[0001] The present invention concerns a process and a installation. The process is to be
used in conjunction with the process and installation described in
European Patent No. 2,692,701. We shall call the installation described in the
EP 2,692,701, Radiant, as it is an energy production concept that combines a Power Plant (PP)
with a Waste Water Treatment Plant (WWTP). The present invention refers to a transport
concept and we shall call it Conexant and it applies to a six train FWSG as described
in
EP 2,692,701, or a population equivalent between 280-2,236.
[0002] The most important feature of the concept it derives from the existence of a seasonal
energy surplus and a seasonal energy deficit for Radiant plants as well as for photovoltaic
energy production of an agglomeration, Connexant being used for the transport of both
energies. In conclusion, Conexant keeps the principle of the Radiant plant which is
to use the energy produced in summer during the winter, but applies it to pairs of
plants located at antipodes and therefore with seasons in opposition.
[0003] Conexant may also transport other energy sources like nuclear, hydro and wind power,
but the the subsequent development strategy however will be for only two main sources
of energy: biomass (Radiant) and photovoltaic energy (at consumer level). Those sources
of energy are complementary in respect to availability: one is available all the time,
and the other only in the daytime. The energy compensation has two main tipes: seasonal
and diurnal. We shall present them both.
[0004] The seasonal compensation for the warm season in northen hemisphere is presented
in Figure 1. During the warm season (between the spring and autum equinox) there will
be an energy transfer from parallel 46.9991 (EPSG 4326) to parallel -26.2185 (EPSG
4326). The same energy transfer will be made during the cold season (in the northern
hemisphere), only this time from the parallel - 26.2185 (EPSG 4326) to the parallel
46.9991 (EPSG 4326). In this situation, presented in Figure 2, the energy transfer
is made from the tropical zone to the temperate zone. The difference in latitude will
be felt by a higher energy intensity per square meter for the southern hemisphere.
However, more photovoltaic installations will be needed in the southern hemisphere
to compensate for the much higher energy consumption imbalance in the northern hemisphere
(proportional to the asymmetry in population distribution).
[0005] The six points are retransmission centers. The energy in that area is received and
passed on under the seasonal compensation schemes. The positioning of each of the
6 retransmission centers was established by an algorithm. Positioning accuracy is
in the tens of thousands of degrees (approximately 10 meters). The algorithm will
be presented below. The presentation of the 6 points and the geographical equator
is made in Figure 3.
[0006] The numbering of the points is from 1 to 6 starting from the top left, ending in
the bottom right in the up-down, left-right directions. We will start by presenting
the algorithm for establishing the points on the main meridian or meridian 3-4. This
is the one that crosses Europe and Africa. The algorithm for establishing points 3-4
has three stages. The first of these was the one in which the meridian was determined,
with the property that the intersections with the land areas have, in sum, the longest
length. Also in the first stage, the maximum of the meridian + antimeridian intersections
with the land was calculated. The result was identical to the first calculated maximum,
namely the merdian 22.5565 (EPSG 4326). The second stage was to establish the parallel
whose intersections with the land areas have, in sum, the longest length. The result
was in North Africa, 30.4382 (EPSG 4326) and is called the main parallel. The first
two steps are shown in Figure 4.
[0007] In the third stage, the parallel with the maximum land at the north of the main parallel
(global maximum) was determined as well as the parallel with the maximum land south
of the main parallel (local maximum but global for Australia). These are, as already
mentioned, 46.9991 (EPSG 4326) and -26.2185 (EPSG 4326). The parallels will be called
the northern parallel and the southern parallel. The two previously determined parallels
will determine the existence of a "false equator" in the middle of the distance between
them. This is important because it separates the Radiant power plants that will transmit
to a retransmission center or another diametrically opposite. The false equator will
be present in all the images that follow from now on. The parallels and the false
equator are in Figure 5
[0008] . The algorithm for determining the western meridian or meridian 1-2 consisted of
the following steps: establishing point 1, establishing point 2.
[0009] Point 1 resulted from the intersection of a meridian with a parallel. The merdian
was the one that intersects the maximum land between the false equator and the North
Pole, on the North American continent. The parallel was the northern parallel. The
resulting point is: -98.0063; 46.9991 (EPSG 4326). The same procedure was applied
with point 2. The difference was that the meridian intersected the maximum land between
the equator and the South Pole, on the South American continent, and the parallel
was the southern one. The resulting point is: -69.4974; -26.2185. The determination
of meridian 1-2 is shown in Figure 6. The algorithm for establishing the eastern meridian
or meridian 5-6 consisted of the following steps: establishing point 5, establishing
point 6. Point 5 resulted from the intersection of a meridian with a parallel. The
merdian was the one that intersects the maximum land between the false equator and
the North Pole, on the Asian continent. The parallel was the northern parallel. The
resulting point is: 103.7923; 46.9991 (EPSG 4326). The same procedure was applied
with point 6. The difference was that the meridian intersected the maximum land between
the equator and the South Pole, on the Australian continent, and the parallel was
the southern one. The resulting point is: 142.1776; -26.2185 (EPSG 4326). The determination
of the meridian 5-6 is presented in Figure 7.
[0010] The daytime compensation scheme equals the differences between the photovoltaic energy
produced during the day and that produced during the night. For daytime compensation,
in addition to the meridians, the diagonals were taken into account. Distances between
points. including the diagonals are listed below. Seasonal are the distances 1-2,
3-4, 5-6, the rest beeing composite.
Link |
Distance (m) |
Link |
Distance (m) |
Link |
Distance (m) |
Link |
Distance (m) |
1-2 |
8,600,095 |
3-5 |
5,879,029 |
2-6 |
13,287,425 |
2-3 |
12,240,351 |
3-4 |
8,108,189 |
4-6 |
11,326,092 |
6-3 |
14,308,444 |
1-6 |
14,323,267 |
5-6 |
8,978,985 |
2-4 |
8,958,424 |
4-5 |
11,470,642 |
2-5 |
17,624,493 |
1-3 |
8,100,491 |
1-5 |
9,376,473 |
4-1 |
14,380,011 |
|
|
[0011] The largest diagonal is 2-5. Its distance is the maximum distance for which the 6
retransmission centers are dimensioned. Alternatively a pair of new retransmission
centers (with retransmission from other centers only) may be positioned in the Pacific
Ocean.
[0012] Figure 8 is the daytime compensation scheme for 12/21/2017 11:28 PM UTC. The (civil)
night areas are the areas marked with transparent gray.
[0013] Figure 9 is the daily compensation scheme for 21.06.2018 23:06 UTC. Here the retransmission
center, which is in the hot season and which releases energy during the night (3),
is powered by the hydrogen reserve of the Radiant plant. Conexant has 3 levels of
power supply:
- base load - when Conexant delivers from the hydrogen supply,
- peaking mode 1 - when within 5,000 km (for 0-3.5 hours) the energy is delivered directly
in peer to peer mode (without retransmission), direct daytime offset.
- peaking mode 2 (peaking 2) - when it can no longer be supplied in peaking 1 it is
delivered at a fixed point (retransmission center).
[0014] Figure 10 is the daytime compensation scheme for 21.03.2018 22:30 UTC (after the
spring equinox). All six retransmission centers may be positioned within a 70 kilometers
radius away from the points mentioned above. The coordinates precision is 10 meters
for theoretical purposes only. The same observation goes for the starting/ending time
of the warm seaseon which may be with an additional 0-40 days delay, depending on
global wheather forcasts, according to an separate alghoritm that will be established.
Also theoretical is the assumption of intersecting the maximum land surface. This
assumtion is made with respect to a population that will be distributed evenly in
villages that have an an average of 2.236 population equivalent, that is the maximum
capacity of a Radiant FWSG.
[0015] This Patent purpose is not to be a design manual. The processes described in
US Patents No 593,198 (filled on 27/03/1897),
645,576 (filled on 02/09/1897),
649,621 (filled on 19/02/1900),
787,412 (filled on 16/05/1900),
1,119,732 (filled on 18/01/1902) are linked with a phenomenon that Tesla envisioned and shall be called Wireless
in Tesla's Sense (WTS). WTS is to be applied following the Patents and all his lectures
and articles. The prior art mentioned is cronologically ordered so will shall mention
the features that remain from older Patents. Besides WTS which is coherent in all
priror art mentioned, there are two distinct stages in the Patents: one of a smaller
potential and scale experiments and the other, after the return from Colorado Springs
in January 1900, of a greater potential and scale, the ready to build stage. And as
we already mantained there are three levels of Conexant link-up (in both senses):
- level 1 from the household to the Radiant FSWG or from FWSG's reserve;
- level 2 from the FWSG to the retransmission centers or between 2 FWSG's;
- level 3 between retransmission centers.
Tesla built level 1, experimental transmitters, then the prototype he tried to put
in operation was a level 2 for which he secured a reserve by making bigger the storage
capacity of the condenser. So, having in view that in the present patent we deal with
the whole system we shall mention only the differences and as already stated the features
that remain from older patents.
[0016] The first feature, presented in
US 593,138 is the conical spiral coil. Tesla used for the prototype an undeground structure
that used the deep aquifers with very deep shafts. For level 1 which is used at a
range of 0-5 km and with transmitters at every house hold, we intend to use close-to-surface
waterflows, namely wastewater. For this the grounding will be something like a cross
formed by two semi-elipses intersected and conected to a central conductor, like an
inversed lightning-protector from Figure 5
US 1,266,175 (filled by Tesla in 06/05/1916). And between excitation coil at the household and the grounding cross, the wastewater
pipe will be positioned. Besides using the close to surface waterflows, this design
is electrical shock hazard free. In respect with the conical spiral coil we have a
new winding geometry for the single layer coil, named Io, based on the following equations:

and

[0017] Where the general equation of the winding, Io, is the reunion of G1 and G2 parametric
curves with
t (real number) beeing the parameter,
r (real number) beeing the scale factor and
k (natural number) beeing the closeness factor. The general equation curves for
r=
1, k=
1 and
t ∈ [-2,2] are in Figure 11 and Figure 12.
[0018] The two curves describing the winding have all points in the surface of two Gabriel's
horns or they are enveloping the surface of two rectangular hyperbolas rotated around
their asymptotes. The bigger is the closeness factor
k, the greater is the number of spins of the windings that are on the same Gabriel's
horn. The biggest number of spins of each winding is around the vertex of the hyperbola.
The bigger is the scale factor
r the greater the diameter corresponding to the vertex, in other words the scale factor
can be used for dimensioning a winding by transforming
x(t), y(t) and
z(t) in axis for measuring real lenghts.
[0019] Io can be used in the case of a homopolar generator (HPG) or a homopolar motor (HM),
the space between the windings being the transfer surface which can also use new methods
for transfer from a stationary to a rotating system. The rotor will also have a corresponding
stator. The original idea for this HPG is mentioned in Nikola Tesla's article from
"
The Electrical Engineer", N.Y, Sept. 2, 1891.
[0020] Regarding the use in Conexant concept, the use of G1 and G2 will be restricted to
only one of them, G2 will be used only in the northen hemisphere, Figure 11 rotated
clockwise until
x = -∞ is at the top of the page and G1 will be used in the southern hemisphere, Figure
11 rotated counterclockwise until
x = -∞ is at the bottom of the page.
[0021] In conclusion, the secondary conical coil presented in Figure 1 and Figure 2 of the
patent
US 593,138 will be replaced by G1 or G2, depending of the Earth's hemisphere. The curve of the
secondary winding will be equally distanced from the hyperbola's vertex. The primary
winding will be at the base of the secondary on a slightly bigger diameter corresponding
to the vertex, and it will be calculated using a bigger scale factor. The second secondary
coil presented in
US Patent 1,119,732 will remain as it is. The frequncies will be: level 1- greater or equal to 7.83 Hz,
level 2-greater than 7 kHz, level 3-greater than 2 Mhz and flywheels may be used at
all levels for momentary storing the energy. For opening comunication channels phase-shifting
will be used.
[0022] Furthermore from the "state of the art" which is presented in Tesla's Patents lectures
and articles there are no other observations. Nevertheless WTS implies a great importance
given to:
- total length of the secondary circuit which is approximately one-quarter of the wave
length of the electrical disturbance in the circuit which can be achevied at low frequencies
by using thin graphene-infused copper wires;
- very large self-inductance and a comparatively small capacity;
- if necessary, for predimensioning the secondary coil, the calculus of hyprebola lenght
by means of ellipic integrals, in order be divided to an wire diameter and also the
total lenght of G1 or G2 coil wire;
- inductance calculations formulae for variable-pitch multi-section helical coils by
means of elliptic integrals;
- capacitance to ground calculation formulae for sphere or toroid also by means of elliptic
integrals.
1. Process for transporting energy that derives from the existence of a seasonal energy
surplus and a seasonal energy deficit from a biomass cumulated with a solar production
concept, applied to pairs of plants located at antipodes but also to pairs of plants
located on different meridians (sesonal and diurnal) named Conexant.
2. At least six installations for retransmission (retransmission centers) located on
the world map (EPSG 4326) two to the left and two to the right of a zero meridian
(that has the maximum land intersected by the meridian and antimeridian) and three
on the upper side with three on the bottom side of an false equator which is determined
first, by finding a main parallel that intersects the maximum land and then by finding
two parallels that intersect the maximum land, one at the north of the main parallel
and one at the south of it and then dividing the distance between them by two, after
which the two points of the zero meridian are established by the north and south parallels
and the rest of four points are found by intersecting the meridian of maximum land
between the North pole and the false equator with the north parallel on the North
American continent, by intersecting the meridian of maximum land between the South
pole and the false equator with the south parallel on the South American continent,
by intersecting the meridian of maximum land between the North pole and the false
equator with the north parallel on the Asian continent and by intersecting the meridian
of maximum land between the South pole and the false equator with the south parallel
on the Australian continent.
2. Three levels of power supply: Base Load - when Conexant delivers from the hydrogen
supply, Peaking Mode 1 - when within 5,000 km (for 0-3.5 hours) the energy is delivered
directly in peer to peer mode (without retransmission), direct daytime offset, Peaking
Mode 2 (peaking 2) - when it can no longer be supplied in Peaking 1 it is delivered
at a fixed point (retransmission center) which correspond with three levels of Conexant
link-up (in both senses): Level 1 from the household to the Radiant FSWG or from FWSG's
reserve, Level 2 from the FWSG to the retransmission centers or between 2 FWSG's,
Level 3 between retransmission centers.
3. Level 1 is using close-to-surface waterflows, namely wastewater for which the grounding
will be a cross formed by two semi-elipses intersected and conected to a central conductor,
like an inversed lightning-protector from Figure 5 US 1,266,175 (filled by Tesla in
06/05/1916) and between excitation coil at the household and the grounding cross,
the wastewater pipe will be positioned.
4. The Io geometry which is the reunion of the parametric curves

and

with
t (real number) beeing the parameter,
r (real number) beeing the scale factor and
k (natural number) beeing the closeness factor. Io may can be used in the case of a
homopolar generator (HPG) or a homopolar motor (HM), and G1 alone can be used in Conexant
in the southern hemisphere whereas G2 alone can be used in Conexant in the northen
hemiphere, both as the first of the two single layer secondary coils.