendication 1, dans lequel le liquide de refroidissement diélectrique
intermédiaire est du trichlorobenzène, du tétrachloroben- zène ou des mélanges de
ceux-ci et le fluide de refroidissement permanent est un fluide diélectrique de refroissement
à huiles siliconées.
3. Procédé selon la revendication 1 ou 2, dans lequel chaque étape (c) est prolongée
pendant 20 jours à 1 an ou 30 à 120 jours ou 45 à 90 jours.
4. Procédé selon les revendications 1 à 3, dans lequel, lors de l'exécution de l'étape
(d) du cycle précédent et de l'étape (b) du cycle immédiatement suivant, le liquide
de refroidissement intermédiaire est vidé du sommet de la cuve tandis qu'un liquide
de refroidissement diélectrique intermédiaire refroidi et frais est introduit dans
le fond de la cuve et que le fonctionnement électrique de l'appareil se poursuit.
5. Procédé selon les revendications 1 à 4, dans lequel les étapes (d) et (f ) sont
effectuées par l'introduction du fluide de refroidissement permanent, sans PCB, dans
le fond de la cuve tandis que le liquide de refroidissement diélectrique intermédiaire
présent dans la cuve est retiré du sommet de ladite cuve, et que le fonctionnement
électrique de l'appareil se poursuit.
6. Procédé selon les revendications 1 à 5, dans lequel la cuve est équipée d'un isolant
thermique afin d'élever la température du liquide de refroidissement diélectrique
qu'elle contient durant chaque étape (c) pendant que ledit appareil à induction électrique
fonctionne.
7. Procédé selon les revendications 1 à 6, dans lequel le liquide de refroidissement
diélectrique intermédiaire présent dans la cuve est chauffé pendant l'étape (c) pendant
que l'appareil à induction électrique fonctionne.
8. Procédé selon les revendications 1 à 6, dans lequel, durant l'étape (c), le liquide
de refroidissement diélectrique intermédiaire est retiré de ladite cuve, chauffé et
renvoyé à ladite cuve tandis que suffisamment de fluide diélectrique intermédiaire
est maintenu dans ladite cuve et que ledit appareil à induction électrique fonctionne.
9. Procédé selon les revendications 1 à 8, dans lequel le liquide diélectrique intermédiaire
est plus volatil que les PCB et est séparé des PCB contenus par distillation du liquide
diélectrique de refroidissement intermédiaire.
10. Procédé selon les revendications 1 à 8, dans lequel le liquide de refroidissement
diélectrique intermédiaire contenant des PCB élués à partir de l'isolant solide est
retiré de la cuve sous forme d'un courant décalé tandis que l'appareil à induction
électrique fonctionne et qu'un liquide de refroidissement diélectrique intermédiaire
frais est ajouté en quantité sensiblement équivalente à celle du fluide diélectrique
intermédiaire contenant des PCB retiré dans le courant décalé.
11. Procédé selon l'une des revendications 1 à 10, dans lequel la cuve est rincée
avec un solvant pour les PCB après l'étape (a) et avant l'étape (b).
12. Procédé selon la revendication 11, dans lequel le solvant de rinçage est le même
liquide que le liquide de refroidissement diélectrique intermédiaire utilisé à l'étape
(b).
13. Procédé selon la revendication 11, dans lequel le solvant de rinçage et le liquide
de refroidissement diélectrique intermédiaire sont du trichlorobenzène.
14. Procédé selon les revendications 1 à 12, dans lequel le liquide de refroidissement
diélectrique intermédiaire est du 1,2,4-trichlorobenzène ou un mélange de trichlorobenzène
et de tétra- chlorobenzène.
15. Procédé selon les revendications 1 à 14, dans lequel le fluide de refroidissement
permanent utilisé pour remplir la cuve est une huile siliconée.
16. Procédé selon la revendication 15, dans lequel le fluide de refroidissement permanent
utilisé à l'étape (f ) est une huile siliconée ayant la formule suivante:

dans laquelle n est un nombre d'une valeur telle qu'une viscosité d'environ 50 mm
2/s à 25° C est établie.